Tender For General-Government Secretariat Thiuvananthapuram- Supply ,Installation Of 10Kva Ups And Providing Additional electrical installation In Telephone Exchange In Connection With The Upgradation Of Exchange From Epabx System To Ippbx System-Ele
Tender Overview
Project Description
Tender for General-Government Secretariat Thiuvananthapuram- Supply ,Installation Of 10Kva Ups And Providing Additional electrical installation In Telephone Exchange In Connection With The Upgradation Of Exchange From Epabx System To Ippbx System-Electrical Work-General Electrical Work
BOQ
| Sl. No. | Item Description |
| 1 | Installation of 10KAV UPS |
| 2 | OD90122/2026-2027:Supply Installation Testing and commissioning of 10KVA=10KW Unity output power factor modelMODEL 3 PHASE IN AND 3 PHASE OR 1 PHASE SELECTABLE OUT TOWER TYPE ONLINE DOUBLE CONVERSION PURE SINE WAVE UPSSYSTEM WITH SALIENT FEATURES Like, maximum power availability Leading AC-AC efficiency up to 96% saves energy costs Low harmonic pollution (iTHD0.99) reduce upstream investment costs Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life DSP based technology enables reduction in the number of electronic components to lower failure rate Adjustablecharging current and battery voltage meet different battery configuration requirements, IGBT Rectire and inverter, Generater compatable,Noice level <58dB, can Parellel upto 4 systems.etc. (Delta /Numeric/Emerson )The supplier should be submitting Tested documents, Operation manual, service manual etc. EXTRNAL EXIDE C10 RATED TUBULAR BATTERY 12V, 75AH, 20 NUMBERS (MINIMUM VAH 18000) FOR 60 MINUTES BACKUP.. SUITABLE battery Rack with Battery breaker switch, Cables, Interlinks, all accessories with freight and Installation, Including three year service by service provider of OEM and its confimity certificate submitted at the time of installation |
| 3 | Electrification for the installation of UPS |
| 4 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 5 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 6 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 7 | 1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 8 | OD77342/2026-2027:SITC 1200 lumen round/ square(1X1) recessed fitting made of diecast aluminium body, polycarbonate diffuser, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea |
| 9 | OD77343/2026-2027:Supply and installation of 3600 lumen square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea (UGR less than 19) |
| 10 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 11 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 12 | 2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.25 amps |
| 13 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)8 way, Double door |
| 14 | 2.4.1:Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way (4+12) Double door |
| 15 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 16 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 17 | OD90110/2026-2027:Supplying and fixing FP sheet steel enclosure on surface/ recess complete as required. |
| 18 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 19 | 1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm |
| 20 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 21 | 1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm |
| 22 | 1.17.18:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 2.5 sq. mm |
| 23 | 1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm |
| 24 | 1.14.10:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 25 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 26 | 90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid |
| 27 | 90.9.2.11:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable retainer |
| 28 | 90.9.2.12:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.1 to 3 module mounting box |
| 29 | 90.9.2.13:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.4 to 5 module mounting box |
| 30 | 90.9.2.2:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider |
| 31 | 90.9.2.3:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree |
| 32 | 90.9.2.4:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 degree |
| 33 | 90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree |
| 34 | 90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap |
| 35 | OD49/2026-2027:Supply and Fixing timer switch, 24 Hrs programmable with IP 53 cover (AUTS02DIG00 L&T or equivalent) |
| 36 | OD50/2026-2027:Supply and Fixing the following types current rated contactor with AC coil suitable for 240V, 50Hz in existing cubicle panel board including drilling holes in making connection etc. as required.32A,AC3 2 pole contactor(MNX 32-2P- L&T or techno commercial equivalent) |
| 37 | OD51/2026-2027:Supply and fixing Wall Mount BCH BOX 200 x 300 x 150 mm BIL50010 CPR,POWERDER COATED |
| 38 | OD52/2026-2027:Class C/ Type 2 Surge Protection Devices For VDB/Sub Distribution Board (SDB): Three Phase Application: This panel should include pluggable type surge arrester in suitable enclosure Class C/ Type 2 as per IEC 61643 -11 for surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4- 44). Modular connectable arrestor with dynamic cut-off unit and visual status display for each cartridge. It should be included Locking mechanismwith vibration protection and voltage keying for safe operation of the device. And the remote signalling can be acheived by inbuilt potential-free changeover contact in FS version. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) . Total Nominal discharge current- 60 kA (8/20? sec) for Line to Neutral & 40 kA(8/20? sec) for Neutral to Earth, Total Max discharge current - 160 kA (8/20? sec). Voltage protection level 1400V (L to N) & (N to E). Operating temp -40o to +80oC. Response time <25 nano sec (L to N), < 100 nano sec (N to E). DIN rail mounting type etc complete with back up fuse as required and as directed. The product should be tested and aproved by any one of the following external testing institute(UL, KEMA, OVE, VDE) |
| 39 | 90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 40 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 41 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 42 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 43 | OD90133/2026-2027:Supply and fixing ofSelf-adhesive vinyl sticker for lettering and figures of sizes and colour selected by the Engineer in charge for the identification mark to fan, AC, SB, DB, panel board , fire etc as required Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender