Project Description

Tender for Tender Shedule For Electrical Works For Extension Of Library Block Along With Light Roofing For Providing New Class Room For The Use Of Fyugp Kariyavattom C Us. (Retender)

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 07-Aug-2026 2026_KU_854026_1 Date 13-Aug-2026

BOQ

Name of Work:- Tender shedule for Electrical works for extension of Library block along with light roofing for providing new class room for the use of FYUGP Kariyavattom C us. (Retender)
Sl. No. Item Description
1Point Wiring
21.10.1IWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
31.10.2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
41.10.3Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
590.3.18.2Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
690.15.4.3Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surgeprotection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificatesfrom NABL accredited Third party lab to be produced mentioning chip manufacturer)
790.3.19.3Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulatedand sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture
890.4.1Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
990.4.2Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.
10OD10810/2025-2026Supply of 1200 mm sweep,BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Air delivery minimum 215 CMM,electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers,etc.., suitable for 230 V, 50 Hz, single phase AC Supply complete as required with minimum 2 Year Warranty.(Item Code : Atomberg EFFICIO-Step Regulator type)
111.44Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copperconductor, single core cable etc. as required
121.47Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
13OD14242/2025-2026Supply of Integral, SMD 2x2 LED, IP 20, 36W LED Recess mounted back lit down light fixture with System efficacy of more than 100lm/W and system lumen output 3600lm. Luminaire shall have powder coated CRCA housing, satin finished translucence (HET) diffuser for Uniform illumination and wider light distribution reputed makes such as Nichia / Cree / Bridgelux / Lumileds should be provided. LEDs used in the product shall comply with EN 62471 . Luminaire shall use SMD type LED. The LED shall be compliant with LM80-08 standard with L70 life of 50000 Hrs tested at maximum current . The LEDs used should be with CCT of 3000 to 5700 K and CRI of Minimum 80. LED Driver shall be Multistage, Isolated type, APFC, Constant Current topology driver with proper heat sink for heat dissipation suitable to operate in input voltage range of 150V to 270V (nominal rated voltage – 240V) with 2KV internal surge protection, Power factor greater than 0.95 and total harmonic distortion (THD) of less than 10% should be integral to the luminaire. Complying to SELV < 60V DC standards. Compliance IS 15885 (Part2/Sec13) : (Item code:Wipro /Crompton/Philips or as instructed by the engineer incharge)
1490.3.11Conveyance, installation, testing and commissioning of surface mounting down light fittings of all types directly on ceiling including giving connections with requiredlength of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washingetc as required.
151.25Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. asrequired
16Switchboard and accessories
171.27.1Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)d
181.56Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socketoutlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings)
191.27.2Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
201.24.3Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
211.24.5Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
22Wiring
231.17.12Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x2.5 sq. mm
241.17.15Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
251.17.18Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 2.5 sq. mm
261.17.3Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X1.5 sq.mm
271.17.6Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
281.21.1Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.20 mm
291.21.2Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.25 mm
3090.9.1.1Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 onsurface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
3190.9.2.1Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 onsurface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
3290.9.1.7Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 onsurface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
3390.9.1.9Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 onsurface / recess including cutting the wall and making good the damages in case of recessed installation as required.Joint cover
341.17.21Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
35Distribution board
3690.11.1.19Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth busand DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
3790.11.1.10Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth busand DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
382.3.3Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
392.3.4Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
40OD18010/2025-2026Supplying and fixing 40 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
412.10.1Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required. Single pole
422.10.4Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required. Triple pole
432.10.3Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required. Double pole
442.11Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
452.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
462.14.2Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
472.13.1Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
482.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
4990.14.1.1Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising ofthe following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
5090.14.10.1Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in theexisting panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermalmagnetic release having adjustable OL
5190.14.10.3Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in theexisting panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermalmagnetic release having adjustable OL
5290.14.2.1Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
5390.14.3.1Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
5490.14.5Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
5590.14.6Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
5690.14.7Supply and providing copper earth bus in the panel board
57OD29470/2025-2026Supply and fixing three phase digital multifunction meter to read V, A and F of accuracy class 1 including giving necessary connections as required.
58OD29467/2025-2026Supply and Fixing of Red, Green, Blue, Yellow, Orange colours LED indicator,AC/DC, 22.5 mm cut including Connection etc..as required
59OD16100/2025-2026Supplying and fixing 4-pole sheet steel enclosure conforming to IEC: 61439-3 on surface / in recess and suitable for mounting MCB / Isolator complete with connections, testing, commissioning etc. as required.
60Cable and termination
6190.12.7.13Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 6 sq mm with factory made clamp
6290.12.7.42Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
639.1.34Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
6490.16.1.2Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
6590.16.5.2Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
669.1.7Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm)
6790.12.7.28Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
689.1.21Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3 1/2X 35 sq. mm (32mm)
69Earthing
70OD12383/2025-2026Supply and laying the following size of strips laid 0.50 m below ground level in ordinary soil including excavating trench of suitable size, refilling, connection / termination with suitable size nuts, bolts, washers etc. as required.25 x 3 mm copper strip tinned at the points of contacts.
71OD12385/2025-2026Supply and providing test joint for the earthing system using 2 numbers of the following size of strips including cutting and bending to shape, drilling necessaryholes and fixed to the watering pipe etc as required.2 x 25 x 3 mm tinned copper strip.
72OD12388/2025-2026Supply and providing earth lead from the test joint to the earth electrode using the following size of conductors / strips including cutting, drilling necessary holes (incase of strip) and fixing firmly with plate, test joint etc as required. 25 x 3 mm copper strip tinned at the points of contacts.
73OD12391/2025-2026Supply and fixing the following size of strip as main earth bus on the surface of wall using necessary finger type supports, connecting all the earths, tinning the points ofcontacts, making good the damages, colour washing etc as required. 25 x 3 mm copper strip tinned at the points of contacts.
745.4Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
75Fire Extinguishers
76OD12394/2025-2026Supply and providing ISI marked 5 Kg dry chemical powder (ABC) fire extinguisher conforming to IS: 15683 along with hose and clamps including fixing it to wall asrequired. (Make- Ceasefire, Safex, Eco fire or Safe pro) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56738631
AUTHORITY Government Departments
TENDER VALUE 8.64 Lakhs
LAST DATE 13-08-2026
Authority
Authority Name Kerala University
Work Description Tender for Tender Shedule For Electrical Works For Extension Of Library Block Along With Light Roofing For Providing New Class Room For The Use Of Fyugp Kariyavattom C Us. (Retender)
Basic Detail
Tender No UE/DB1/ (e-GP)/12/2026-2027
Bidding Type Tender
Location
City Thiruvananthapuram
State Kerala
Key Dates
Publish Date 07 Aug 2026
Submission Date 13 Aug 2026
Open Date 18 Aug 2026
Finance
Tender Value 8.64 Lakhs
Tender Fee 2000
EMD 21700
Exemption Not Available
Document List
BOQ_1443385.xls
epaymentform.pdf
gd.pdf
makeofmaterials-1.pdf
sbd.pdf
Tendernotice_1 (10).pdf
4fd433cf-4d4f-4aff-bddc-00a40c83ff0a.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 13, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 3 days
Aug 13, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Aug 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1443385.xls

pdf

epaymentform.pdf

pdf

gd.pdf

pdf

makeofmaterials-1.pdf

pdf

sbd.pdf

pdf

Tendernotice_1 (10).pdf

html

4fd433cf-4d4f-4aff-bddc-00a40c83ff0a.html

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders