Tender For Thorough Rewiring Of The Room Labelled As Cu Cash Counterat Ground Floor Of N.R Sen Building,Rajabazar Science Building For The Installation Of X-Ray Defractometer Under Rusa 2.0 Grant, University Of Calcutta.
Tender Overview
Project Description
Tender for Thorough Rewiring Of The Room Labelled As Cu Cash Counterat Ground Floor Of N.R Sen Building,Rajabazar Science Building For The Installation Of X-Ray Defractometer Under Rusa 2.0 Grant, University Of Calcutta.
BOQ
| Sl. No. | Item Description |
| 1 | Distribution wiring in 2x22/0.3(1.5sq.mm) single core stranded FR PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit FR with 1x22/0.3(1.5sq mm) single core stranded \\"FR\\" PVC insulated…………..Modular type switch fixed on MOD GI switch board ....2no suitable size ph& N...original finish a) Ave run...8mtr. |
| 2 | Distribution wiring in 1.1KV grade 22/0.3(1.5sq.mm)single core stranded FR PVC insulated &unsheathed copper wire in 20mm size pvc rigid conduit FR with 1.1KV grade 1x22/0.3(1.5sq.mm)…to 6A 3pin mod type plug socket & switch on 4mod GI switch board…..building works a) On Board |
| 3 | S&F 240V ,16A 3pin mod type plug socket with 16A mod type switch without plug top on 4 mod GI mod type switch board…..continuity wire etc |
| 4 | S&F240V 4nos 6A 3pin mod type plug socket with 4nos6A mod type switch,16A mod switch type MCB…2row 18 mod top cover…..continuity wire etc |
| 5 | Disrtibution wiring in 1.1KV single core stranded FR PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit FR…as required 2x22/0.3(1.5sq.mm)+ 1x22/0.3(1.5sq.mm) ECC |
| 6 | 2x56/0.3(4sq.mm)+1x36/0.3(2.5sq.mm)ECC |
| 7 | d)2x84/0.3(6sq.mm)+1x56/0.3(4sqmm) ECC |
| 8 | b)2x36/0.3(2.5sq.mm)+ 1x22/0.3(1.5sq mm)ECC |
| 9 | S&F D/D horizontal TPN MCB DB with IP42/43…with neutral link & provision for earthing attachment 8way,Legrand,Schneider,L& T |
| 10 | S & F240/ 415V MCB isolator on DIN rail of existing DBs & necy connection 100A DP, Legrand,Schneider,L&T |
| 11 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection i]SP 6-32Amps Make Legrand |
| 12 | ii] DP 32A Make Legrand |
| 13 | iii]DP25A Make Legrand |
| 14 | iv]DP16A Make Legrand |
| 15 | v]DP 6A Make Legrand |
| 16 | S and fixing 240V 25A modular type socket,25A modu-lar type starter,25A modular switch type DP MCB ,6 m-odule GI switch board,cpver plate,..making necy,co-nnection with copper wirw ,earth continuity wir |
| 17 | Fixing only single/Twin fluorescent light fitting complete with all accessories directly on wall / ceiling/HW round block & suitble size MS fastner |
| 18 | Supplying of luminaires which are as follows compact LED light fitting 4ft,20W ,Philips/CG/ polycab or equivalent make |
| 19 | D)Supply & fixing of ceiling fan 1200 mm(48\\") IS 374:2019 withBLDCmotor, incl down rod upto 1500mm,minimum air delivery 210m3/min 3star BEE rating with service value >4.1 to<5.1,Orient , summer cool, bolt,crompton greaves Havells, or equivalent make [2X Dia] |
| 20 | supplying &Laying of cable as below on existing cable tray & binding with suitable GI wire…of PVc Arm.cable with AL.conductors 1.1 kv grade conforms to IS:1554(part 1)for following cross section a)1x35sq.mm 3.5C [ GF Panel to HDB] |
| 21 | S& F compression type gland with brass gland,brass ring,rubber ring for dust & moisture proof entry..as below& fixing only the end with dowels make socketaa)1x35sq.mm 3.5C |
| 22 | Fabricating and SITC of 6KW 240/415Vcapacity of airconditio-er factory made Timer control panel IP54 prot-ection along with astronomical timer,32A DP Conta-ctor,40Amp DP MCB earthing studd,detachable gla-nd plate internal wiring to be fixed on the wall. |
| 23 | S & F MCB SS encl with IP-2/30 protection,powder coated provision for 2 pole MCB 7 provision for earthing. |
| 24 | Earthing with 50mm dia GI pipe 3.64mm thick & 3.04 mm long & 1x4SWG GI wire 4mtr long 13mm dia & 80mm long GI bolt double nuts & double washers incl S&F15mm dia GI.pipe protection partly filled with Bitumen ….as below By ISI medium GI pipe |
| 25 | Excavation of soil for installation of earth electrode & filling & ramming a) for soft soil |
| 26 | Extra for providing masonary enclosure on the top of the earth electrode overall size 86.36x86.36x46 cm deep……. GI pipe |
| 27 | S & F earth busbar of galvanized MS flat of 25x6 mm on wall having clearence of 6mm incl providing of drilled holes…….as required |
| 28 | connecting the equipment to earth busbar incl S& F GI wire of size as below on wall staples inside wall as reqd & making connection with equipments with nut bolts etc & mending good damages. 10SWG |
| 29 | Labour charges for dismantling the existing wirings,fitting & accessories & depositing the same to the authority Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender