Tender For Repair/ Maintenance And Improvement Of Existing Fire Fighting System Water Supply Pipe Line, Pump Motor And Other Connected Items At Amn Jetty And Pin Jetty At Naval Station Karanja
Tender Value
45 Lakhs
Estimated cost
Bid Submission
25 Aug 2026
24 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
karanja → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Repair/ Maintenance And Improvement Of Existing Fire Fighting System Water Supply Pipe Line, Pump Motor And Other Connected Items At Amn Jetty And Pin Jetty At Naval Station Karanja
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches for laying pipes and fittings, n exc 1.5 m wide and not n exc 1.5 m depth and getting out in hard dense soil including grading and ramming bottom surface complete all as specified and directed by Engr-in-Charge. |
| 2 | Returning , filling in including spreading, levelling , watering & well ramming in layers n.exc 25cm including making good disturbed surface to original levels complete all as specified and directed |
| 3 | Removal of exacavation material to a distance n exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed |
| 4 | Supplying, laying, testing and commissioning of ductile iron pipe (DI Pipe) (ISI marked IS No 8329:2000), laying above the ground of nominal diameter 100mm, class K -9, with internal cement mortar lining and external bitumen coating with flanged at both the ends with & including all jointing material and painting with two coats of synthetic enamel paint (post office red colour) including removing the old unserviceable pipes, of any type complete all as specified and directed. |
| 5 | Supplying, laying, testing and commissioning of ductile iron pipe (DI Pipe) (ISI marked IS No 8329:2000), laying above the ground of nominal diameter 150mm, class K -9, with internal cement mortar lining and external bitumen coating with flanged at both the ends with & including all jointing material and painting with two coats of synthetic enamel paint (post office red colour) including removing the old unserviceable pipes, of any type complete all as specified and directed. |
| 6 | S&F in repair or replacement and commissioning of 150 mm bore MS ERW pipe class 'B' in standard length conforming to IS 1239 part -I (ISI Marked) duly painted with two coats synthetic enamel paint of first quality over coat of primer for complete all as specified and as directed. |
| 7 | S&F in repair or replacement and commissioning of 100 mm bore MS ERW pipe class 'B' in standard length conforming to IS 1239 part -I (ISI Marked) duly painted with two coats synthetic enamel paint of first quality over coat of primer for complete all as specified and as directed. |
| 8 | Supply, laying, jointing DI fittings (DI Specials) conforming to IS 9523 such as bends, caps, collars, Tees, Tail piece, Elbows, Tapers and Reducers etc complete all as per site requirement. Note:- The DI specials shall be of minimum class K-9 and from same manufacturer as of DI pipe. |
| 9 | Supply & fix in repair double door fire hose cabinate box with arrangement for holding 2 Nos 15m long hose pipe of size not less than 800mm x 600 mm x 250 mm, made out from 16 Gauge MS sheet duly painted with two coats of (red colour) synthetic enamel paint over a coat of red oxide zinc chrome primer with double leafed glazed shutters (glazed with 4 mm thick transparent fiber sheet) mounted over the MS angle iron 50mm x 50mmx 6mm frame having minimum 1m long, 4 Nos legs, and grouted the same into PCC (using1:3:6 type) and must have the legend \\" FIRE HOSE\\" painted prominently in the graphic style complete all as specified and directed by Engr-in-Charge |
| 10 | S&f in repair/ replacement of pressure gauge 4\\" dia 0 to 14 Kgs rating in existing position complete all as specified and directed. |
| 11 | S&F in repair / replacement of strainer for sucction 100 mm more flanged type ISI marked complete all as specified and dirrected. |
| 12 | S&F in reapir /replacement of channels / angles for foundations, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and directed by Engr-in-Charge |
| 13 | Supply and fix in repair sluice valve with flanged ends 150 mm bore cast iron body, flanged and drilled end non rising type with nuts, as per IS 14846, ISI marked including all joints, class PN 1.6 complete all as specified and directed. |
| 14 | Supply and fix in repair sluice valve with flanged ends 100 mm bore cast iron body, flanged and drilled end non rising type , SS spindle with nuts, as per IS 14846, ISI marked including all joints, class PN 1.6 complete all as specified and directed. |
| 15 | Supply and fix in repair sluice valve with flanged ends 80 mm bore cast iron body, flanged and drilled end non rising type , SS spindle with nuts, as per IS 14846, ISI marked including all joints, class PN 1.6 complete all as specified and directed. Please Enable Macros to View BoQ information |
| 16 | Supply and fix in repair sluice valve with flanged ends 80 mm bore cast iron body, flanged and drilled end non rising type , SS spindle with nuts, as per IS 14846, ISI marked including all joints, class PN 1.6 complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 24 daysAug 27, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender