Tender For Providing Of Modernized Kill House At Sarsawa Under Ge (Af) Sarsawa
Tender Overview
Project Description
Tender For Providing Of Modernized Kill House At Sarsawa Under Ge (Af) Sarsawa
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-Aug-2026 | CORRIGENDUM01 | Other | 03-Sep-2026 |
| 2 | 18-Aug-2026 | CORRIGENDUM1 | BOQ | 03-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. |
| 2 | Construction of Modernized Kill House RCC framed construction with permanent specifications all as specified.Note:- Plinth height (FFL) 60cm above existing average GLand 45cm above Made-up Ground Level (MGL). Following additional specifications/instructions are given here as under for guidelines for execution of building work :- (i) Outer Perimeter Wall -The outer perimeter wall of the Kill House shall be 230mm thick fly ash brick masonry wall with RCC framed structure (columns and beams). Brick masonry shall be in cement mortar 1:4 with RCC columns of minimum M25 grade concrete and Fe500 TMT steel. RCC framed structure to comply with IS 456:2000 and brick masonry to comply with IS 2212.(ii) Inner Structure-(a) Overall Dimensions: The inner RCC structure shall be 24.4m x 14m (excluding wall thickness) (Approx) as shown in Ground Floor Plan View. (b) Layout: Eight rooms in two sets of four rooms each. Each room: 4m x 5m clear dimension. Rooms arranged as Room-1 to Room-8 per Ground Floor Plan. |
| 3 | (c) Passages / Corridors: 2m wide passages shall be provided all around the two sets of rooms — on the North side, South side, East side (open passage below catwalk), West side (open passage below catwalk) and between the two sets of 4 rooms (centre corridor). Refer Ground Floor Plan View. (iii) Outer Shed(a) A covered shed shall cover the entire structure of the Kill House including all rooms, corridors, catwalk areas, waiting area and control room. (b) The basic structure shall comprise structural steel with Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick roofing system supported on roof trusses. (iv) Flooring- 100 mm thick PCC (1:2:4) over 100 mm thick PCC (1:4:8) over 200 mm thick hardcore, broken stone or boulders over rammed earth for entire Kill House and 2m compound area all around, as per specification.(v) Corridor -(a) 2m wide passages/corridors shall run all around the two sets of 4 rooms and between the two sets as shown in Ground Floor Plan View. (b) All room doors shall open into the corridor.(vi) Catwalk -(a) General: Two catwalks shall be provided on the first floor- one on each long side (East and West) of the inner structure, running parallel to each set of rooms. Each catwalk shall enable clear visual access to all rooms of the inner structure by a person standing on it. Refer First Floor Plan View. |
| 4 | (b) Dimensions: (i) Length: 24.4m per catwalk (full length of inner structure). (ii) Width: Minimum 2.00 m width. (iii) Floor Height: 2.6m above FFL (0.2m above room wall height of 2.4m — confirmed by sightline analysis). Catwalk deck to be weather resistant heavy duty steel with minimum load bearing capacity of 20 tonnes. (c) Observation Glass: The room-facing side of the catwalk perimeter wall shall have a 1.0m high bulletproof glass panel positioned between 3.6m and 4.6m above FFL (i.e. 1.0m above catwalk floor level), as shown in Section View A-A' and First Floor Plan (legend: Bulletproof glass of height 2.2m refers to total observation height from catwalk floor to glass top). (d) Railing: (i) Height: Minimum 1100mm above catwalk floor level as per IS 4756 / NBC 2016. (ii) Design: Double tubular horizontal rail type; vertical stanchion posts maximum 1500mm apart. (iii) Top rail: 40mm dia MS tube, 3mm wall thickness. Mid rail at 550mm height. Toe board minimum 100mm at floor level. (iv) Finish: Hot dip galvanised minimum 85 microns coating. (v) Load rating: Minimum 0.74 kN/m horizontal as per IS 875 Part-2. (e) Access: A common staircase located at the entry of the shoot house shall permit access to both catwalks without entering the inner structure. A corridor at first floor level as shown in First Floor Plan shall connect the staircase to both catwalks. |
| 5 | (vii) Control RoomOne control room of 3.6m x 5m with permanent structure shall be constructed adjacent to the inner structure at ground floor level as shown in Ground Floor Plan View. Specification(i) RCC framed structure with brick masonary (1:4)(ii) RCC roof M-25 Design Mix(iii) Floor finish - Vitrified tiles over proposed Kill house flooring(iv) Internal wall finishes - 02 coat OBD over a coat of primer(v) External wall finishes - 02 coat exterior emulsion paint over a coat of primer(vi) Appropriate chemical water proofing treatment of roof slab(viii) Waiting Area(a) A waiting area shall be provided adjacent to the staircase at ground floor level as shown in Ground Floor Plan View. Flush Door 60mm thick complete all as specified & as shown in drg - 03 Nos |
| 6 | NOTE: Schedule ‘A’ Part II to VI items which are Prepriced by MES, Bidders shall insert their lump sum amount in the Green coloured field under Col-7 only. |
| 7 | Lump sum price worked out by the Contractor for “EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II |
| 8 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION\\"” as listed in Schedule ‘A’ Part III |
| 9 | Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIFICATION ” as listed in Schedule ‘A’ Part IV |
| 10 | Lump sum price worked out by the Contractor for “LIGHTENING PROTECTION ” as listed in Schedule ‘A’ Part V |
| 11 | Lump sum price worked out by the Contractor for \\"REFRIGERATION AND AIR CONDITIONING” as listed in Schedule ‘A’ Part VI |
| 12 | SCHEDULE `A' PART - VII MISC ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. |
| 13 | INTERNAL ELECTRIFICATION |
| 14 | Supply and fixing wall mounting fan 230 volts single phase 300mm sweep suitable for wall mounting complete all as specified and directed. |
| 15 | Supply and fixing double door three phase distribution board 4 way loadline VTPN upto 125 Amps when MCCB to be used as incomer and made out of CRCA sheet 1.6mm thick, phosphatised powder coated with bus bar 200 Amps, 415 volts, earth stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box, ground terminal blocks, poly layer for protection complete all as specified and directed. Note : (a) MCCB and MCBs are to be measured and paid seperately. (b) Make of MCBs and DB should be same. |
| 16 | Supply and fixing MCCB 25 Amps, 4 pole with adjustable thermal setting and rupturing capacity 16 KA complete all as specified and directed. |
| 17 | SPECIAL ITEMS FOR KILL HOUSE BUILDING |
| 18 | WALLS : CRS RUWAS CLOCOM PANELS HC50185010(Composite Rubber Steel-Close Combat) 500x500x130mm:a) Supply & Fixing of CRS RUAS Composite Anti Ricochet Ballistic Resistant wall Panels of Size 500x500x130mm thick ±5mm with 50mm thick Shredded Hot Moulded bonded Rubber, 18mm laminated wood, MS 50 mm tubular structure for air vent & 10mm thick High Carbon steel plate backing of 450 HBW , 1-2mm Pynate coating, braced with Protection lining for Ballistic purpose, anchored & fixed to existing wall with MS Framed Structure, Fixing with Chemical Resin based Anchor Thread Rods of size M16 / 190 mm Galvanized 5.8 grade Bolts on RCC wall MS framework as per site requirement, conforming to Ballistic Evaluation properties. b) A 25mm gap shall also be provided between the floor and the bottom of the RUWAS CLOCOM Panels for collection of bullet fragments on the floor , properly covered with Anti-richochet Rubber Barriers |
| 19 | MODULAR CLOCOM WALLS : CRS RUWAS -DUAL CLOCOMMODULAR MOVABLE WALLS HC50185010-D (Composite Rubber Steel-Close Combat) 500x500x250mm:a) Supply & Fixing of CRS RUAS Composite Anti Ricochet Ballistic Resistant movable walls of customized Size of 250-300mm thick ±10mm with 50mm thick Shredded Hot Moulded bonded Rubber(Dual Side), 18mm laminated wood( Dual Side), MS 50 mm tubular structure for air vent (Dual Side)& 10mm thick High Carbon steel plate backing of 450 HBW , 1-2mm Pynate coating, braced with Protection lining for Ballistic purpose, anchored & fixed to MS Framed Structure movable with locking wheels as per site requirement, conforming to Ballistic Evaluation properties.b) A 25mm gap shall also be provided between the floor and thebottom of the CLOCOM Walls for collection of bullet fragments onthe floor |
| 20 | CEILING : BRBL PANELS +BAAC PANELS: BRBL PANELS SAW 06-50-36 ( Ballistic Resistant Base Lining) 500x500x95mm: Supply & Fixing of BRBL panel of size 500x500x95mm ±5mm with 6mm MS Layer , 50mm Air Vent & 36mm Wooden Stopper braced with PE,.as a base layer lining for Ballistic purpose, anchored & fixed to existing truss with M12 GI bolts .BAAC PANELS : BAAC RUWO 5050 (Ballistic Acoustic )500x500x100 : Supply & Fixing of Ballistic Acoustic Ceiling Composite lining panel of RUBBER WOOBER’pynate sandwiched panels ,having Rubber made of hot mould crumb rubber granules & Wood Fibre 1mm width cement composites 100 mm thick size 500X500 mm ,with noise absorption to be installed on Wooden Stopper for Acoustic vibration management and long life. |
| 21 | FLOOR BALLISTIC RUBBER PANEL 500X500X50mm :Supply & Fixing of 50mm thick Ballistic Rubber Panel made of crumb rubber granules polymerically bonded and moulded with hot moulded cure technology. |
| 22 | Acoustic PanelsSupply & Fixing of Acoustic Panels in the inner face of the outer perimeterwall (room/corridor facing side) shall be lined with acoustic panels of minimum 50mm thickness fixed to the framed structure to reduce internal sound levels to not more than 80 dB during live firing of 7.62mm / 5.56mm ammunition. |
| 23 | S&F Laminated ballistic glass, minimum 40mm overall thickness, borosilicate glass with polycarbonate interlayers. Standard: EN 1063 Class BR6 / NIJ Level III — rated to defeat 7.62 x 51mm NATO, 9mm Parabellum and 5.56 x 45mm calibre at specified test distances fixed with Heavy duty MS hollow section frame 75mm x 50mm x 4mm, powder coated, anchored at base and top with M16 chemical anchors (min 4 Nos per upright). Glass-to-frame joint sealed with structural silicone sealant complete all as specified and directed. |
| 24 | EXTERNAL ELECTRIC SUPPLY |
| 25 | Supply, install, test and commissioning of LT Panel board out door type made out of 3.15 mm CRCA Sheet CPRI tested cubical type totally enclosed weather dust and vermin proof with front and rear opening of 400 Volts 3 phase 4 wire 50 Hz having 4 pole aluminium bus bar capacity 150 Amps insulated with heat shrinkable sleeves RYB and supported on SMC/DMC insulator including internal wiring with FRLS copper wire powder coated including connecting all in coming and out going cable feeders with necessary lugs ferrules etc . The panel should have angle iron support of size 50x50x6 mm with 4 legs of 750 mm long (300 mm grouted in PCC and 450 mm above GL) on the base all around including PCC foundation support, well finishing with cement mortar.Comprising of the following switchgear and accessories are as under:- (Main Panel) (a) Mains Incomming : (i) MCCB 125 Amps 4 Pole 25 KA -01 No b) Outgoing :(i) MCCB 25 Amps 4 pole 16 KA-06 Nos (02 spare)(ii) Digital type Multifunctional meter to measure Amp,Voltage-01 No(iii) LED Indicating lamp with inbuilt selector switch - 01 set of three (iv) CT 100/5A with MCB SP 10 KA-03 |
| 26 | Note for item no 5.01 (i) All MCCB shall be with adjustable Thermal magnetic setting (TMD). (ii) The board shall be epoxy polyster powder coated with structure siemens grey shade RAL-7035 (iii) Sheet metal works shall be processed with nine tank process i.e. degreasing, activation, derusting, water rinsing, phosphating, passivation and water drying.(iv)Busbar shall be of electrolytic grade aluminium and shall be insulated with Red, Yellow, Blue and black colour heat shrinkable PVC sleeves.(v) Earth bus shall run throughout the length of the panel at the bottom of the panel.(vi) Each feeder shall be provided with individual inscription plate made out of black anodized alluminium / polycarbonate sheet with engraved/painted letters. (vii)Power switches/MCCB's will be provided with door operating mechanism, door interlock and padlocking feature.(viii ) Danger notice board with conventional skull & bone sign in postman red to be provided on front & rare side.(ix) All incoming & outgoing feeder shall be provided with cable glands at entry & exit of cable.(x) all MCCB's to be provided with rotary operating handle. |
| 27 | S&F heavy duty industrial exhaust fan of minimum 5000 cfm air handling capacity , suitable for continuous operation in industrial workshop, shooting range environments. The fan shall be of axial / centrigugal type , complete with high efficiency motor , vibration, isolators, mounting frame, safety gaurds, flexible connections, control panel, wiring and all necessary accessories. The system shall be designed to maintain a minimum 10 -15 air changes per hour complete all as specified and directed. |
| 28 | SHOOTING TARGET |
| 29 | Design installation, testing and commissioning of base mounted running target on 5 feet or 2 mtr with activity popup , slicing, turning, swing, double swing, up and down, vertical target sound target all targets are wireless remote operated works on 220 V AC supply 50 Hz complete all as specified and directed. |
| 30 | ELECTRONICS |
| 31 | Supply, installation, testing and commissioning of LED TV 43 inch screen size with latest LED panel technology (IPS/VA/DLED as per OEM design) having minimum Full HD (1920 × 1080) resolution, high brightness and contrast ratio suitable for continuous monitoring application, wide viewing angle (minimum 178°), minimum 2 x HDMI ports, 1 x USB port, audio output, built-in speakers of adequate wattage, low power consumption and energy efficient operation, complete with suitable wall mounting bracket/stand, necessary power cord, HDMI cable, plug top and all connected accessories, including fixing at required height, connection to DVR/CCTV system, testing and commissioning, complete in all respects and in working condition as specified and directed by Engineer-in-Charge.(Make: Sony/Samsung/LG) |
| 32 | Supply, installation, testing and commissioning of CCTV Camera 2 MP (minimum 720P resolution) with 3.6 mm fixed lens, suitable for indoor/outdoor application with minimum IP-66 protection (for outdoor use), having CMOS image sensor, minimum 20–30 m IR night vision, wide dynamic range and digital noise reduction, complete with compatible DVR system of suitable channel capacity with H.264/H.265 compression, HDMI/VGA output, USB port, network interface, and minimum 1 TB surveillance grade HDD, along with regulated power supply unit, necessary connectors, mounting brackets, junction boxes, PVC casing-capping/conduit, suitable size copper coaxial/UTP cable with power cable, complete wiring, termination, testing, configuration and commissioning, complete in all respects and in working condition as specified and directed by Engineer-in-Charge.(Make: SP plus/Honeywell/ Bosch/Panasonic/ Sony) |
| 33 | AUDIO AND PA SYSTEM |
| 34 | Supply and fixing of 250 Watt 100V line multi-channel PA amplifier complete with external zone selector capability and spare power capacity, speaker selector switch, 10 Nos ceiling mounted speakers of 20 Watt each for 10 rooms, wired dynamic cardioid microphone with XLR cable (wireless microphone optional), including all necessary speaker cables, connectors, PVC conduit, fixing accessories and testing for clear voice communication, complete all as specified and directed.(Make: JBL/BOSCH/Honeywell) |
| 35 | FIRE FIGHTING |
| 36 | Supply and fixing of Trolley Mounted Fire Extinguisher of capacity 50 Kg foam type suitable for class A and B fires, consisting of heavy duty steel cylinder mounted on a wheel trolly frame with handle for easy mobility. The extinguisher shall be approved make and ISI marked, conforming to relevant Indian Standards. The trolley shall be fabricated from robust mild steel construction with corrosion resistant coating and fitted with heavy duty rubber wheels for smooth movement on rough and industrial surface. The extinguisher shall be designed for high discharge efficiency and quick response during emergency conditions completeall as specified and as directed. Note :-(a) Capacity 50 Kg (Foam solution)(b) Type : AFFF Mechanical Foam(c) Fire Class : A & B, C, D & F(d) Operating Pressure : As per manufacturer standards (Typically 10-15 bar)(e) Discharge method : Continuous foam jet through nozzle/ branch pipe(f) Mobility : Heavy duty trolley mounted Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender