Tender For maintenance of electrical installation & Fans I/C Compound Light, Street Light, Cctv System & Fire Alarm At Dseu Jaffarpur, New Delhi.
Tender Value
19.32 Lakhs
Estimated cost
Bid Submission
05 Aug 2026
3 days left
EMD
38659
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for maintenance of electrical installation & Fans I/C Compound Light, Street Light, Cctv System & Fire Alarm At Dseu Jaffarpur, New Delhi.
BOQ
| Sl. No. | Item Description |
| 1 | Sub-Head- I (MOEI & fans.)Routine Maintenance all electrical installation internal and external, compound light, electrical/pump panels and switch gears, pumps, provision of fans and fittings, lamps of all sizes etc repairing of panel board, street lights in all days i/c sunday & holidays etc as reqd. |
| 2 | Wireman- 1 No. (9 AM to 5 PM) |
| 3 | Khallasi - 1 No. (9 AM to 5 PM) |
| 4 | Sub-Head-II (Manitenace Material for day to day use)Following material /electrical accessories shall be supply by agency suitable for existing different type switch box / fitting and existing man power shall be used for replacement on day to day maitenance works etc as required. (Labour already included in Item No. 1 o Sub Head - I : EI & FANS ) |
| 5 | S.P. 5/6 amps, one way modular switch, ISI marked |
| 6 | S.P. 15/16 amps, one way modular switch, ISI marked |
| 7 | 3 pin 5/6 amps modular socket outlet, ISI marked |
| 8 | 6 pin 15/16 amps modular socket outlet, ISI marked |
| 9 | Modular bell push, ISI marked |
| 10 | Telephone Socket outlet modular type |
| 11 | T.V. Socket outlet modular type |
| 12 | Ceiling rose, 3 pin, 5 amps ISI marked |
| 13 | Call bell/ buzzer, single phase |
| 14 | 6 to 32 Amp c Curve SP MCB, \\"C\\" curve, 10 kA breaking capacity |
| 15 | 40 A, rating, 2 pole RCCB, 30mA |
| 16 | 63 A TPN/FP MCB |
| 17 | Modular base & cover plate for 6 module |
| 18 | Modular base & cover plate for 8 module |
| 19 | Modular base & cover plate for 12 module |
| 20 | 1.5 sq. mm ISI marked, FR PVC insulated, single core copper conductor cable |
| 21 | 4.0 sq. mm ISI marked, FR PVC insulated, single core copper conductor cable |
| 22 | 6.0 sq. mm ISI marked, FR PVC insulated, single core copper conductor cable |
| 23 | 2.50 mF capacitor |
| 24 | Stepped type Modular Fan regulator (2 module) |
| 25 | Ceiling fan with Brush Less Direct Current (BLDC) Motor, etc. complete as req 1200 mm sweep Ceiling fans 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 26 | 300 mm sweep heavy duty exhaust fans |
| 27 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) of following body materials. Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 28 | a) 36 watt |
| 29 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) of following body materials. Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector |
| 30 | a) 12 -15 watt |
| 31 | Supply of LED Bulk Head fitting not more than 10 W, System efficacy not less than 100 lumens / watt, System output not less than 1000 lumens / watt, CRI>80 and CCT= 5500-6500K and IP-66 rated with aluminium die cast housing & frostrated glass diffuser complete as required. |
| 32 | 600 mm long nominal size LED batten mirror light fitting made out with Aluminium die cast housing and Poly carbonate diffuser with all accessories having rating not more than 10 W, System Efficacy not less than 100 lm/W, lumens output not less than 1000, CRI >80 complete etc. as required. |
| 33 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) of following body materials. Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 34 | a) 36 watt |
| 35 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) of following body materials. |
| 36 | 72 watt |
| 37 | 45 watt |
| 38 | Sub-Head- III (Minor Repairs of EI, Compound Light .) |
| 39 | Supply of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size way. |
| 40 | 3 X 10 Sq.mm |
| 41 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in following way. |
| 42 | Upto 35 sq. mm (clamped with 1mm thick saddle on wall surface) |
| 43 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 44 | SITC of weather proof pole box made out of hot moulded SMC sheet with clamp /fastner neutral link strip, gland thimble and 1 No. 6 Amps SPMCB Complete with inter connection with copper wire, earthing (Box Size - 300mm x 200 mm x 105 mm) |
| 45 | Rewinding of 1200mm ceiling fan complete with super enemelled copper winding wire i/c varnishing backing testing commissioning and without returning of scrop copper wire etc. as reqd. |
| 46 | Rewinding of 300mm Exhaust fan complete with super enemelled copper winding wire i/c varnishing backing testing commissioning and with credit of scrap copper wire etc. as reqd. |
| 47 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 48 | Group C |
| 49 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 50 | Group C |
| 51 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 52 | 8 way , Double door |
| 53 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 54 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 55 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 amps modular socket outlets and 2 nos 5/6 amps modular switches, connection etc. as required. |
| 56 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess i/c providing and fixing 25 amp modular socket outlet and 25 Amps modular SP MCB, “C” curve including connection, ainting etc. as required. |
| 57 | Supplying and fixing RJ-45 Data socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 58 | Complete Servicing of existing installed WTAC /STAC of 2.0 TR capacity AC i/c indoor & outdoor units, checking for unit, inspection, greasing, oiling etc i/c chemical cleaning of the condensing coil with high pressure pump changing the air filter, checking & tightening all electic connection i/c replacement of wornout parts such as starting / running capacitors, starting relays, overload relay, tharmostat, selector switches, sleeves, knobes, connector and associated control wiring, filter, drain pipe, man leads etc testing the machine complete as reqd. (Replacement of compressor, condensor unit, cooling coil unit, blower, fan blower motor, front grill, gas charging etc not covered under routine maintenance) |
| 59 | Supplying & charging of M-22/R22/R-32/R-410A/R-134A gas in the exising WTAC / STAC/Water cooler of following capacity unit i/c pressure testing, flushing the system & gas charging complete etc as reqd. |
| 60 | 2.0 TR |
| 61 | Repair of damaged PCB of indoor and outdoor unit of 2.0 TR AC i/c tightening the loose connection, testing the machine etc complete as required. |
| 62 | Supplying and fixing of 2.0 TR capacity WTAC/ Split AC cooling coils i/c pressure testing after removing the leakage with brazing, flashing the system , vaccuming the system, checking & repairing nterconnection complete in all respect as required at site. i.c dismantled of old material etc. as reqd. |
| 63 | Supply & Replacement of 2.0 TR WTAC / STAC burnt out / defective copper condenser coil with new one of the same size and design suitable for 2.0 TR Split type AC Out Door unit i/c breezing the all copper pipe with all distribution joint's and make sure the connections with capillary tube linking dryer duly proper etc. Nightrogen pressure testing, leak detections, vaccumizing the unit, complete as reqd. i/.c dismantled of old material etc. as reqd |
| 64 | Supplying & fixing of following capacity compressor in the existing WTAC / Split AC making copper pipe connection, brazong pressure testing and supplying and charging M-22/R-32/R-410A refrigerant gas charging i/c cutting the copper piping dismantling of the old compressor complete as reqd. |
| 65 | Compressor -2.0 TR |
| 66 | Providing and fixing WTAC /STAC fan motor capcity 1/4 to 1/8 HP i/c dismantling the burnt out motor from the existing unit & fixing of new motor making cnnection, testing complete etc as reqd. |
| 67 | Supplying & fixing of copper refrigerant pipe of size 1/4\\", 1/2\\" or 5/8\\" (as per suitable existing) with insulation and copper wire 3core 80-20 (2.5 sqmm) i/c all connection in the existing AC units i/c dismantled as per reqd at site. |
| 68 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 69 | SH-IV:- Fire Alarm system |
| 70 | Dismantling & Cleaning of Existing Detector like multi criteria optical smoke cum Heat detectors UL listed / rise cum fixed temparature type heat detector UL listed/Addressable manual call point UL listed / Multi-tone hooters with strobe lights UL listed i/c Checking connection of the existing detector installed at various floor of each panel work involve in testing of AFA System etc complete as reqd. |
| 71 | Repairing of existing fire alarm panel i/c intial inspection, checking of power supply system, PCB & module assement, wiring and circuit restroation, component repair/replacement, software/configuration checking along with testing comissioning etc complete as required. |
| 72 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 73 | SH-V:- Comprehensive maintenance of CCTV cameras system |
| 74 | Comprehensive maintenance of Prama / CP PLUS make entire CCTV system consisting of indoor / outdoor Bullet Or Dome IP Cameras, server with Hard Disk Drives, Network Switches, & LCD/LED display monitors as installed at various locations and in the control room i/c weekly checking and cleaning of all installations etc. as required: 24 nos. CCTV & 32 Channel NVR - 1 Nos completed. etc as reqd. |
| 75 | SH-VI:- Credit of Dismantled material |
| 76 | Less Credit cost for following old dismantled materials |
| 77 | Copper winding wire |
| 78 | AC Compressure 2 TR |
| 79 | WTAC/STAC fan motor |
| 80 | AC Copper refrigerant pipe associated |
| 81 | 2.5 mfd condensers |
| 82 | 5/6A/ 15/16A Switch/ Socket/ bell push/ 2 way switch |
| 83 | Call Bell |
| 84 | c' curve SP MCB 6-32A |
| 85 | 6-32A DP MCB 'c' curve/ RCCB |
| 86 | 6-32A SPN MCB 'c' curve |
| 87 | 63 A TPN MCB 'c' curve |
| 88 | 1.5/4.0 sqmm. FRLS Copper conductor cable |
| 89 | 6.0 sqmm. FRLS Copper conductor cable |
| 90 | Ceiling fan |
| 91 | LED Panel light 2x2 ft. |
| 92 | Exhaust Fan/ Fresh Air Fan |
| 93 | Street light fittings /Post Top Lantern Fittings |
| 94 | LED Down lighter |
| 95 | LED Batten light |
| 96 | LED Bulk Head fitting |
| 97 | LED batten mirror light fitting |
| 98 | Modular base & cover plate for 1,2,3,4,5,6,7,8 & 12 module |
| 99 | Modular bell push, ISI marked |
| 100 | Stepped type Modular Fan regulator (2 module) |
| 101 | Aluminium cable associated Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysAug 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender