Tender For Construction Of 33/11 Kv Electrical Yard Comprising Supply, Installation, Testing And Commissioning Of 33 Kv Line Bay, 33 Kv Transformer Bay, Power Transformer, 11 Kv Indoor Switchgear, Common Equipment And Miscellaneous Works For Upcoming
Tender Overview
Project Description
Tender for Construction Of 33/11 Kv Electrical Yard Comprising Supply, Installation, Testing And Commissioning Of 33 Kv Line Bay, 33 Kv Transformer Bay, Power Transformer, 11 Kv Indoor Switchgear, Common Equipment And Miscellaneous Works For Upcoming Receiving Station Kandi Handwara
BOQ
| Sl. No. | Item Description |
| 1 | Electrical Yard Works |
| 2 | Shifting of 6.3 MVA Power Transformer from ECSD Pampore to Receiving Station( The job includes Loading / Handling /Carriage upto site/ Unloading /Dragging /Assembling/Installation and Commissioning of Power Transfomer at site including insurance during transit (Complete Job)( Power Transformer to be provided by the Department) |
| 3 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 33 kV VCB (36 kV, 1250A, 26.2 kA, Outdoor Type of reputed make as per approved drawings/standards |
| 4 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator without Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards |
| 5 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator with Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards |
| 6 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 KV Current Transformer (33 KV, 1Φ, 2 Ratio 3 Core, Outdoor Type ; 300-150/5-5A) of reputed make as per approved drawings/standards |
| 7 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) of reputed make as per approved drawings/standards |
| 8 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV C&R Panel along with O/C, E/F,REF and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port |
| 9 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV 10 kN Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m of reputed make as per approved drawings/standards |
| 10 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV /110 V Single Phase outdoor type Potential Transformers (1 No. per Φ) of reputed make as per approved drawings/standards |
| 11 | Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 11 Mtr. Long Pole(ST-410 SP-56) with planting depth of 1/6 th of the height of the pole, (11 mtr. Long ) as per approved drawings/standards |
| 12 | Supply & Laying of Cement bottoming for 11 Mtr ST Pole in 1:2:4 mix as per Standards 0.66 cum / pole including the Loading/Carriage/Unloading of required material. |
| 13 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm as per approved drawings/standards for 11 Mtr ST Poles |
| 14 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of G.I Pipe of Dia 150mm, 5.9 mm Thick 3 m long with G.I Base Plate 8 mm Thick as per approved drawings/standards |
| 15 | Supply,Testing,Loading,Carriage,Unloading and fixing of Galvanised Nuts & Bolts of sizes |
| 16 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards |
| 17 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards |
| 18 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards |
| 19 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards |
| 20 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards |
| 21 | Supply & Fixing of Lugs, Ferrules etc. |
| 22 | Supply, Carriage upto site (including Loading/Unloading),Testing, Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (200mm2 ACSR Conductor) as per approved drawings/standards |
| 23 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of CT Clamps/PG Clamps(0.2 ACSR)/T Clamps (0.2 ACSR) Al. Make (800 Amp) as per approved drawings/standards |
| 24 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting of reputed make as per approved drawings/standards |
| 25 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm of reputed make as per approved drawings/standards |
| 26 | Supply, Carriage upto site (including Loading/Unloading),Installation of Earth wire 7/4.00 mm sq. as per approved drawings/standards |
| 27 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :400-200/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make) |
| 28 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Incomer SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :600-300/5-5A,Epoxy Casted PT with PTR :11KV/110 V, TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make) |
| 29 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type of reputed make as per approved drawings/standards (01 Set = 03 No.) |
| 30 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 kV 400 mm² Single Core XLPE Cable armoured, FRLS (Polycab, Havells, KIE or equivalent) as per approved drawings/standards |
| 31 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 kV 3-Core XLPE 300 mm² armoured, FRLS (Polycab, Havells, KIE or equivalent) as per approved drawings/standards |
| 32 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Indoor Heat Shrinkable Cable Termination Kits 1 C-400 mm²(3M/Vitchem or equivalent) as per approved drawings/standards |
| 33 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Outdoor Heat Shrinkable Cable Termination Kits 1 C-400 mm² (3M/Vitchem or equivalent) as per approved drawings/standards |
| 34 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Indoor Heat Shrinkable Cable Termination Kits 3 Core 300 mm²(3M/Vitchem or equivalent) as per approved drawings/standards |
| 35 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Outdoor Heat Shrinkable Cable Termination Kits 3 Core 300 mm² (3M/Vitchem equivalent) as per approved drawings/standards |
| 36 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch. as per approved drawings/standards |
| 37 | Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 9 Mtr. Long Pole ( ST-410 SP33) with planting depth of 1/6 th of the height of the pole, (9 mtr. Long ) as per approved drawings/standards |
| 38 | Supply & Laying of Cement bottoming for 9 Mtr ST Pole in 1:2:4 mix as per Standards 0.48 cum / pole including the Loading/Carriage/Unloading of required material. |
| 39 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Pipe 40 mm 2.5 mtr long through GI strip 25x3mm as per approved drawings/standards |
| 40 | Supply,Carriage upto site (including Loading/Unloading) and fixing of Danger Plates with Clamps as per approved drawings/standards |
| 41 | Supply,Carriage upto site (including Loading/Unloading) and fixing of Anti-Climbing Device with Clamps as per approved drawings/standards |
| 42 | Providing & Painting of Poles with one coat of Red Oxide and two coats of aluminium paint and as per approved drawings/standards |
| 43 | Supply, Carriage upto site (including Loading/Unloading), Fixing of GI flat for earthing (50x6) mm as per approved drawings/standards |
| 44 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 100 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) (Post Amendment 04 to IS 1180)as per approved drawings/standards |
| 45 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 120 mm² XLPE LT Cable 4 Core, armoured, FRLS (Polycab, Havells, KIE or any other reputed make) as per approved drawings/standards |
| 46 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Earthing of 100 KVA SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover as per approved drawings/standards |
| 47 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of LT Distribution Box for 100 kVA DTR with 160 Amp MCCB 3P 16 kA for incomer as per approved drawings/standards |
| 48 | Supply, Carriage upto site (including Loading/Unloading),Testing & laying of HDPE Pipe Outer Dia 160 mm Inner Dia 148 mm for 11kV XLPE Cable from Power Transformer to Control Room including excavation as per approved drawings/standards |
| 49 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting of reputed make as per approved drawings/standards |
| 50 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm of reputed make as per approved drawings/standards |
| 51 | Supply, Carriage upto site (including Loading/Unloading), Fabrication, Installation & Testing of Earthing Mat (GI Flat 50mm x8 mm) as per approved drawings/standards (Joints should be welded properly and painting of joints to be carried out by using Red Oxide and Deeco Paint. The job includes the excavation of existing earth to the depth as per the KPDCL standards in vogue and back filling of good earth upto ground level after fixing the earth mat including spreading of extra soil in available space as per the directions of Incharge Engineer ( The earthing value should be less than 2 ohms) |
| 52 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Electrode ( 3m long 40mm dia GI pipe) including their jointing to earthing mat through GI Strip (50x6)mm by welding/bolting and painting of joints with Red Oxide and Deeco Paint as per approved drawings/standards |
| 53 | Supply, Carriage upto site (including Loading/Unloading), Installation, Testing & Commissioning of Yard Lighting by way of Providing 12.5 Mtr motorised High Mast with 4 No.s of 200 W LED flood lights (Bajaj/Havells/Syska/Wipro or any other eputed make) on each High Mast .The job includes provding and fixing of control panel containing all protective equipments (like surge arrestor, MCB,over voltage protection, servo stablizer,Timer), complete wiring and Construction of Foundations using reinforced concrete including TMT Bars as per the drawings/standards |
| 54 | Construction of Borewell of G.I 5 \\" dia outer pipe and 1\\" dia inner pipe for motor with submersible pump (1.5 HP) including Providing/Loading/Carriage/Unloading of required material as per the drawings/standards (Excluding the charges of submersible pump) |
| 55 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Motor with submersible pump (1.5 HP) (Havells/Crompton/Kirsolkar/Jindal make) as per approved drawings/standards including providing & fitting of 1\\" dia GI pipe from pump upto Water Tank. |
| 56 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of Battery Bank 36 V,200 AH , of 18 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant (reputed make) as per approved drawings/standards |
| 57 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 36V, 200 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply (reputed make) as per approved drawings/standards |
| 58 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Distribution Panel (36 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, One Change over switch 63 Amp 2 Pole ,24 No DP DC MCB (20A) including indication lamps and cables and other accessories as per approved drawings/standards |
| 59 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Double Door Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm, Powder Coated, degree of protection IP43,Danger plate (Caution Plate) shall be fitted suitably on inner door of the DB. The A.C Distribution Board shall be provided with the following equipments 200 Amps Switch Fuse disconnector for incoming supply, 2 No TPN MCB's (125 Amps ),3 No TPN MCB's (32 Amps ),3 No DP MCBs (32A), 09 No. MCB 16A DP,ammeter with selector switch,voltmeter with selector switch,3 no. LED type phase indication lamps for incoming feeder, 3 no. single phase L.T. CTs of 10 VA and CT ratio 200/5 A,1 no. timer with contactor for lighting circuit,rectangular busbar suitable for 200 Amps including necessary cable glands and termination blocks as per approved drawings/standards. The number of outgoing feeders from AC Distribution Board shall be such that each substation equipment is fed by separate feeder with 20% as spare. |
| 60 | Supply, Carriage upto site (including Loading/Unloading) & Fixing of Rubber Mat 1mx2m 19mm thick as per approved drawings/standards |
| 61 | Supply, Carriage upto site (including Loading/Unloading) & Fixing of Fire Extingiusher Co₂ Type of 4.5 kg capacity for Control room as per approved drawings/standards |
| 62 | Supply , installation and testing of Fire Fighting Equipment (3 No. Fire Buckets of 9 ltrs,having round bottom with handle, painted white from inside and post office red colour from outside , bottom is painted black. Filled with sand. |
| 63 | Supply of ISI-marked Safety/ Industrial Helmet made of high-quality, impact-resistant HDPE/ABS material, equipped with adjustable headband, chin strap, ventilation system, sweat-absorbent inner lining and Detachable and Interchangeable LED Headlamp with HEadlamp Bracket conforming to IS:2925 standards, of approved make and colour, as per directions of the Engineer-in-Charge |
| 64 | Supply of Electrical Rubber Insulating Gloves suitable for working up to 33 kV, made of high-dielectric natural rubber, seamless, ergonomically designed, conforming to IS:4770 / IEC 60903 standards, duly tested and certified, complete with manufacturer’s test certificate, of approved make and quality, as per directions of the Engineer-in-Charge. |
| 65 | Supply of Electrical Rubber Insulating Gloves suitable for working up to 11 kV, made of high-dielectric natural rubber, seamless, ergonomically designed, conforming to IS:4770 / IEC 60903 standards, duly tested and certified, complete with manufacturer’s test certificate, of approved make and quality, as per directions of the Engineer-in-Charge. |
| 66 | Supply of ISI-marked Safety Belt / Full Body Harness made of high-strength polyester webbing with adjustable shoulder and thigh straps, equipped with double lanyard, shock absorber, and forged steel snap hooks, conforming to IS:3521 standards, of approved make and quality, as per directions of the Engineer-in-Charge |
| 67 | Supply of ISI-marked industrial Safety Shoes made of genuine leather with steel toe cap, oil/acid/slip resistant PU sole, shock-absorbing heel, and padded ankle support, conforming to IS:15298 (Part 2) standards, of approved make, size, and quality, as per directions of the Engineer-in-Charge |
| 68 | Supply of Earthing Discharge Rod suitable for safely discharging high-voltage lines/equipment up to 33 kV, made of high-quality epoxy/fiberglass insulating rod with metallic clamp, complete with 16 sqmm multi-strand copper earthing cable of adequate length and earthing terminal, conforming to relevant IS/IEC standards, complete with carrying case, of approved make and quality, as per directions of the Engineer-in-Charge |
| 69 | Supply of High Voltage Detector suitable for outdoor/indoor use, capable of detecting multiple voltage levels ranging from 3.3 kV to 33 kV (or higher as specified), provided with clear audible and visual indication, telescopic epoxy/fiberglass insulating rod, battery-operated electronic circuit, and complete with carrying case, conforming to relevant IS/IEC standards, of approved make and quality, as per directions of the Engineer-in-Charge |
| 70 | Supply, installation, testing and commissioning of HD CCTV Camera system including IP/HD cameras (06 No.),6 Channel NVR with surveillance-min. 1 TB storage storage, 32 inch LED monitor, cabling, power supply units, mounting accessories and all required works complete as per specifications and directions of Engineer-in-Charge. The equipment shall be of reputed make such as Hikvision / CP Plus / Dahua / Honeywell or equivalent approved by Engineer-in-Charge. |
| 71 | Supply of heavy-duty Telescopic Aluminium Ladder of maximum extended height 18 ft, made of high-tensile aluminium alloy sections with minimum 3 mm wall thickness, equipped with slip-resistant steps, rubber shoes at the base, safety locking mechanism at each stage, lightweight and portable design, conforming to IS standards, of approved make and quality, as per directions of the Engineer-in-Charge |
| 72 | Supply of heavy-duty Aluminium Extension Ladder of size 2 × 20 feet (two-section), fabricated from high-tensile aluminium ‘C’ section, with minimum 3 mm wall thickness, complete with rope and pulley arrangement for smooth extension, anti-skid steps, rubber shoes at the base, and safety locking arrangement, of approved make and quality, as per directions of the Engineer-in-Charge |
| 73 | Supply ,Carriage upto site (including Loading/Unloading)Installation, Testing & Commissioning of single phase LT Servo Stablizer 5 KVA Cu Wound, oil cooled, with motor control, electronic overload protection,ground fault monitoring with trip indication ,surge supressor, voltage cutt off for servomotor at input and over voltage, auto manual switch , with digital VIF meters , input range 100-280, out put 230volts, |
| 74 | Supply of Motorized 22 inch petrol chain saw tree cutter.of reputed company. |
| 75 | Transformer Foundation, Equipment Foundation, Yard Concreting , Yard Metalling, Cable Trench etc. works |
| 76 | Earthwork in excavation over areas (exceeding 30 cms in depth, 1.5m in width as well as 10 Sqm on plan) incld. disposal of excavated earth, and lift upto 1.5m, (All kinds of soil). By mechanical means |
| 77 | Providing & laying in position cement conc. of specified grade excld. Cost of centering & shuttering- all work upto plinth level in 1:2:4 (1 cement :2 coarse sand :4 graded stone agg. 40 mm nominal size (Crushed) including carriage of all required material |
| 78 | Providing & laying of stone soling in level including carriage of all required material |
| 79 | Providing and laying in position specified grade of reinforced cement conc. excluding the cost of centering, shuttering, finishing -and reinforcement All work upto plinth level, M20 grade concrete including carriage of all required material |
| 80 | Reinforcement for RCC work incld. straightening, cutting, bending, placing in positions and binding all complete (T.M.T). including carriage of all required material |
| 81 | Centring & Shuttering upto plinths and footings including carriage of all required material |
| 82 | 12 mm thick cement on the rough side of Transformer bed ,Equipmen founations Cable trench etc mix:1:6 (1: cement :6 fine sand) |
| 83 | Providing and laying including stacking 75 to 100 mm size aggregate for metal in the switch yard |
| 84 | Providing and Fixing of Angle Iron of different sizes including Loading/Carriage/Unloading of required material including a coat of Red Oxide primer |
| 85 | Providing and Fixing of 8 mm thick MS chequered plates for Cable Trenches including Loading/Carriage/Unloading of required material with a coat of Red Oxide primer/paint |
| 86 | Spares/ Contingencies |
| 87 | Hiring of Vehicle (Scorpio/Bolero/Innova/Tavera or equivalent) to be used by the Engineer Incharge for supervision of the project including Fuel/Toll Tax/ Driver/ any other maintenace charges of the vehicle. The max. Kms to be driven per day is 100 Km. In case the vehicle is utilized less than 100 km on any given day, the payment shall be subject to deduction on account of actual fuel savings. Such deduction shall be worked out proportionately based on the approved mileage (km per litre) of the vehicle and the prevailing fuel rate. |
| 88 | Supply, Carriage upto site (including Loading/Unloading),Testing of 20 A Auxiallary Switch suitable for 11KV VCB of (Allind-Make/ Electric field /Easun / CG/ Crompton / Alastom or equivalent) of reputed make |
| 89 | Supply, Carriage upto site (including Loading/Unloading),Testing of 20 A Auxiallary Switch suitable for 11KV VCB of (Allind-Make/ Electric field /Easun / CG/ Crompton / Alastom or equivalent) of reputed make |
| 90 | Supply, Carriage upto site (including Loading/Unloading),Testing of Limit Switch suitable for 11KV VCB reputed make |
| 91 | Supply, Carriage upto site (including Loading/Unloading),Testing of 12 KV, Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :400-200/5-5A=03No. ; 600-300/5-5A= 03 No. |
| 92 | Supply, Carriage upto site (including Loading/Unloading),Testing of 11kV/ 110 V, Three phase epoxy resin cast Voltage Transformer with rated burden 15VA per phase and accuracy class 0.5 (reputed make) |
| 93 | Supply, Carriage upto site (including Loading/Unloading), Testing of 11 KV VCB 110 V Charging Motor |
| 94 | Supply, Carriage upto site (including Loading/Unloading),Testing of Panel spouts Bushing suitable for 11KV VCB |
| 95 | Supply, Carriage upto site (including Loading/Unloading),Testing of Interrupting chambers (Housing Assembly) |
| 96 | Supply, Carriage upto site (including Loading/Unloading),Testing of Shower Contacts for 11 KV VCB |
| 97 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioining of 11KV Vacuum Interrupter- 1250 Amps (Crompton Greeves / Alstom /ABB ) as per relevent IS |
| 98 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioining of 33 KV Vacuum Interrupter (800 Amps) Crompton Greeves /ABB/Stelmac) as per relevent IS |
| 99 | Supply, Carriage upto site (including Loading/Unloading), Installation, Testing & Commissioining of Master Trip Relay as per relevent IS |
| 100 | Supply, Carriage upto site (including Loading/Unloading),Testing of 30-36 VDC Tripping/Closing coils suitable for 11KV VCB Panels like Allind,Vijay,Crompton greeves,Easun Reyroll,Alasthom, Electricfield,Sudhir,ABB,L&T, Pascal or equivalent of reputed make |
| 101 | Supply & Fixing of Wooden Bed in Staff Cabin as per the directions of Engineer in Charge |
| 102 | Supply including carriage of Kitchen Set Containing Gas Stove Two Burner along with 15 Ltr Cylinder 01 No., Induction Cooker 2000 Watt 01 No., Rice Cooker 5 Ltr 01 No.,Pressure Cooker with induction base 2.8 Ltr 01 No., Steel plates 6 No., Steel Glass 06 No., Steel Bowls 06 No, Table spoon 04 No., Tea Spoon 06 No., Knife Set, Steel Air tight Containers 06 No., Non Stick Cooking Frying Pan 02 No., Non Stick Pan Tawa 01 No. Dustbin 02 No. Cleaning Broom 02 No.,Heat Pillar 2000 watt 01 No.All supplied items should be of reputed make |
| 103 | Supply including carriage of Washroom Items like Bucket 20 Ltr 01 No. ,Jug 02 No., Mug 01 No. Stool 01 No., Floor Wiper 01 No.,Slippers 02 Pairs,Towels 02 No., Toilet Brush with holder, Toilet Cleaner Liquid 02 bottles, Tile Cleaner Liquid 02 bottles, Hand Wash 02 No.All supplied items should be of reputed make |
| 104 | Supply including carriage of Plastic Chairs 05 No. along with the table 01 No. All supplied items should be of reputed make |
| 105 | Supply including carriage of High Power Rechargeable Halogen Search Light, 55W Long Range Spotlight, 1000m Operating Range, 350-500m Viewing Distance, Inbuilt AC Charger including charging cable and Shoulder Strap |
| 106 | Supply, Carriage upto site of Heavy Winter Blanket – Double Bed Double Layer 3 Kg weight of standard quality |
| 107 | Supply of Printer Cartridge for HP Laser MFP 136a (Cartridge Model 110 A) for Divisional Office |
| 108 | Supply of 75 GSM A4 size paper Rim for Divisional Office Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 27 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 29 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender