Tender For repair maintenance All E & M Services Installed At Dseu Maharani Bagh C Us, Meera Bai Institute Of Technology, New Delhi During Year 2026-27.
Tender Value
36.41 Lakhs
Estimated cost
Bid Submission
07 Aug 2026
6 days left
EMD
72831
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for repair maintenance All E & M Services Installed At Dseu Maharani Bagh C Us, Meera Bai Institute Of Technology, New Delhi During Year 2026-27.
BOQ
| Sl. No. | Item Description |
| 1 | SH-I: Providing staff and EI Works etc Operation and Routine Maintenance of 1x500 KVA 11/0.440KV electric Sub Station comprising of HT Panel, LT panel APFC panles, transformers, electric driven water supply pump and operation of 01No. 180KVA DG Set with AMF panel round the clock on all days i/c Sunday & Holidays as required. a) E&M Operator -03 Nos. (one no. in each shift)b) Khallasi:-01 No. (In General shift) |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | a) Group C |
| 4 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required. |
| 5 | a) Group C |
| 6 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | a) 20 mm |
| 8 | b) 25 mm |
| 9 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface / recessed steel / PVC conduit as required. |
| 10 | a) 3 x 1.5 sq.mm |
| 11 | b) 3 x 4 sq.mm |
| 12 | c) 3 x 6 sq.mm |
| 13 | Supplying of following items to be used during day to day maintenance |
| 14 | S.P. 5/6A one way Modular switch ISI marked. |
| 15 | S.P. 15/16 A one way modular switch ISI marked. |
| 16 | 3 Pin 5/6 A Modular Socket outlet ISI marked. |
| 17 | 6 Pin 15/16A Modular Socket outlet ISI Marked. |
| 18 | Bell Push modular type. |
| 19 | Stepped type modular fan regulator(2 module) |
| 20 | 3 pole MCCB, 100A, 16kA Ics=100% Icu and Operational Voltage 690V |
| 21 | 3 pole MCCB, 200A, 25kA Ics=100% Icu and Operational Voltage 690V |
| 22 | 4 pole MCCB,100A,30kA Ics=100% Icu and Operational Voltage 690V |
| 23 | 4 pole MCCB, 200A, 36kA Ics=100% Icu andOperational Voltage 690V |
| 24 | 6A, 32A, ratings, SP MCB, \\"C\\", curve, 10 KA braking capacity. |
| 25 | 63 A rating Double Pole isolator |
| 26 | 100A, 4 pole isolator |
| 27 | Supply of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 28 | Supplying of 300 mm sweep metallic heavy duty 900 rpm exhaust fan suitable for operation on 230V, 50 Hz single phase AC supply complete with louvers / shutters in the existing opening including making the hole to suit the size of the above fan making good the damage and connections etc. as reqd. |
| 29 | Supplying of fresh air fan 200 mm sweep with shutter and louver in the existing opeining , including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required. |
| 30 | Supplying 400mm sweep wall mounted cabin fan with speed regulator oscilatting type i/c testing & commsisioning suitable for 230volt 50Hz AC supply etc as reqd. |
| 31 | Supplying of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) a) 18-22watt |
| 32 | Supplying of LED Recessed / surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim a) 18 watt |
| 33 | Supplying of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.) Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) a) 36watt |
| 34 | Supplying of Panel light 1x4 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.) Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness >0.50 mm) a) 40watt |
| 35 | Supplying of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirementdeg., suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy 105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).a) 70 Watt LED Flood light. |
| 36 | 100 Watt LED Flood light. |
| 37 | Supplying of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). a) b) 90 Watt LED street light. |
| 38 | Supplying & Laying of following sizes of XLPE insulated and PVC sheathed aluminium conductor armoured cable in pipe/HUME/Surface as reqd. |
| 39 | a) 3 x 6 sqmm XLPE Al. Armoured cable |
| 40 | b) 3 x 10 sqmm XLPE Al. Armoured cable |
| 41 | c) 3.5 x 50 sqmm XLPE Al. Armoured cable |
| 42 | Preventive and routine maintenance contract of 180 KVA DG Set i/e Engine, Alternator installed at Meera Bai Institute of Technology Maharani Bagh, Complete etc as reqd. (Labour charges and freight charges only) |
| 43 | Supplying & Replacement of following parts with new one \\"B\\" check of 1 X180 KVA DG SET (Old materials shall be retained by the contractor) a) Filter Fuel - 01 b) Diesel Filter-01 No c) Gasket Cyl Head Cover-01 No d) Safety Element-01 No e) Primary Element-01 No f) Coolant Additive-10 Ltr- 01 No g) Lub Oil - 35 Ltr |
| 44 | Supplying and replacement of following unservicable/damaged spare parts of 1 X 6CTA,180 KVA, DG Set (Old materials shall be retained by the contractor) |
| 45 | a) Set of Hose |
| 46 | b) Set of Hose Clip |
| 47 | c) Flexible pipe |
| 48 | Supply & replacement of 12V 180 AH Genset batteries including buyback of old batteries |
| 49 | SH-III: Servicing and Maint. Of WTAC/STAC and Water Cooler Supply & Charging R-22/410/407/32/134a gas in the existing WTAC/STAC of 1.5/2.0 TR unit and water coolers i/c pressure testing, flushing the system and Gas Charging complete as reqd. |
| 50 | Supplying & Fixing 25 mm diameter PVC heavy duty pipe for drainage in the existing split type AC unit with supporting clamps etc . complete as reqd. |
| 51 | Supplying and fixing of Extra copper refrigerant piping of 5/8”, 3/8”, 1/4” i/c nitrile rubber insulation wrapping etc. complete as reqd. |
| 52 | Providing and fixing of 3 core 2.5 sqmm PVC insulated and PVC sheathed bright annealed copper conductor cable for communication between indoor unit/outdoor unit/controllers inside building in existing steel/PVC Conduit/ surface/ existing channel, i/c making connection etc as reqd. |
| 53 | Replacement of following capacity compressor in the existing WTAC/Split AC with new one and making copper pipe connection, brazing pressure testing and supplying and charging refrigerant gas i/c cutting the copper piping dismantling of the old compressor complete as Reqd. |
| 54 | a) 1.5TR capacity |
| 55 | b) 2.0TR capacity |
| 56 | Replacement of upto 1 TR capacity compressor in the existing water cooler with new one and making copper pipe connection, brazing pressure testing and supplying and charging refrigerant gas i/c cutting the copper piping dismantling of the old compressor complete as Reqd. |
| 57 | Supplying and replacement of wornout/defective copper condensor coil with new one in same size of design suitable for following capacity split type AC out door unit i/c breezing the all copper pipe with all distribution joints of make sure the connection with capiliary tube linking dryer duly proper etc pressure testing leak detection, vaccumizing the unit, gas charging etc complete as reqd. |
| 58 | a) 1.5/2.0TR capacity |
| 59 | Supplying and replacement of wornout/defective copper condensor coil with new one in same size of design suitable for following capacity window type AC i/c breezing the all copper pipe with all distribution joints of make sure the connection with capiliary tube linking dryer duly proper etc pressure testing leak detection, vaccumizing the unit, gas charging etc complete as reqd. |
| 60 | a) 1.5TR capacity |
| 61 | Supplying and replacement of wornout/defective copper cooling coil with new one in same size of design suitable for following capacity split type AC out door unit i/c breezing the all copper pipe with all distribution joints of make sure the connection with capiliary tube linking dryer duly proper etc pressure testing leak detection, vaccumizing the unit, gas charging etc complete as reqd. |
| 62 | a) 1.5/2.0TR capacity |
| 63 | Supplying and replacement of wornout/defective copper cooling coil with new one in same size of design suitable for following capacity window type AC i/c breezing the all copper pipe with all distribution joints of make sure the connection with capiliary tube linking dryer duly proper etc pressure testing leak detection, vaccumizing the unit, gas charging etc complete as reqd. |
| 64 | a) 1.5TR capacity |
| 65 | Replacement of non repairable inverter PCB in existing indoor/outdoor unit of STAC and WTAC complete etc as reqd. |
| 66 | Replacement of non repairable non inverter PCB in existing indoor/outdoor unit of STAC and WTAC complete etc as reqd. |
| 67 | Dismantling, shifting and reinstallating of existing 1.5TR/ 2.0TR capacity STAC (indoor and outdoor unit) including repairing the damaged caused due to dismantling within same office etc as required. |
| 68 | Providing & replacement WTAC/STAC fan motor Capacity 1/4 to 1/8 hp including dismantling the burnt motor from the existing unit & fixing of new motor, making connections testing, commissioning etc.as reqd. |
| 69 | Supplying and replacement of following defective spare parts in the existing AC unit with new one i/c connection testing etc. complete as required. |
| 70 | a) Running capacitor - 36 Mfd/45 Mfd |
| 71 | b) Starting capacitor- 80/100 Mfd |
| 72 | Supply and fixing of 15/16Amp 3pin top plug including connection complete as reqd. |
| 73 | Supplying and fixing stand for the outdoor unit of the STAC made of MS duly powder coated complete etc as required. |
| 74 | Preventive maintenance & servicing of WTAC/STAC unit and water cooler i/c cleaning of water tank, attending day to day complaints from 9 AM to 5 PM and rectifying the defects, replacement of worn out parts such starting / running capacitor, starting relays, overload relays, thermostate, selector switches, sleeves, knobs, Front grills connectors, PCB etc. which required to be replaced during preventive maintenance & cleaning of filters, condenser fan, blower, fan/blower motor, Coils, Gas charging and any work related to AC/Water cooler is to be carried out as per instruction of Engineer-in-charge etc complete as required by deploying following staff:-(1) AC Mechanic :- 1 No. (9am to 5pm) For 03 Months for financial year 2026-27 & For 05 Months for financial year 2027-28 |
| 75 | Preventive Maintenance of 50 LPH and all type RO plants connected with/within water coolers i/c services (cleaning of all Filters), repair/ replacement of all electrical and electronic spare parts and replacement of consumables and non consumables items as when required like Pre Filter, Sediment Filter, Pre Carbon Filter and Post Carbon Filter alongwith membranes, pump and its accessories etc. as required. (Contractor has to pay minimum transportation charges Rs 100/- per visit to attend complaints for GB Pant College Campus. a) Per Visit for 8 hours RO Technician |
| 76 | Supply & Replacement of RO TFC Membrane 75 GPD Eureka Forbes make i/c testing, commissioning etc. as required. (old dismantle shall be retained by the contractor.) |
| 77 | Supply & Replacement of RO TFC Membrane 150 GPD Eureka Forbes make i/c testing, commissioning etc. as required, old dismantle shall be retained by the contractor. (old dismantle shall be retained by the contractor.) |
| 78 | Supply and replacement of Particulate / Sediment/ Pre-Filter 10/20\\" Eureka Forbes make i/c Leak testing, commissioning etc complete as reqd at site. Dismantle shall be retained by the contractor. |
| 79 | Supply and replacement of Pre /Post Carbon Filter 10/20\\" Eureka Forbes make i/c Leak testing, commissioning etc complete as reqd at site. (Dismantle shall be retained by the contractor.) |
| 80 | Supply and Fixing of 20\\"x 2.5\\" Pre Filter bowl assly to prevent of excess silt in feed water to RO machines i/c Leak testing, commissioning etc complete as reqd at site. (old dismantle shall be retained by the contractor.) |
| 81 | Supply and fixing of Automated Switching on/off device as per level of water in storage tank/ Water cooler etc as reqd. (old dismantle shall be retained by the contractor.) |
| 82 | Suppy & Replacement of the defective spare Parts in existing Water PurificationSystem to make the machines operational i/c testing , commissioning etc. complete as reqd. (Old materials shall be retained by the contractor) |
| 83 | SMPS 24/48V |
| 84 | RO Pump 48V |
| 85 | Solenoid Valve 24V |
| 86 | Push type chrome Platted Brass Tap |
| 87 | Providing and replacing of old defected/ rusted RO body parts with new one in existing Eureka Forbes RO Systems (old dismantle shall be retained by the contractor.) |
| 88 | Supply and replacement of defective RO Body Spares Chassis of existing AG Reviva 50 LPH RO Water Purification system i/c testing &commissioning etc complete as reqd. |
| 89 | Supply and replacement of defective RO Spare Mounting Tray of existing AG Reviva 50 LPH RO Water Purification system i/c testing &commissioning etc complete as reqd. |
| 90 | Supply and replacement of defective Back Plate of existing AG Reviva 50 LPH RO Water Purification system i/c testing &commissioning etc complete as reqd. |
| 91 | Supply and replacement of defective Top Cover of of existing AG Reviva 50 LPH RO Water Purification system i/c testing &commissioning etc complete as reqd. |
| 92 | Supply and replacement of defective Wall mount Stand of existing AG Reviva 50 LPH RO Water Purification system i/c testing &commissioning etc complete as reqd. |
| 93 | SH-IV: Comprehensive maintenance Lift Comprehensive maintenance of 1 No. 13 passengers (884 kgs) OTIS passenger lift complete with all the connected accessories, control panel, AC motor, Gear Box Fly wheels, Ropes, lift pit, guide rails counter weights, lambda mechanism and greasing / oiling the moving parts of the lift, cleaning & decarbonising all the electrical controls complete etc. as per terms & condition. |
| 94 | Credit for dismantle materials |
| 95 | Assorted Ceiling Fans |
| 96 | Assorted Exhaust fans |
| 97 | Assorted wall/PVC fresh air fan |
| 98 | Assorted Switch /sockets/Regulators |
| 99 | Assorted all type indoor fittings |
| 100 | Assorted Flood light/street light fitting |
| 101 | Assorted MCCB |
| 102 | Assorted wire with insulation copper |
| 103 | Assorted SP MCB |
| 104 | Assorted compressor 1TR/1.5TR/ 2TR |
| 105 | Assorted Refrigerant copper pipe |
| 106 | Assorted 3 core 2.5sqmm wire with insulation |
| 107 | Assorted cooling/condensor coil |
| 108 | Assorted PCB |
| 109 | Assorted Fan Motor |
| 110 | Assorted Running/Starting capacitor |
| 111 | Assorted Al. armoured Cable Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 07, 2026
17:00 IST