Tender For Petty Repair Pertains To E/M Works In Zone A & B Under Age E/M At Ge Jhansi
Tender Value
50 Lakhs
Estimated cost
Bid Submission
20 Aug 2026
20 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jhansi → Uttar Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Petty Repair Pertains To E/M Works In Zone A & B Under Age E/M At Ge Jhansi
BOQ
| Sl. No. | Item Description |
| 1 | Attending to daily electrical complaints in the Jhansi Military area by deploying adequate skilled teams (Qualified Electrician and Helper) round-the-clock (24/7) to ensure uninterrupted power supply. Scope includes diagnosing and rectifying defects by replacing unserviceable items (switches, sockets, DBs, light/power MCBs, holders, bells, capacitors, plugs, fans, and geysers). Rate includes minor consumables (insulation tapes, screws) and replacement pieces of multi-stranded single-core copper cable (1.5 sq. mm to 6.0 sq. mm) up to 0.50 meters per complaint, complete as directed by the Engineer-in-Charge Note:- (i) Daily signed complaint slips/job cards (in the approved format) are mandatory and shall form an integral part of the running/final bill.(ii) Major equipment or component replacements (excluding minor consumables and wire patches up to 0.5m) shall be measured and paid for separately under respective items of Schedule 'A'.(iii) All deployed electricians and helpers shall report to the E/M Yard on a daily basis for complaint assignment and logging. |
| 2 | Supply and fix in replacement fan capacitor 2.5 m.f.d for ceiling Fan, including taking down old unserviceable capacitor all as specified and directed. |
| 3 | Supply and fix in replacement fan capacitor 4 m.f.d for Exhaust Fan, including taking down old unserviceable all as specified and directed. |
| 4 | Taking down carefully existing copper/aluminium point wiring (light, fan, socket or power) complete of any description wooden boards, laminated sheets from sunken boxes, boards, shades light fitting etc and making good the disturbed surfaces of walls, floors, ceiling etc with cement plaster, putty and paint to match with the existing surface complete all as specified and directed. |
| 5 | Note for serial Item No 5 to 16 : Modular switches, sockets, and fan regulators shall be measured and paid for separately under respective line items |
| 6 | Material & Labour for point wiring for One light / ceiling fan / exhaust fan / call bell point controlled by one switch, wiring shall consist of 1.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, fan regulator, etc. complete all as specified and directed. |
| 7 | Material & Labour for point wiring for One 6A socket point controlled by one switch on independent board, wiring shall consist of 1.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 8 | Material & Labour for point wiring for One 6A socket point controlled by one switch on same board, wiring shall consist of 1.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc. Rate shall be inclusive of loop wiring inside the existing master pressed steel terminal box of thickness not less than 18 SWG sharing the same 3 mm thick phenolic laminated hylam sheet cover, including all hardware and its all accessories complete all as specified and directed. |
| 9 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board, wiring shall consist of 2.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 2.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 10 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board, wiring shall consist of 4 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 4 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 11 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. Wiring shall consist of 2.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 2.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 12 | Material & Labour for point wiring for One light / ceiling fan / exhaust fan / call bell point controlled by one modular switch position, wiring shall consist of 1.5 sq. mm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single-core copper conductor cable conforming to IS:694, along with one run of 1.5 sq. mm green FRLSH insulated copper conductor cable for continuous earthing, drawn through and including medium-grade rigid PVC conduit (minimum 20mm OD) conforming to IS:9537 (Pt-III) concealed in walls or floors. Rate shall be inclusive of modular GI/metal box embedded in the wall, modular grid frames with matching cover plates, all conduit accessories, deep junction boxes, inspection covers, common earth loop connections to the earth dolly, wall chasing, plaster patching, and hardware consumables complete all as specified and directed by the Engineer-in-Charge. |
| 13 | Material & Labour for point wiring for One 6A socket point controlled by one switch on independent board , wiring shall consist of 1.5 sq. mm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single-core copper conductor cable conforming to IS:694, along with one run of 1.5 sq. mm green FRLSH insulated copper conductor cable for continuous earthing, drawn through and including medium-grade rigid PVC conduit (minimum 20mm OD) conforming to IS:9537 (Pt-III) concealed in walls or floors. Rate shall be inclusive of modular GI/metal box embedded in the wall, modular grid frames with matching cover plates, all conduit accessories, deep junction boxes, inspection covers, common earth loop connections to the earth dolly, wall chasing, plaster patching, and hardware consumables complete all as specified and directed by the Engineer-in-Charge. |
| 14 | Material & Labour for point wiring for One 6A socket point controlled by one switch on same board , wiring shall consist of 1.5 sq. mm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single-core copper conductor cable conforming to IS:694, along with one run of 1.5 sq. mm green FRLSH insulated copper conductor cable for continuous earthing, drawn through and including medium-grade rigid PVC conduit (minimum 20mm OD) conforming to IS:9537 (Pt-III) concealed in walls or floors. Rate shall be inclusive of modular GI/metal box embedded in the wall, modular grid frames with matching cover plates, all conduit accessories, deep junction boxes, inspection covers, common earth loop connections to the earth dolly, wall chasing, plaster patching, and hardware consumables complete all as specified and directed by the Engineer-in-Charge. |
| 15 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board, Wiring shall consist of 2.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 2.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 16 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board, Wiring shall consist of 4 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 4 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 17 | Material & Labour for point wiring for One 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane , Wiring shall consist of 2.5 Sqmm 1100 Volts grade FRLSH insulated, unsheathed, multistranded single core copper conductor cable conforming to IS:694, along with one run of 2.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing, drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of separate pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, etc. complete all as specified and directed. |
| 18 | Taking down submain wiring of any size any type and in any position metallic/non metallic PVC conduit of wooden batten complete all as specified and directed. Please Enable Macros to View BoQ information |
| 19 | Taking down submain wiring of any size any type and in any position metallic/non metallic PVC conduit of wooden batten complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 20, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysAug 22, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender