Tender For Construction Work Of Office Building Of Chief Engineer Aligarh Region, Pwd Aligarh In Aligarh District (Work Of Electrification, Fire Fighting System, Pa Sound System Etc.)
Tender Value
Ref. Documents
Estimated cost
Bid Submission
14 Aug 2026
14 days left
EMD
6.02 Lakhs
Bank guarantee accepted
Document Fee
2354
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Aligarh → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Work Of Office Building Of Chief Engineer Aligarh Region, Pwd Aligarh In Aligarh District (Work Of Electrification, Fire Fighting System, Pa Sound System Etc.)
BOQ
| Sl. No. | Item Description |
| 1 | PART-A (INTERNAL ELECTRIFICATION )Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C As per PS No D.S.R 1.10.3 |
| 2 | wiring for twin control light point with 1.5 sqmm FRLS/HFFR PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit with 2way modular switch modular plate suitable GI box and earthing the point with 1.5sqmm FRLS PVC insulated copper conductor single core cable etc as required As per PS No D.S.R 1.11 |
| 3 | Supplying and drawing following sizes of FRLS /HFFR PVC insulated copper conductor, single core cable in the existing PVC conduit as required. 1x1.5 sqmm.for Inverter As per PS No D.S.R 1.17.1 |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. As per PS No D.S.R 1.31 |
| 5 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. . As per PS No D.S.R 1.32 |
| 6 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. As per PS No D.S.R 1.57 |
| 7 | Supplying and fixing following way, Horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4+18) double door As per PS No D.S.R 2.4.2 |
| 8 | Supplying and fixing following way, Horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4+12) double door As per PS No D.S.R 2.4.1 |
| 9 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door As per PS No D.S.R 2.3.2 |
| 10 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 A As per PS No D.S.R 2.14.1 |
| 11 | Supplying and fixing following rating, 4 pole,(3phase & Nutrual) 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with co nnections, testing and commissioning etc. as required. 25 A As per PS No D.S.R 2.15.1 |
| 12 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A As per PS No D.S.R 2.14.3 |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole As per PS No D.S.R 2.10.1 |
| 14 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X 1.5sq.mm+1X1.5sq. mm earth wire As per PS No D.S.R 1.14.1 |
| 15 | 2X 2.5sq.mm+1X2.5sq. mm earth wire As per PS No D.S.R 1.14.2 |
| 16 | 2X 4sq.mm+1X4sq. mm earth wire As per PS No D.S.R 1.14.3 |
| 17 | 2X 6sq.mm+1X6sq. mm earth wire As per PS No D.S.R 1.14.4 |
| 18 | 2X 10sq.mm+1X6sq. mm earth wire As per PS No D.S.R 1.14.5 |
| 19 | 2X 16sq.mm+1X6sq. mm earth wire As per PS No D.S.R 1.14.6 |
| 20 | 4X 6sq.mm+2X6sq. mm earth wire As per PS No D.S.R 1.14.9 |
| 21 | 4X 16sq.mm+2X6sq. mm earth wire As per PS No D.S.R 1.14.11 |
| 22 | Earthing with G.I. earth plate 600mmX600mmX6mm thick including accessories and provding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr long etc. with charcoal/ coke and salt as required. As per PS No D.S.R 5.4 |
| 23 | Pvoviding & fixing 25mmX5mm GI Strip on surface or in recess for connection etc. As required As per PS No D.S.R 5.15 |
| 24 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. As per PS No D.S.R 1.38 |
| 25 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. 100 mm X 100 mm X 60 mm deep As per PS No D.S.R As per PS No D.S.R 1.22.2 |
| 26 | 180 mm X 100 mm X 60 mm deep As per PS No D.S.R 1.22.5 |
| 27 | 200 mm X 150 mm X 60 mm deep As per PS No D.S.R 1.22.7 |
| 28 | 200 mm X 250 mm X 75 mm deep As per PS No D.S.R 1.22.10 |
| 29 | 250 mm X 300 mm X 100 mm deep As per PS No D.S.R 1.22.16 |
| 30 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS: 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 °C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) As per PS No D.S.R 9.2.3 |
| 31 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. As per PS No D.S.R 1.33 |
| 32 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. As per PS No D.S.R 1.19 |
| 33 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm As per PS No D.S.R 1.21.2 |
| 34 | Suppiying and fixing following size/ modules, Gl box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mm×75mm) As per PS No D.S.R 1.27.1 |
| 35 | Suppiying and fixing following size/ modules, Gl box along with modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mm×75mm) As per PS No D.S.R 1.27.4 |
| 36 | Suppiying and fixing following size/ modules, Gl box along with modular base & cover plate for modular switches in recess etc. as required. 12 Module (200mm×150mm) As per PS No D.S.R 1.27.6 |
| 37 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch. As per PS No D.S.R 1.24.1 |
| 38 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 A switch. As per PS No D.S.R 1.24.3 |
| 39 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 A socket outlet. As per PS No D.S.R 1.24.4 |
| 40 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 A socket outlet. As per PS No D.S.R 1.24.5 |
| 41 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. TV antenna socket outlet As per PS No D.S.R 1.24.7 |
| 42 | Extra for the luvers/ shutters complete with frame for a exhaust fan of all sizes. As per PS No D.S.R 1.51 |
| 43 | S/F of PVC batten/angle holder including connections etc as required As per PS No D.S.R 1.58 |
| 44 | S/F modular blanking plate on the existing modular plate & switch box excluding modular plate etc as required As per PS No D.S.R 1.26 |
| 45 | Numbering of ceilling fan /exhaust fan /fluorecent fittings as required As per PS No D.S.R 1.49 |
| 46 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. 4 way double door TPN MCBDB As per PS No D.S.R 2.24.1 |
| 47 | 6 way double door TPN MCBDB As per PS No D.S.R 2.24.2 |
| 48 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc.as required. 8 way double door SPN MCBDB As per PS No D.S.R 2.23.2 |
| 49 | Providing & laying & fixing GI pipe medium class in ground complete with GI fitting including trenching (75cm deep) re-filling etc. compelete in all respect 100mm dia As per PS No D.S.R 15.13.3 |
| 50 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS: 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI ≥80, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy 135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated CRCA Sheet body (Thickness > 0.5 mm) 18-22 Watt As per PS No D.S.R 8.11.5 |
| 51 | LED Down lighter (SMD Type) (System lumen efficacy >135lm/Watt)Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI ≥80, UGR (Unified Glare Rating) ≤ 19, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management; heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body including trim.15watt. As per PS No D.S.R 8.3.3 |
| 52 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450mm sweep As per PS No D.S.R 1.50.1 |
| 53 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non-Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test IEC 60332-1, Smoke Density IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required.1 Run of Cable As per PS No D.S.R 39.18.1 |
| 54 | Suppling & making & termination with brass compression gland and aluminium lug for following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 KV grade as required. 4X10sqmm (25mm) As per PS No D.S.R 11.1.32 |
| 55 | Suppling & making & termination with brass compression gland and aluminium lug for following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 KV grade as required. 3.1/2X150sqmm (50mm) As per PS No D.S.R 11.1.26 |
| 56 | Supply of fresh air Fan 300 mm 1-phase 900 rpm,230/250 volts,50Hz. Complete in all respect. TS 01/SE/(E/M)-/Agra/25-26 Dated - 15-04-2025 |
| 57 | S/O Exhaust fan 300 mm sweep 900 rpm Heavy duty complete in all respect. TS 01/SE/(E/M)-/Agra/25-26 Dated - 15-04-2025 |
| 58 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground levelover a cushionof 75 mm. thick sand all around and protected with burnt bricks on sides and on top. Onsurface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge,complete in allrespect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 150 sq. mm 3-1/2 core As per PS No 20a.1.16 UPPWD |
| 59 | S/F of water tight oplong 10 W LED Bulk head luminaire having pressure dia cast houseing with driver set confirming to IP 65 and above protection IK 08 high purity /transmisivity UV stablized no Yellowist diffuser / for uniform light distribution detachable driver set, open short circuit protection suitable for 24 hours continuous operation, complete in all respect.1200 system lumains >120 lumain /watt, PF>0.95 CRI>70,>300V over voltage protection, 4KV internal surge protection, matel housing with 5year warrantee CAT AAA As per PS No 23.11 UPPWD |
| 60 | Supply and fixing LED Bulb 15watt lumen 630 to 735 complete in all respect. |
| 61 | S/F 10W LED Mirror Light. complete in all respect. |
| 62 | Supply and fixingof plainor pin type copper tin plated cable socket ( lug ) to the cable leads, insulatingwith tape and makingconnection etc. complete in all respect as per direction of the EngineerIncharge. 4sqmm |
| 63 | Supply and fixingof plainor pin type copper tin plated cable socket ( lug ) to the cable leads, insulatingwith tape and makingconnection etc. complete in all respect as per direction of the EngineerIncharge. 6sqmm |
| 64 | Supply and fixingof plainor pin type copper tin plated cable socket ( lug ) to the cable leads, insulatingwith tape and makingconnection etc. complete in all respect as per direction of the EngineerIncharge. 16sqmm |
| 65 | Supply and fixing hexagonal/Round G.P.fan box of approved make made up of 1.0 mm thick ISI Marked G.P.sheet spot welded Four to Eight holes of 25.4 mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5 mm G.P. Sheet made upper & lower cover duly screwed fitted with 300 mm round zink coted M.S Bar X 12 mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material, labour, T&P etc. required for proper completion of the work |
| 66 | Supply and fixing of G.P. Boxes/Housing for Conceaded LED 340mm wide x 101.6 mm deep(3.0) of approved make made up of 1.0 mm thick ISI Marked G.P.sheet spot welded Four to Eight holes for pipe entry of 25.4 mm of the box. Holes should be semi-shuttered type with 0.5 mm G.P. Sheet made upper & lower cover duly screwed & brand name should be empossed. Including all materials, labour and T&P required for proper completion of work as directed at site by the Engineer in charge. |
| 67 | S/L of 1800mm X900 mm X12mm thick chequered rubber matting of tested quality. |
| 68 | supply and erection of factory fabricated and wired metal clad dust and vermin proof floor mouting. MS channel base with bottom and topmcable entries electrical control panel with TPN MCCB (4Pole 36KA with Thermal magnetic release) swetches complete and instrument chamber etc. complete in all respect. instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage , current and other parameter with each phase with touch type selector switches for different reading, instrument fueses current transformer etc. The panel board shall have suitable capacity electrolytic aluminium busbar snsulated with heat shrik sleeving and mounted on non hygroscopic support such as CMC/DMC support with detaichable side covers and shall be suitable for extension on sides. The MCCB shall be complete with suitable cable end boxes compression gland and indicating lamp on incoming etc. The job includes the groutnig of panel board as per direction of engineer incharge . All outgoing 32A . The switch board shall be fabricated with CRCA sheet with minium thickness of 1.6/2.0 mm. Cubic type swith board shall be of category A only. panel should have manual/ automatic on /off with digital timer switch, suitable size contactor and concern accessories complete in all respect.Incoming 1.250 A / 415V MCCB 4pole 36kA 1 No2. digital metering (MFM) 1 set3. phase indicator (RYB) 1 set4. On/Off Indicator 1 setoutgoing -MCCB 63 A 4 pole 36 kA 4 Nos MCCB 32 A 4 pole 36 kA 2 Nos (1 spare)On/Off Indicator 6 setChange over 63 Amp 4 PoleMCCB 32A 4P 36KA 2Nos. (1 spare) (through changeover)On/Off Indicator 2 set Bus bar250 A four pole aluminium bus bar 1 set |
| 69 | PART-B (EXTERNAL ELECTRIFICATION )Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door as per PS No DSR 2.3.2 |
| 70 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 A as per PS No DSR 2.14.1 |
| 71 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63mm dia (OD-63mm & ID-51mm nominal) as per PS No DSR 15.15.1 |
| 72 | Suppling & making & termination with brass compression gland and aluminium lug for following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 KV grade as required. 2X6sqmm (19mm) as per PS No DSR 11.1.1 |
| 73 | Supplying and drawing following sizes of FRLS /HFFR PVC insulated copper conductor, single core cable in the existing PVC conduit as required. 1x1.5 sqmm.for Inverter as per PS No DSR 1.17.3 |
| 74 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. as per PS No DSR 5.16 |
| 75 | Earthing with G.I. earth Pipe 4.5 Meter Long 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipewith charcoal/ coke and salt as required. as per PS No DSR 5.2 |
| 76 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). Supplying, Installation, Testing & Commissioningof Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electricalcircuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixturesas per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).90 watt as per PS No DSR 8.14.14 |
| 77 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole as per PS No DSR 2.10.1 |
| 78 | Supply and fixing of 7 mtr. G.I. Octagonal pole of approved make (top dia 70 mm, Bottom dia 130 mm & Base plate 12 mm thick) having 3 mm, thickness with single arm bracket length of 1 mtr. length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T & P complete in all respect. as per PS No PWD 21.2 |
| 79 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. CABLE SIZE-6 SQ MM X 2 CORE as per PS No PWD 20a.1.1 |
| 80 | Part C-Internal Hydrant SystemSupplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required Single headed Gunmetal as per PS No 27.9.1 |
| 81 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Gun Metal as per PS No D.S.R 27.16.1 |
| 82 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connectio :Gun Metal as per PS No D.S.R 27.18.1 |
| 83 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with twoor more coats of synthetic enamel paint of required shade complete as required : 80mm dia as per PS No D.S.R 27.7.6 |
| 84 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with twoor more coats of synthetic enamel paint of required shade complete as required : 100mm dia as per PS No D.S.R 27.7.7 |
| 85 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 (b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m as per PS No D.S.R 27.17.1 |
| 86 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M 2 way 100 mm dia ms pipe as per PS No D.S.R 27.19.1 |
| 87 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. as per PS No D.S.R 27.20 |
| 88 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 100 mm as per PS No D.S.R 27.14.5 |
| 89 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required 80 mm as per PS No D.S.R 27.11.4 |
| 90 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required 100 mm as per PS No D.S.R 27.11.5 |
| 91 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. as per PS No D.S.R 27.22 |
| 92 | (a) Supplying, installation, testing and commissioning of electric driven terrace pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads. 450 lpm at 35 m Head as per PS No D.S.R 27.4.2 |
| 93 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger.The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. 2 LOOP PANEL. as per PS No D.S.R 28.2.1.2 |
| 94 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. as per PS No D.S.R 28.2.4 |
| 95 | Supplying, installation, testing & commissioning ofaddressable fire control module complete as required. as per PS No D.S.R 28.2.10 |
| 96 | Supplying, installation, testing & commissioning ofaddressable manual call point complete as required. as per PS No D.S.R 28.2.14 |
| 97 | Supplying, installation, testing & commissioning of intelligentaddressable programmable sounder complete as required. as per PS No D.S.R 28.2.6 |
| 98 | Supplying, installation, testing & commissioning of faultisolator complete with base as required. as per PS No D.S.R 28.2.7 |
| 99 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable,600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. as per PS No D.S.R 28.5.2 |
| 100 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade Onsurface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge,complete in allrespect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.10 sq. mm 4 core as per PS No 20c.1.8 UPPWD |
| 101 | Providing and placing on terrace (at all floor levels)polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fitting and base support for tank.[Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license].Per liters capcity. as per PS No 18.48 (Civil DSR) |
| 102 | SITC of Hose Cabinet Box of 18 SWG M.S.Sheet with glass to accommodate Hose Reel Drum with Ruber Pipe with Nozzle. 2 Nos. RRL Hose and 1 No. Branch Pipe with Nozzle |
| 103 | SITC of Air Release Valve. Complete with accessories. |
| 104 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 105 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 106 | Supply and fixing of self glow type exit signage complete in all respect. |
| 107 | Part D-PA Sound SystemSITC of Chairman Unit Microphone: Base Unit -Frequency Response: 40Hz-16KHz; Sensitivity: -44 dB:2dB ; Supports Discussion & Video; Chairman Unit should have Priprity and Talk button; The talk button should have built-in Dual colour LED light, Green colour indicating its On & Red colour indicating to talk Connectivity : Daisy Chain connection with Loop In Loop Out; Detachable Microphone ; Polar Pattern – Cardioid; LED Light – Should have Red Ring LED Light Indicating Microphone ON/Off; Microphone Length - 420mm or more, Make: ATDSC/Bosch/Telvic |
| 108 | SITC of Delegate Unit Microphone: Base Unit -Frequency Response: 40Hz-16KHz; Sensitivity: -44 dB:2dB ; Supports Discussion & Video; Delegate Base Unit should have Talk button; The talk button should have built-in Dual colour LED light, Green colour indicating its On & Red colour indicating to talk Connectivity : Daisy Chain connection with Loop In Loop Out; Detachable Microphone ; Polar Pattern – Cardioid; LED Light – Should have Red Ring LED Light Indicating Microphone ON/Off; Microphone Length - 420mm or more, Make: ATDSC/Bosch/Telvic |
| 109 | SITC of Audio Controller : The main unit of the portable digital conference system can support 60 units of Chairman & Delegate microphone. ; It support 250 Microphones with extension power unit.; Equipped with four groups or 8p-DIN interface for system connecting.; Modes : Discuss mode, Free mode, FIFO mode (1-9),Limit mode (1-9) ; 9 Microphones can be on at a time. First In First Out ; The working mode is displayed on LCD screen. ; Look At Me – Speaker tracking compatible with camera and processor; Connection: 8PIN x 3 plugs for Microphone ; 8 PIN x1 socket for system connection; RCA : 4 x RCA Port; RJ 45 x 1; XLR Port x 1 Make: ATDSC/Bosch/ Telvic |
| 110 | SITC of \\"Look at me\\" Integrated Controller Processor for Audio Conferencing Microphone, Make: ATDSC/Bosch/Telvic |
| 111 | SITC of Amplifier: Power Output 300W Max., 250W RMS at 10% THD, 220W RMS at 5% THD, Output Regulation 2 dB, no load to full load at 1kHz, Input Channels 6 X Mic. 0.65mV/4.7k Ohms , 2 X Aux 100mV/470k Ohms, Frequency Response 50-15,000Hz ±3dB, S/N Ratio 60dB, Tone Controls Bass ±10dB at 100Hz, Treble±10dB at 10KHz, 8 Ohms & 100V, Digital Player MP3 Player with USB, SD Card & Bluetooth, Power Consumption AC : 250VA DC : 4A, Consist of USB Pen drive Port SD Card Plug and Play, Compatible with Radio & Bluetooth, EQ & Recording, 5 Channels Microphone Inputs, 2 Channels Aux Inputs, 1 Channel Line Output. 100V Constant Voltage Output and 4Ω\ 8 Ω \16 Ω Resistance Output Make: ATDSC/EV/Bosch |
| 112 | SITC of DSP : It should be equipped with reference-quality mic preamps that should spec in at an incredible 0.0007% THD, the DSP should be excellent for live streaming, video conferencing or recording applications specially in PC/Laptop The DSP should includes 2 channels of reference-quality mic preamps, 2 direct outputs for recording, a stereo input channel, a dedicated media channel, an on-board selectable high impedance preamp equalized for guitar, 3-band EQ per channel with bypass, signal/clip indicators, and a stereo master LED meter bridge. The Bluetooth should allow seamless connection to smart devices.The DSP shall stream the stereo mix directly to and from a PC via USB. It should also have a tablet cradle to hold a smart device like tablet on DSP, for convenient display and easy operation, 3-band EQ on all channels, ATDSC/YAMAHA/ Equipson |
| 113 | SITC of Celling/Wall Speaker: 2 way ceiling 8” speaker; Tweeter in the centre: Adjustable tweeter for desired sound in a particular direction; Watt 40W; Power taps: 40W/20W/10W; Frequency Response: 100-20KHz; Sensitivity (1M/1W): 87± 3Db; SPL: 96dB at 100V/ 10W; Rated Power: 40W; Power Taps: 40W/20W/10W; Line Input: 100V; Woofer Speaker Voice Coil Size: 25.9 x 0.17 x 2 Layer; DC Impedance: 7.2Ω; Former: ASV, ATDSC/ Work Pro/ EAW |
| 114 | SITC of Wireless Handheld Microphone: Consists of Handheld microphones with receiver , Distance up to 100 feet (between Receiver and microphone), Individual channel output with level control & mix output. Display on Transmitter & Receiver for frequency indication Make: ATDSC/ Audio Technica/Telvic/ WorkPro/ Clockaudio |
| 115 | SITC of Interactive Flat Panel : Display Panel Size: 86\\", Technology :Zero Bonding Technology; Backlight :DLED; Resolution : 3840×2160 Pixels - 4K UHD & 4K UI; Brightness : 450cd/㎡; Dot Pitch : 0.4935x0.4935mm; Contrast Ratio: 4000:1(Typ.); Response : Time 6ms; Aspect Ratio : 16:9; Touch Screen :IR ; Touch Points : 20Points; Frame Frequency :60Hz; Angle of View :178° ; Ageing :≥50,000 H ; Active Area : 1895.04×1065.96mm; Display Cover : Anti-glare with 9H Hardness (Anti Scratch); System Version: Android11.0; Type C Ports: Front:- 1 x Type C, Rear:- 1 x Type C; Other Ports : 1 x VGA IN, 1 x DP IN, 1 x Audio In, 1 x Audio Out , 1 x RJ45 In ,1 x RJ45 Out ; Built-in Speaker: 2 X 20W; AC Input ×1; Power Switch ×1; Power Supply: 100 V ~ 240 V, 50-60Hz. Make : ATDSC/Viewsonic/Vivitek |
| 116 | SITC of Large Format Display :Size-65\\" , Resolution 3,840 X 2,160 (UHD) , Backlight Unit Type Direct, Brightness (nit) 400, Audio Output: 10W + 10W Speaker ,System : 2.0 ch; Broadcasting System : TV Reception DVB-T2/C/S2 ; Interface Side : HDMI In 3 (2.0), Headphone Out (Phone Jack Type), Rear: USB (2.0), RF In (2), Digital Audio Out (Optical), External Speaker Out(3.5mm phone jack), RJ45 (Usage Purpose, LAN); Power Type : Built-In Power. Make : LG/Samsung/Panasonic /Sony |
| 117 | SITC of OPS: PROCESSOR : Core i5 1O21Ou / 1035G7, Generation: 10th Generation , Max Resolution: 4k@60Hz, MEMORY: 8GB DDR4 Expandable upto 32GB, GRAPHICS : On Board Intel® UHD Graphics , LAN : 10/100/1000 Gigabit LAN , Prime Storage : 256GB SSD M.2, Second Storage : (optional) , USB: 5 USB PORTS (2 x USB 3.0 + 2 x USB 2.0 + 1 TYPE C PORT, MEMORY Slots : 2 SLOTS , AUDIO: AUDIO IN + OUT , DISPLAY PORT : DP + HDMI , Wi-Fi : Dual Wi-Fi (2.4Ghz and 5Ghz), Bluetooth : BT 4.0, OS: Windows / UBANTU 19.04 or ABOVE, Certifications : CE , FCC. |
| 118 | SITC of 4K HDR HDMI Distribution Amplifier, 1:4 HDMI distributor Resolution — Up to 4K@60Hz (4:4:4), Bandwidth — Up to 17.82Gbps, Compliance — HDR10, HDCP 2.2, HDCP authorization control, Max. Data Rate — 17.82Gbps (5.94Gbps per graphic channel) Make: Kramer/Manhattan/MS |
| 119 | SITC of HDMI Extenders over CAT 6, 4K Enabled Transmitter/ Receiver, Make : ATDSC/ Mnhattan/MS Pro |
| 120 | SITC of PTZ Camera USB based : Yes; Zoom : Minimum 20X Optical Zoom; Digital 16X; Iris: f=5.5~110mm ; F1.6 ~ F3.5;Viewing Angle:3.3° (tele) –54.7° Wide; Sensor: 1 /2.8inch or better CMOS sensor; Mega Pixels:2.07 ; Video Format: SDI Video Formats Minimum illumination :0.5 Lux ; DNR:2D & 3D DNR; White Balance :Auto/Manual, Electronic Shutter : Auto/Manual; Video Adjustment: Brightness, Color, Saturation, Contrast, Sharpness, B/W mode, Gamma curve; SNR : >55 dB; Interface : USB 2.0 x1 , USB 3.0 x1, LAN x1, RS232 x 1, HDMI x 1, Pan Rotation:+ 170° Tilt Rotation :-30°~+90° ; Pan Control Speed: 0.1~60°/second ;Tilt Control Speed : 0.1~30°/second ;Preset Speed: Pan: 60°/second, Tilt 30°/second ;Preset Number:255 preset Make: ATDSC/Lumex/ Vaddio |
| 121 | SITC of Equipment Rack of - 18 U Height Space, Front and Rear Lockable Door, Front Door Transparent Acrylic, and Rear powder coated Steel door with cooling Fan, Castors Power Socket Point and MCB protected, complete in all respect, Make: Economic/Vallrack/Cormack |
| 122 | Supply, Laying and Fixing of Video Data Cable, Microphone Cable, Speaker Cables, Power Cables & Connectors for Audio and Video Equipment |
| 123 | Supplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz, 1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS: 1391 Part II 2023. The system shall be able to operate up to 50 °C (out door ambient temperature). 2ton with 5-star BEE Rating as per PS No DSR 32.2.4 |
| 124 | SITC of 5 KVA Automatic Voltage Stablizer (130-280V) Copper Winding. |
| 125 | Charges of wall chase cutting, repairing and painting ts 31 CE dt 14-08-2018 |
| 126 | SITC of Suction/Discharge both copper pipe line in split A.C. Unit 1.8/2.0 ton capacity including brazing, nitrile, rubber insulation 9mm thick class 'O' etc complete 3/8\\" (9.50 mm) and 5/8\\" (15.90mm) |
| 127 | Supply and laying of Heavy Duty PVC Plastic braided 20mm OD flexible pipe for condensed water drain with clipping accessories complete |
| 128 | Supply and laying of 2.5sqmm 4 Core round copper cable for indoor unit to outdoor unit |
| 129 | Supply and laying of 2.5sqmm 3 Core round copper cable for stablizer to indoor unit. |
| 130 | Supply and Fixing of Outdoor Unit stand for split type A.C. |
| 131 | Supply , Fabrication and Installation of M.S. cage for protection of Outdoor unit from animal/theft L X W X H 1300 mm X 600 mm X 1200 mm complete in all respect Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 14, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysAug 14, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender