Tender For Providing New Electric Connection Of 4Mw For D.T.C Bus Depot, Sarojini Nagar New Delhi
Tender Value
3.41 Crore
Estimated cost
Bid Submission
25 Aug 2026
11 days left
EMD
6.83 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing New Electric Connection Of 4Mw For D.T.C Bus Depot, Sarojini Nagar New Delhi
BOQ
| Sl. No. | Item Description |
| 1 | Supply of 11KV 800 A VCB switchgear panels Incoming Panel as per the Technical Specifications |
| 2 | Supply of 11KV 800 A VCB switchgear panels Outgoing Panel as per the Technical Specifications |
| 3 | Supply of 11KV , 800 A VCB switchgear panels Bus Coupler Panel with Bus Riser as per the Technical Specifications |
| 4 | Providing and Fixing of Battery Charger Unit along with Li- batteries complete in all respect as per site requirement for 110V DC , Capacity -100 AH |
| 5 | Supply of 11KV XLPE Aluminium Cable of size 400sqmm/3C as per the Technical Specifications |
| 6 | Cartage, Installation, Testing and Commissioning of 11 KV HT VCB Panel complete in all respect as per site requirement. |
| 7 | Providing conductive concrete earth grid of 2 Nos. interconnected earth electrodes with installation & Testing connection including connection with application-Normal Soil earthing to deliver earth results not exceeding 2 Ohms for sub station equipment i.e 11KV Panel Board SPECIFICATIONS a) Earth Electrodes :- Metal Electrode Cu-Bonded MS road Size : Dia 60mm (+-0.5mm), Length - 3 Mtrs with enhanced conductive concrete embedding size dia :100mm Length 3 Mtr. of each earth electrode b) Interconnecting strip :-All the 2 Electrodes of the grid will be horizontally inter-connected with metal conductor : Cu Bonded MS Flat size 50mm X 6 mm & enhanced conductive concrete embedding size 75sqmm buried at 600mm below the ground level c) Test Links :- Test Links Cu-Bonded MS Flat of size : 50mm X 6mm shall be provided , one no. at any of the two electrodes for the grid for the connection between earth grid pit and the application d) Pit Covers :- RCC Pit Cover frame at size 300mm X 300mm shall be provided at two earth electrodes |
| 8 | Providing and Fixing 25mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required. |
| 9 | Providing & Fixing of 25 mm x 5 mm G.I. Strip in 40mm GI Pipe from earth electrode including connection with brass, nut, bolt, spring washer excavation and refilling as required, complete in all respect as per site requirement. |
| 10 | Providing and Fixing of synthetic insulating mat 2.5 mm thickness and 1 Mtr width suitable for 11 KV HT Panel board ISI marked having di-electric strenght 45 KV, confirming to IS 15625:2006, complete in all respect as per site requirement. |
| 11 | Supplying and laying of ISI marked XLPE insulated, sheathed, armoured, copper conductor of size 2.5 sq.mm/10 C control cable for working voltage upto 1.1 KV in recess/on surface/in G.I. pipe/cable trays etc from energy meter box to HT panel complete in all respect as per site requirement. |
| 12 | Supplying and laying of ISI marked PVC insulated, sheathed, armoured, copper conductor of size 2.5 sq.mm/4 C control cable for working voltage upto 1.1 KV in recess/ on surface/ in G.I. pipe/cable trays etc from Battery Tripping Unit to HT panel complete in all respect as per site requirement. |
| 13 | Providing and Fixing of Meter Box for 3-phase energy meter of suitable size along with Test Terminal Block (TTB) fabricated from 1.6 mm MS sheet duly powder coated including Providing and Fixing bakelite sheet of suitable size with locking arrangement, complete in all respect as per site requirement. |
| 14 | Supplying and Fixing Fire Extinguisher CO2 (4.5 Kg) complete in all respect as per site requirement. |
| 15 | Supplying and Fixing of First Aid Box complete in all respect as per the site requirement |
| 16 | Supplying and Fixing of First Aid Chart, laminated in wooden frame complete in all respect as per site requirement. |
| 17 | Supply & fixing of cable Boots suitable for 11KV , CABLE of size upto 400sqmm for each phase as per site requirement Make: 3M/Raychem/Cabseal/Denson |
| 18 | Supply & fixing of Caution Boards of size ( 1 X 1 Feet) as per site requirements |
| 19 | Design, Providing & fixing of single Line Diagram of ESS & Inventory Board in Glass/Polycarbonate Frame of size ( 2 Feet X 2 Feet ) on wall with nutbolts etc. with provision of removable Drawing sheet complete in all respect as per the site requirement |
| 20 | Supplying and Fixing Fire Buckets ( 2 Nos. ) with stand complete in all respect as per the site requirement . |
| 21 | Supplying & Fixing of ESS Name Plate in 3mm ACP( Aluminium Composite Panel) sheet with pasting digital ECO Vinyl Paint reflective component of size 3 X 2 Feet along with Aluminium frame and hook for hanging purpose as per the site requirement |
| 22 | Laying of XLPE insulated 11 KV grade H.T cable of size 400 Sqmm. 3C direct in ground including excavation, sand cushioning, protective covering & refilling the trench as per |
| 23 | Handling/Laying of XLPE insulated 11 KV grade H.T cables of sizes 400 Sqmm. 3C which are not necessarily laid in ground but part of it going up to panel, transformer & part in the building in open trench or otherwise. |
| 24 | Drawing of XLPE insulated 11 KV grade H.T cables of sizes 400 Sqmm. 3C in existing RCC/HDPE Pipe, closed duct, subway or Sub Station. ) |
| 25 | Road cut of any thickness (metalled/concrete) for one HT cable Road Berm/Stone/Brick footpath/C.CSlab/Approach gate |
| 26 | Supply and laying HDPE pipes ISI marked PN-6 class of size 125 mm dia (OD) across Road/Service Road by Trench less Technology in various Roads/Service Road/Main Gate in NDMC area. |
| 27 | Supplying and making of straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for cable of size 400sqmm/3C XLPE aluminium conductor cable of 11KV grade as requiredMake : 3M/ Raychem/ Cabseal /Denson |
| 28 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for cable of size 400sqmm/3C XLPE aluminium conductor cable of 11KV Grade as required Make : 3M/ Raychem/ Cabseal /Denson |
| 29 | Ground Penetration Radar Survey (GPRS) for laying of 11 KV HT XLPE cable of size 400 Sq.mm/3C. |
| 30 | Supply and fixing of RCC Cable Route markers and joint markers made of 1:3:6 (1 cement, 3 course sand, 6 graded stone aggregate of 20mm nominal size) cement concrete , inclduing inscription duly engraved as per the site requirement . |
| 31 | SITC of 11 KV Indoor epoxy resin casted CT single wound for metering CT class 0.5p10 VA burden 5, short time current 18.4 KA/1 sec insulation level 12/18/75 KVP as per ISS 2705/1992 for 11 KV HT panel. (03 Nos. in One Set), complete in all respect as per site requirement. MAKE : AE/Kappa/Areva/Crompton/Savio/Hans |
| 32 | Add GST@18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysAug 25, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender