Tender For maintenance of Completed Scheme Under Na-Ii, South Zone. Sh:- Reconditioning, Servicing, Supplying, Installation, Testing & Commissioning Of Fire Fighting And Fire Alarm System At Community Hall Kishangarh, New Delhi
Tender Overview
Project Description
Tender for maintenance of Completed Scheme Under Na-Ii, South Zone. Sh:- Reconditioning, Servicing, Supplying, Installation, Testing & Commissioning Of Fire Fighting And Fire Alarm System At Community Hall Kishangarh, New Delhi
BOQ
| Sl. No. | Item Description |
| 1 | Removing, checking, overhauling, reconditioning, servicing of the 72 HP diesel engine driven pump set including cleaning, oiling, greasing, replacement of mobil oil, necessary repairs of internal defective parts, alignment of shaft as required, checking fixing internal wiring and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional complete as required. |
| 2 | Supply, installation, testing & commissioning of 12V 12Ah lead acid Battery including interconnecting cables using lugs, thimbles etc. for DG set complete as required. |
| 3 | Removing, checking, overhauling, reconditioning, servicing of the Electric driven Main pump set 60 HP including cleaning, oiling, greasing, necessary repairs/replacement of internal defective parts, alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode of the Main pump set to make it functional as per Delhi Fire Service requirements. |
| 4 | Checking, overhauling, reconditioning, servicing of the Jockey pump 12.5 HP including cleaning, oiling, greasing, necessary repairs/replacement of internal defective parts alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 5 | Removing, checking, Overhauling, reconditioning, servicing of the terrace pump 12.5 HP including cleaning, oiling, greasing, necessary repairs of internal defective parts, alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 6 | Reconditioning, overhauling, servicing, cleaning of existing installed 150 mm Control Valve including repairs of internal defective parts i.e, water motor alarm, bronze seat clapper, clapper arm, nut, bolts, oiling, gaskit, tracing leakages & repairing so as to make them in proper functional condition etc complete as required as per site requirement. |
| 7 | Providing & replacement of pressure switch in M.S. pipe line including connection etc. as required. |
| 8 | Checking, servicing, repairing as required, testing & commissioning of existing 80 mm Cast iron double flanged non return valves including repairs of internal defective parts as required, greasing, oiling, so as to make them in proper working condition etc. complete as required. |
| 9 | Supplying, replacing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :80 mm |
| 10 | Supply, replacing, Testing and Commissioning of pressure gauge including all accessories complete as required.. |
| 11 | Supplying and replacement of single headed internal hydrant valve with instantaneous Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Stainless Steel cap and chain as required. |
| 12 | Reconditioning, overhauling, servicing, cleaning of existing installed hydrant valve including repair of internal defective parts, oiling, gaskit, tracing leakages, checking for leakages and repair of pipe connection with GI Fittings, painting so as to make them in proper functional condition etc. complete as required as per site requirement. |
| 13 | Supply, installation, testing and commissioning of PVC shut off nozzle complete as required. |
| 14 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 15 | Supplying & fixing 63 mm dia stainless steel short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 16 | Painting of all size of MS pipe with two coats of primer and enamel paint of required shade after cleaning the pipes surface of following size complete as required. |
| 17 | 150mm dia |
| 18 | 100mm dia |
| 19 | 80mm dia |
| 20 | 50mm dia |
| 21 | 25mm dia |
| 22 | Supplying and Fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required:4 Way |
| 23 | Supplying, Fixing, Testing and Commissioning of 100 mm dia draw out connection screw type with 100 mm dia C.I. Foot valve complete with nut-bolt, rubber gasket, complete, etc. as required. |
| 24 | Supply, Installation, Testing and Commissioning 25 mm Air release valve, having threaded connection including the cost of required fittings as per standard design complete in all respect. |
| 25 | Reconditioning, servicing, testing & commissioning of exhaust air starter panel including repair/replacement of defective parts, checking and replacing the worn out, burned wires, including the connection through bus bar / copper conductor flexible connection with all accessories so as to make the fans in fully functional. The job includes testing commissioning of the same complete in all respects. |
| 26 | Supplying, installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required.10 Zone panel for fire alarm system 250 Watt amplifier racks suitable for operation on 230V AC/24V DC supply conforming to IEC-268-3 complete with all accessories as required - 2 Nos.(one to act as standby) Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24 V DC supply conforming to IEC-268 for simplex mode of operation/communication suitable for 20 Nos.talk back unit -1 set. Announcement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc. complete as required -1 set.Amplifier change over switch for inter changing amplifier -1 No.Monitor panel for loudspeaker complete with output selector, ON/OFF switch, fuse, visual indications etc. complete as required- 1 No.Gooseneck microphone with stand and ON/OFF switch- 1 No.Main ON/OFF switch, fuse indication lamps, DC and AC voltmeters & ammeters, terminal blocks etc. complete as required -1 set.Battery charger trickle cum boost to take complete load of fire alarm & PA system complete with all accessories including providing & fixing of 2 nos.12 volt, 60 AH each sealed maintenance free batteries -1 set. |
| 27 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 28 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 29 | Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 30 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 31 | Restructuring, Reprogramming & Readdressing of \\"Agni\\" make conventional 10 zone Fire Alarm System by Agni certified Engineer consisting of existing devices viz smoke detector, Heat Detector, Manual Call point, sounder etc. including checking for faults in loop wiring of all devices and fixing of the same, tracing for defective/ non-functional devices and repairing/replacing so as to make system fully functional complete as required. |
| 32 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 33 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.20 mm Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender