Tender For Repair And Maintenance Of 11/.415Kv Damaged Cable And Electric Breakdown Including Fault Detection, Localization, Rectification Works In 11/.415Kv Underground Cable Network, Overhead Lines And Lt Panels At Map Naraina, Naraina Baugh, Mh Li
Tender Overview
Project Description
Tender for Repair And Maintenance Of 11/.415Kv Damaged Cable And Electric Breakdown Including Fault Detection, Localization, Rectification Works In 11/.415Kv Underground Cable Network, Overhead Lines And Lt Panels At Map Naraina, Naraina Baugh, Mh Line, Kv No-3, Naraina Pump House, Me Line, 5 Sikh Li Line & Md Accn, Dental Officers Mess, Oval Sub Stn, Cicg Sub Stn, Bor Sub Stn, Cod Depot Sub Stn No 1 To 3, Adp Sub Stn, Mcc Sub Stn, 505 Abw Sub Stn No 1 To 6, Cod Power House, Local Sub Stn, Map Kirby Place, Esd I & Ii, 226 Supply Depot, Shamshan Ghat Sub Stn, Fol Depot, Subraminiam Line And 1181 Pnr Coy, Kirby Grid To Subroto Park Ss/Rr Hosp Ss/ Sekhawati Grid In The Area Of Age (U) E/S - I, Under Ge (U) Elect Supply Deihi Cantt-10
BOQ
| Sl. No. | Item Description |
| 1 | Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed by the Engr-in-Charge.Note: (a) 11 KV HT cable & joints shall be measured and paid for separately under respective items of schedule.(b) Retrieved old serviceable cable cover will be laid in trenches for cable protection. If extra PCC cover and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for separately under respective items of schedule. |
| 2 | All as per item Ser No 1.00 here in before but 1100 Volt LT cables complete all as specified and directed by the Engr-in-Charge. |
| 3 | M&L for disconnecting faulty /burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work, suitable size of thimble LT tap, relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 25 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable in LT Panel/pole/main switch etc complete all as specified and directed by the Engr-in-Charge. |
| 4 | S&F of Cable jointing kit for 11 KV (Earthed) grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable incl testing and commissioning complete all as specified and directed by the Engr-in-Charge of following size :- |
| 5 | 95 Sqmm 3 core. |
| 6 | 120 sqmm 3 core |
| 7 | 150 sqmm 3 core. |
| 8 | 185 Sqmm, 3 core. |
| 9 | 240 Sqmm 3 core. |
| 10 | 300 Sqmm 3 core |
| 11 | S&F of Cable jointing kit for 11 KV (Earthed) grade cable for Outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable incl testing and commisioning complete all as specified and directed by the Engr-in-Charge of following size :- |
| 12 | 95 Sqmm 3 core. |
| 13 | 120 sqmm 3 core |
| 14 | 150 sqmm 3 core. |
| 15 | 185 Sqmm, 3 core. |
| 16 | 240 Sqmm 3 core. |
| 17 | 300 Sqmm 3 core |
| 18 | S&F Cable jointing kit for 11 KV (Earthed) grade cable for Straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable incl testing and commissionig complete all as specified and directed by the Engg-in-Charge of following size :- |
| 19 | 95 Sqmm 3 core. |
| 20 | 120 sqmm 3 core |
| 21 | 150 sqmm 3 core. |
| 22 | 185 Sqmm, 3 core. |
| 23 | 240 Sqmm 3 core. |
| 24 | 300 Sqmm 3 core |
| 25 | Supply, fixing and testing of Straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armored heavy duty aluminum conductor 1100 Volts grade complete all as specified and directed by the Engr-in-Charge for the following sizes:- |
| 26 | 16 -25 sqmm x 4 core |
| 27 | 35-50 sqmm x 3.5 core |
| 28 | 70-95 sqmm x 3.5 core |
| 29 | 120-150 Sqmm x 3.5 core |
| 30 | 185-240 Sqmm x 3.5 core |
| 31 | 300 Sqmm x 3.5 core |
| 32 | 400 sqmm x 3.5 Core |
| 33 | M&L for excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and leveling of bottom surface to required level complete all as specified and directed by the Engr-in-Charge . |
| 34 | M&L for returning filling in, including spreading, leveling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by the Engr-in-Charge. |
| 35 | M&L for removing excavated material (i.e. soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by the Engr-in-Charge. |
| 36 | M&L for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed by the Engr-in-Charge. Note : Measurement shall be taken after punning down. |
| 37 | Supplying and laying of un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx180mmx40mm complete all as specified and directed by the Engr-in-Charge. |
| 38 | All as per srl item No 12.00 here-in-before but using old cable cover complete all as specified and directed by the Engg-in-Charge. |
| 39 | S&F of sub class B bricks having minimum compressive strength 75Kg/Sqcm laid in trenches for cable protection etc complete all as specified and directed by the Engr-in-Charge. |
| 40 | All as per srl item No 14.00 here-in-before but using old bricks complete all as specified and directed by the Engr-in-Charge. |
| 41 | Supplying, laying, jointing, testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed by the Engr-in-Charge of following sizes:- |
| 42 | 95 sqmm 3 core. |
| 43 | 120 sqmm 3 core. |
| 44 | 150 sqmm 3 core. |
| 45 | 185 sqmm 3 core |
| 46 | 240 sqmm 3 core |
| 47 | 300 sqmm 3 core |
| 48 | Supply, laying, jointing, testing and commissioning in replacement LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armored, with multistranded aluminum conductors, IS-1554 marked, laid in trenches complete all as specified and directed by the Engr-in-Charge of the following sizes:-Note :- Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately. |
| 49 | 16 Sqmm 4 core |
| 50 | 25 Sqmm 4 core |
| 51 | 35 Sq mm 3.5 core. |
| 52 | 50 Sq mm 3.5 core. |
| 53 | 70 Sqmm 3.5 core |
| 54 | 95 Sqmm 3.5 core |
| 55 | 120 Sqmm 3.5 core |
| 56 | 150 Sqmm 3.5 core |
| 57 | 185 Sqmm 3.5 core |
| 58 | 240 Sqmm 3.5 core |
| 59 | 300 Sqmm 3.5 core |
| 60 | M&L for boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 80 to 100 mm bore and making good both ends complete all as specified and directed by the Engr-in-Charge. |
| 61 | S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole or for crossing of culverts/nallah etc complete all as specified and directed by the Engr-in-Charge of following bore sizes:- |
| 62 | 40 mm |
| 63 | 50 mm |
| 64 | 80 mm |
| 65 | 100 mm . |
| 66 | M&L for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole, Transformer, LT panels, in and outside area of HT/LT Sub stn and removing all rubbish to a distance not exceeding 50 m complete all as specified and directed by the Engr-in-Charge. |
| 67 | M&L for testing, setting & co-ordination of relay parameters consideration with incoming and outgoing feeders including following tests and setting complete all as specified and directed by the Engr-in-Charge as per detalis mentioned as under :- (i) testing of following relays of control panel with secondary injection kit checking and programming of realy (ii) OVER CURRENT IDMT with pick upsetting ,TMS ,CTR |
| 68 | M&L for re-painting of existing transformer/RMU GI fencing of any sizes by applying 2 coats of aluminum paint including rubbing with wire brush/sand paper to fencing/angle irons, at different location after disconnecting of HT supply from incoming and LT supply complete all as specified and directed by the Engr-in-Charge. |
| 69 | M&L for fixing of LT Panel door having thickness 3.15 of existing panels complete with locking arrangement, welding of door using hinges, and painting after fixing complete all as directed and specified by Engr-in-Charge. |
| 70 | M&L for Decarbunizing/cleaning complete outgoing/Incoming LT Air Circuit Breaker circuit of size 800/1000/1200 Amps, srpring, arcing surfaces, 3 phase, cleaning with CTC and ensure proper decarburizing, re-fixing the same tightening the nuts, bolts thimbles for incoming and outgoing system complete all as specified and directed by the Engr-in-Charge, the rate quoted is inclusive of spring & cotton waste to be provided by contractor. |
| 71 | Note : Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Engr-in-charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender