Tender For Provn Of Switch Gear, special Repair To Vcb, Ht Cable And Connected Works Under Ge Hisar
Tender Value
1.23 Crore
Estimated cost
Bid Submission
29 Aug 2026
24 days left
EMD
1.98 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Hisar → Haryana
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Switch Gear, special Repair To Vcb, Ht Cable And Connected Works Under Ge Hisar
BOQ
| Sl. No. | Item Description |
| 1 | Supply and laying in replacement, testing and commissioning of HT Underground XLPE insulated, screened PVC bedded galvanized steel strip armoured electric power cable (heavy duty) with aluminium conductor 11 KV grade (Earthed) of sizes 3 Core 185 Sqmm cable comfirming to IS-7098 Pt-II cable laid in trenches / walls / ducts / poles including taking out the old one complete all as specified and directed |
| 2 | M&L in replacement Cross Arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps stay clamps, D clamps, nuts, bolts, washers welding bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed. |
| 3 | M&L for Cable jointing kit in replacement for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm. |
| 4 | Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying of cable etc, and for foundation of poles, stays etc. not exc 10sqm on plan and getting out in soft / loose soil complete all as specified and directed. |
| 5 | M&L for sand cushioning to under ground cable in trenches / ducts in layers of 8cm deep before laying the cable and 15cm deep after laying and stretching the cable complete all as specified and directed. Note : Punned thickness shall be measured. |
| 6 | Supplying and laying in replacement un-reinforced precast concrete cable cover of class HV type 1 with flat size 300 x 180 x 40mm complete all as specified and directed. |
| 7 | M&L for returning filling in approved excavated soil including spreading levelling and well ramming in layers n.exc 25cm thick complete all as specified and directed. |
| 8 | M&L for removing surplus soil to a distance not exceeding 50 m & depositing at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 9 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine for laying underground pipe upto 150mm dia complete all as specified and directed. |
| 10 | Supply and fixing in replacement 100mm bore steel tube of light grade galvanised with all fittings fixed to walls / floors / poles or under road etc of following sizes complete all as specified and directed.Note : (i) The GI pipe should be fixed with pole by MS clamps.(ii) The MS work shall be measured and paid separately. |
| 11 | M/L for Demolition of path /concrete in ground floors and pavings (below or above ground level) .complete all as specified and as directed.Note : The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing for good make. |
| 12 | M&L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate in mass concrete and filling complete for foundation complete all as specified and directed. |
| 13 | Supply, installting, Commissioning & testing HT 11 KV, 3 Phase 50 Hz , rupturing capacity 350 MVA indoor type , VCB PANEL totally metal clad withdrawable type Vacuum Circuit Breaker including suitable as Outgoing , including cable connection with Copper busbar of suitable rating. horizontal isolation horizontal drawout type VCB of capacity minimum 630 Amps rated current, . The switchgear panel shall be made up of CRCA sheet steel duly powder coated or equivalant not less than 2.5mm thick and shall be totally dust and vermin proof. (a) Continous current rating minimum-630A.(b) Short circuit withstand current minimum 25 KA for 1 Sec.(c) Operating Mechanism of the VCB are suitable for 10000 Mechanical Operations (d) CT Ratio should be 200-100/5-5, core 1: Class 1 ,15 VA Core 2: 5P10. 15VA burden(e) Protection arrangements for the breaker shall comprise of the following:-(i) Each of the outgoing switchgear units shall be provided with over current (50/51) and earth fault (50N/51N) protection, the relay should have breaker failure (50BF), negative sequence overcurrent (46), broken conductor (46BC), under current (37) and inrush blocking (68) functions.The main protection relays should be SCADA compatible with IEC 61850 Edition 2 on 2 nos. FO ports. Relay should generate GOOSE message as per IEC 61850 standard for interlocking and also ensure interoperability with third party relays. |
| 14 | (g) Master Trip Relay(h) TCS Relay(j) Auxillary Relay(6 Elements)(k) The following meters, indications and acessories are to be provided with the panel.(i) Digital Ammeter with built in selector switch(l) Necessary Supply with powerpack, healthy indication lamp & switch.(m) Control:-(i) TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement.(ii) Local/remote selector switch for breaker open/close operations.(n) VCB Panels should be Manufactured, designed & supplied by OEM only.VCB Panels from the System houses are not acceptable. All the main components like VCB/Relays/VI should be of same manufacturer.Vacuum interrupter shall be of OEM Make only. VCBs should be supplied with Vacuum interrupter with which Type Testing is done .The offered panels shall be tested for IAC level of 25KA for 0.1Sec. VCBs should be Type Tested for E2/C2/M2 Class.All type test should be as per as per IEC 62271-100-2021 & IEC 62271-200-2021. Please Enable Macros to View BoQ information |
| 15 | (g) Master Trip Relay(h) TCS Relay(j) Auxillary Relay(6 Elements)(k) The following meters, indications and acessories are to be provided with the panel.(i) Digital Ammeter with built in selector switch(l) Necessary Supply with powerpack, healthy indication lamp & switch.(m) Control:-(i) TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement.(ii) Local/remote selector switch for breaker open/close operations.(n) VCB Panels should be Manufactured, designed & supplied by OEM only.VCB Panels from the System houses are not acceptable. All the main components like VCB/Relays/VI should be of same manufacturer.Vacuum interrupter shall be of OEM Make only. VCBs should be supplied with Vacuum interrupter with which Type Testing is done .The offered panels shall be tested for IAC level of 25KA for 0.1Sec. VCBs should be Type Tested for E2/C2/M2 Class.All type test should be as per as per IEC 62271-100-2021 & IEC 62271-200-2021. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 24 daysAug 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender