Tender For Providing Gas Supression System , Fire Fighting & Exit Signage Etc. In Mgsipa, Sector- 26, Chandigarh. (Electrical +Ph Services)
Tender Value
1.54 Crore
Estimated cost
Bid Submission
11 Aug 2026
2 days left
EMD
3.09 Lakhs
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Chandigarh → Chandigarh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing Gas Supression System , Fire Fighting & Exit Signage Etc. In Mgsipa, Sector- 26, Chandigarh. (Electrical +Ph Services)
BOQ
| Sl. No. | Item Description |
| 1 | SITC of 2.0 KG clean agent (FK5-1-12), DLP Assembly with Automatic valve mounted on cylinder, push in connector for tube, 2Kg (KF5-1-12) (UL/FM/ gas, mounting bracket, complete in all respect as desired by the Engineer in charge of work at site. |
| 2 | SITC of 4.0 KG clean agent (FK5-1-12), DLP Assembly with Automatic valve mounted on cylinder, push in connector for tube, 4Kg (KF5-1-12) (UL/FM/) gas, mounting bracket. Complete in all respect as desired by the Engineer in charge of work at site. |
| 3 | SITC of Linear pneumatic heat Detection Tube with all necessary fittings & supports. Complete in all respect as desired by the Engineer in charge of work at site. |
| 4 | SITC of End of Line adapter with pressure gauge for Automatic fire suppression tube used for fittting at the end of the tube for pressurizing and re pressurizing the tube. Fitting made by brass (plated/unplated), Stainless steel, Elastomeric Sealings, Copper Nickle plated, Temperature range TS- 20 Deg C till + 60 Deg C, Maximum working pressure 25 Bars, made as per PED pressure Equipment Directives. Complete in all respect as desired by the Engineer in charge of work at site. |
| 5 | SITC of Pressure Switch to monitor Pressure drop in the tube, switch point 5 Bars. Complete in all respect as desired by the Engineer in charge of work at site. |
| 6 | SITC of Audio Visual Alarm, alarm. Complete in all respect as desired by the Engineer in charge of work at site. |
| 7 | SITC of 10 Zone Microprocessor panel, Voltage 240V, Frequency 50Hz & Number of Phases 3 Conventional (Non Addresable) compatible Complete in all respect as desred by the Engineer in charge of work at site. |
| 8 | SITC of Mannual Call Box (with chain Hammer) (M.S.), SS, Glass, Rectangle shape, 7 to 8 Inch Chain Length etc. Conventional (Non Addresable) compatible Complete in all respect as desred by the Engineer in charge of work at site. |
| 9 | SITC of High Intensity Hooter (M.S). Power I/P 100 V AC or 24 V DC, Sound O/P 100dB (up to 10 feet), Current Consumption 300MA, Housing M S Sheet & Speaker 4 watt Conventional (Non Addresable) compatible Complete in all respect as desred by the Engineer in charge of work at site. |
| 10 | SITC of Smoke Detector is a photoelectric smoke detector with microprocessor- controlled, self-diagnostic circuitry, eliminating the need for burdensome sensitivity test equipment. the also comes with a new magnet-test feature. . Complete in all respect as desred by the Engineer in charge of work at site. |
| 11 | SITC of 4 Non Electric mm Acrylic Sheet based Photo Luminescent Signage, minimum temperature -20 Degree C to 80 Degree C , material Rigid Sheet &thickness 1.5 mm Size 300mm x250mm x 1.5mm Complete in all respect as desred by the Engineer in charge of work at site. |
| 12 | SITC of Heat Detector (ROR cum Fixed), Power source 12v, Operating temperature OØC~ +50ØC, Surge Current (max.) 100 ae A-Start-up time (max.) 60s - stand by current (max.)45 aeA, Non-condensing -Heat Sensitivity 135Ø F/ROR- Start-up- current 200 aeA. Operating Humidity 0%~95% RH Conventional (Non Addresable) compatible Complete in all respect as desred by the Engineer in charge of work at site. |
| 13 | SITC of Beam Detector Voltage 10.2- 32 VDC,Temp -30⁰C to 55⁰C, Detection range (e.g., 5m to 70m) & Humidity 0-95%RH (Non-Condensing). Complete in all respect as desred by the Engineer in charge of work at site. |
| 14 | Supply, installation, testing & Commissioning of Addressable photo-Thermal multi criteria Detector and base with sensitivity range as per NFPA 72 ( 0.5 to 4% obs/ft).The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved Complete in all respect as desred by the Engineer in charge of work at site. |
| 15 | Supply, installation, testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site.UL & FM Approved |
| 16 | Supply, installation, testing & Commissioning of Sounderrated at 80 dBA @ 3m for Audible annunciation a. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. |
| 17 | Supply, installation, testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. |
| 18 | SITC of Emergency exit light with double LED MS dome mounted on top of ligth with EXIT mention in front of light and all switches are with soft touch type. Power consumption of 12 watt LED/70watt Halogen, Battery should be sealed Maintenance free dry batterty 7 Ah 12V. Complete in all respects as desired by the Engineer incharge of work at site. |
| 19 | Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 20 | Fire Survival cable 2Core x 1.5 sq.mm |
| 21 | FOR CENTERALISED COMMAND CENTRE AT SUB-STATION |
| 22 | SITC of 1 loop addressable for fire repeater panel Complete in all respect as desired by the Engineer in charge of work at site. |
| 23 | SITC of monitor module for fire repeater panel Complete in all respect as desired by the Engineer in charge of work at site. |
| 24 | SITC of Hooter with control module for fire repeater panel Complete in all respect as desired by the Engineer in charge of work at site. |
| 25 | Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 26 | Fire Survival cable 2Core x 1.5 sq.mm |
| 27 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 28 | Double Walled Corrugated HDPE Pipe 50/ 38mm (Outer/ Inner dia.) |
| 29 | Hand boring Horizontally for crossing of pipe under road of any obstacle by using Auger/ Bocki method including excavation and joining of pipe upto 160 mm Complete |
| 30 | Supply erection testing & commissioning of NFPA 2001- Clean agent. No residue - safe for electronics, Discharge Time -10s, Pressure Rating -Low pressure (13.5-16 bar), Kit contains FK-5-1-12 Fire Suppression Fluid (2.5lbs/1.4Kg ECS Cylinder bracket (1), EOL Adapter W/Pressure Gauge (1), Rubber Grommets (4), Plastic Loop Clamps (25), UL Listed Clean Agent & Heat Detection Tube, No external power or Human intervention required UL Listed . complete in all respect as desired by the Engineer in charge of work at site. |
| 31 | Supply erection testing & commissioning of NFPA 2001- Clean agent. No residue - safe for electronics, Discharge Time -10s, Pressure Rating -Low pressure (13.5-16 bar), Kit contains FK-5-1-12 Fire Suppression Fluid (5lbs/2.27Kg ECS Cylinder bracket (1), EOL Adapter W/Pressure Gauge (1), Rubber Grommets (4), Plastic Loop Clamps (25), UL Listed Clean Agent & Heat Detection Tube, No external power or Human intervention required, UL Listed. complete in all respect as desired by the Engineer in charge of work at site. |
| 32 | Supply erection testing & commissioning of NFPA 2001- Clean agent. No residue - safe for electronics, Discharge Time -10s, Pressure Rating -Low pressure (13.5-16 bar), Kit contains FK-5-1-12 Fire Suppression Fluid 10lbs/4.54Kg, ECS Cylinder bracket (1), EOL Adapter W/Pressure Gauge (1), Rubber Grommets (4), Plastic Loop Clamps (25), UL Listed Clean Agent & Heat Detection Tube, No external power or Human intervention required, UL Listed. complete in all respect as desired by the Engineer in charge of work at site. |
| 33 | Supply erection testing & commissioning of Pressure switch for signal generation. Complete in all respect as desired by the Engineer in charge of work at site. |
| 34 | Supply erection testing & commissioning of master control Unit with audio visual Alarm with option of monitor module connection to connect system with Addressable fire alarm system. Complete in all respect as desired by the Engineer in charge of work at site. |
| 35 | Supply erection testing & commissioning of heat-sensitive pneumatic polymer tubing UL Listed that reliably detects and releases the extinguishing agent through Heat Detection Tube. Multiple temperature rated tubing options (110 or 180 degree celsius) protect a variety of hazards and equipments. Complete in all respect as desired by the Engineer in charge of work at site. |
| 36 | Public Health:Proving & fixing ISI Marked Non-return valves flanged end class PN-1.0 as per IS:5312/2004 in pipe lines including jointing & cost of Nut Bolt , rubber insertion etc. complete.Note: If Non-return valves class PN-1.6 is used instead of class PN-1.0 , than 5% will be paid extra. Class PN-1.0 as per ISI with gun metal flap |
| 37 | 100mm i/d Non-return valve |
| 38 | 150mm i/d Non-return valve |
| 39 | Supplying, Laying, Testing and Commissioning of ISI marked BUTTERFLY VALVE PN 1.6, with Gun metal seal duly ISI marked complete with rubber insertion, nuts, bolts and washers, matching flanges of required thickness, etc. complete as per specifications. |
| 40 | 80 mm i/d |
| 41 | 100 mm i/d |
| 42 | Providing and fixing Vane type Water flow switch in MS Pipe line for a service pressure up to 450PSI , Minimum flow rate for alarm 10GPM (38 LPM ), Minimum surge 18 FPS (5.5 m/s ) including connection with panel complete in all respect For 50mm to 150 mm pipe line |
| 43 | Providing, fixing and jointing Brass Ball valves screwed with SS/BRASS ball & spindle & Teflon seats, on G.I. Pipe lines including all carriages complete. 25mm i/d Brass Ball valves |
| 44 | Supplying, Installation, Testing and Commissioning of weather proof cabinet for hose fabricated out of 1.6mm thickness M.S. sheet with front glass door having locking arrangement, suitable to accommodate all the necessary pipes, accessories, fittings etc including painting the metal portion with one coat of ready mixed primer paint and two coats of synthetic enamel paint of approved shade and quality, sign writing etc. 600 mm wide x 600 mm high x 300 mm deep Size - (for RRL Reel) |
| 45 | Supplying an Fixing Pendant / Upright type sprinkler with quartzoid bulb, operating temperature 68 / 79 degree centigrade of 15 mm dia orifice sprinler head to approved by UL/SN |
| 46 | Providing, laying, fixing, testing and commissioning of 'C' Class heavy duty MS Pipe conforming to Indian Standard IS : 1239/3589 including fittings like tees, bends, sockets, elbows, flanges, tapers, nuts bolts, gaskets etc. fixing the pipe on the wall / ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete in all respects |
| 47 | 80mm internal diameter |
| 48 | 100mm internal diameter |
| 49 | 150mm internal diameter |
| 50 | Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze(gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing , testing & cost of Nut ,Bolt & insertion sheet, all carriage complete (with the approval of Engineer in-charge). |
| 51 | Class PN-1 as per ISI 100mm i/d Sluice Valves flanged |
| 52 | Supplying, Installation, Testing and Commissioning of G.M Single headed hydrant valve with instantaneous Gun metal peet coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (TypeA) with blank Gunmetal Cap and chain including orifice plate made of 6mm th Stainless steel to keep the pressure not more than 3.5 per sqcm at any point complete in all respects. |
| 53 | Supplying and Installation control valve C/W water motor gong complete with alarm Valve, constant trim, water motor bell, 2No. Pressure Gauge. All parts UL listed. Make Newage complete in all respect. |
| 54 | 150 mm control valve |
| 55 | Supplying, Installation, Testing and Commissioning standard Fire Man's axe with heavy insulated rubber conforming to IS 936 complete in all respect. |
| 56 | Providing and fixing S.S Pressure Gauge complete as required complete in all respect. |
| 57 | Dial diameter 150mm calibration 0-16Kg |
| 58 | Providing and fixing of Pressure switch of approved make in MS pipe line suitable for line presure up 15kg/cm2 & including connection with main panel etc. as requiredcomplete in all restect |
| 59 | Supplying, Installation, Testing and Commissioning of RRL FIRE hose Type A, IS:636, 63mm dia x 15m long with gunmetal male & female couplings (ISI marked) bound & riveted to hose pipes with copper rivets and copper wire as required. |
| 60 | Supplying, Installation, Testing and Commissioning 63 mm dia gun-metal Branch Pipe (ISI marked) with 20mm (nominal internal dia) size Gun metal nozzle confirming to IS 903, suitable for instantaneous connection to interconnect hose pipe coupling as required. |
| 61 | Providing and fixing of FIRE EXTINGUISHER, ABC Powder type (stored pressure) as per IS: 15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in allrespect |
| 62 | 6 Kg. Capacity |
| 63 | Providing and fixing of FIRE EXTINGUISHER, Mechanical Foam Type 9 ltr IS: 15683 Stored Pressure type complete with all accessories as per Manufactures Specification. ISI Mark of approved makecomplete in all respect. |
| 64 | Providing and fixing of FIRE EXTINGUISHER, CO2 type as per IS: 15683complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect. |
| 65 | 4.5 Kg. Capacity |
| 66 | Supplying, Installation, Testing and Commissioning of First Aid-fire Hose reel with MS construction spray painted in post office red, confirming to IS 884 with upto date amendments, complete with rubber hose pipe (IS:444/1987) 20mm dia 30 meter long type- 2, hose reel Drum with bracket as per IS:884, 20mm dia GM nozzle and 20mm dia GM gate valve as required complete with G.I pipe connention with main pipe complete in all respect. |
| 67 | Providing & fixing 560 mm, 500 mm and 450 mm internal diametre circular or 450 mm x 600 mm clear inside opening rectangular RCC manhole cover and frame ISI marked as per IS:12592-2002 including carriage from the stores of the Engineer-in-charge to site of work, loading, unloading including stacking and setting the same to correct lines over manholes including cement concrete copping (M:20) around the frame etc. Dia of steel for lifting hook is 16mm. (for EHD and HD). RCC Man hole cover with Frame 455 x 610 mm rectangular clearopening RCC man hole cover with Extra Heavy duty |
| 68 | Excavation manually in trenches with straight or open cutting in built up street/ lane having wall to wall width of street/ lane upto 3.0 metre, for intramural sullage drains, extramural intercepting drains and outfall drains, storm water channels and other work contingent or incident thereto, to full dimensions and depth as shown on the drawings or as shall be required by Engineer- in-charge including dressing to correct sections and dimensions according to templates and levels, dewatering of rain water, diversion of traffic. Providing and fixing and maintenance of caution boards, fencing, night signals, for leads upto 15m and for all lifts and subsequent refilling, watering and dressing upto groung level, including removal of surplus spoil from the site upto 15 metre distance complete in all respects. For Ordinary gravel soil having gravel upto 40% |
| 69 | Fabrication, supply, installation, testing & commissioning of electrical control panel of cubical construction, floor-mounted type, fabricated out of 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated with approved shade after 7-tank treatment process, including cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering, etc., complete in all respects. Suitable for main fire pump, pressurisation pump & diesel pump set, complete as per CPWD specifications, with following incomings and outgoings, suitable for operation on 415V, 3-phase, 50 Hz AC supply, with enclosure protection class IP42 as required. |
| 70 | Supply Installation Testing of Diesel Engine driven pump suitable for automatic operation,multistage centrifugal pump CI body bronze impellerwith SS shaft mech.seal. Kirloskar,CRI make 2850 LPM @88 Mtr Head complete in all respect. |
| 71 | Supply, installation, testing and commissioning of Kitchen Suppression System comprising of 6 Ltr Stainless Steel (SS) Cylinder with K-Class extinguishing agent, discharge nozzles with protective caps, SS mounting brackets, SS piping with necessary supports, Linear Heat Sensing (LHS) cable rated at 180°C, Low Smoke (LS) cable with End-of-Line (EOL) unit, 2-zone gas release control panel, abort switch, manual release switch, hooter with strobe, 2×1.5 sq.mm control cable and all allied accessories. The system shall provide complete fire protection coverage for 3 nos. kitchen hoods as per applicable standards and OEM specifications |
| 72 | Supply, Installation, Testing and Commissioning (SITC) of Direct Low Pressure (DLP) Fire Suppression System for electrical panel of size 6’×6’×2’ ft, comprising 2 Kg UL-listed FK-5-1-12 clean agent cylinder, end-of-line adapter, low pressure switch for continuous monitoring, red colour heat detection tube with end-of-line plug, T-connection tube, hooter-cum-flasher, pressurizing tube rated for 15–18 bar, along with all necessary fittings, accessories and interconnections, complete in all respects as per OEM specifications and relevant fire safety standards |
| 73 | Supply, Installation, Testing and Commissioning (SITC) of Fire Shaft Door with MS frame, including fabrication, fixing in position with necessary anchors/fasteners, hinges, locking arrangement, fire-rated hardware, surface preparation, painting, and all allied accessories, complete in all respects as per approved design, manufacturer’s specifications and relevant fire safety standards |
| 74 | Supply and fixing of Emergency Action Response (EAR) Sign Board of size 200 mm × 200 mm made of acrylic sheet, with UV printed/reflective signage indicating fire point location, to be installed near the concerned equipment/fire point with necessary screws, spacers and accessories, complete in all respects |
| 75 | Supply of Dräger make Breathing Apparatus with carbon composite cylinder, 9 litre water capacity, 300 bar working pressure, providing minimum 45 minutes duration, complete with face mask, demand valve, pressure gauge, back plate, harness and all standard accessories as per manufacturer’s specifications and relevant safety standards |
| 76 | Supply and Installation of Fire Blanket of size 2 m × 2 m, Air Marshal make, manufactured from fire-resistant fabric with protective storage pouch, suitable for Class A/B fires, complete in all respects as per applicable standards |
| 77 | Supply of Portable Search Light, rechargeable type, with high-intensity LED illumination, battery charger, carrying arrangement and all standard accessories, complete in all respects as per manufacturer’s specifications.. |
| 78 | Providing, installation, testing and commissioning of Flow Switch Panel along with required control cabling of size 2×1.5 sq.mm copper conductor FRLS unarmoured cable and electric hooter, including necessary terminations, glands, lugs, conduits, mounting arrangements and all allied accessories, complete in all respects as per manufacturer’s specifications and relevant standards |
| 79 | Dismantling of existing fire hydrant point including civil work and servicing of hydrant valve and hose real drum complete in all respect. |
| 80 | Dismantling of existing Gong Bell complete in all respects. |
| 81 | Sealing of Ducts/Shaft with non‑flammable MS Sheets 16 SWG, size 2100 x 900 mm, complete in all respects. |
| 82 | Sealing of Ducts/Shaft with non‑flammable sheets, size 1800 x 600 mm, complete in all respects. |
| 83 | Servicing and overhauling of Hose Reel and Landing Valve complete in all respects. |
| 84 | Dismantling of existing Fire Point in Basement complete in all respects. |
| 85 | Dismantling of existing Fire Hydrant Point and converting into shaft condition 900 x 1800 mm with shaft door of same size for smooth operation of Hydrant Valve and First Aid Hose Reel including required civil work, servicing of hydrant valve and hose reel drum, complete in all respects. |
| 86 | Overhauling and servicing of Terrace Pump and fabrication of all‑weather canopy/shed complete in all respects. |
| 87 | Shifting of Terrace Panel from electrical/server room including laying of required cable minimum 10 mtr, size 16 x 4 mm, complete in all respects. |
| 88 | Core cutting of diameter 50 mm to 150 mm complete in all respects. |
| 89 | Overhauling and servicing of Jockey and Main Electrical Panel already installed in the pump room complete in all respects. |
| 90 | Dismantling of old NRV and Butterfly Valve and making connection with required MS Pipe complete in all respects. |
| 91 | Overhauling and servicing of Terrace Pump complete in all respects. |
| 92 | Providing and fixing MS Angle Iron Shed with fibre sheet on top fixing with rivets as per approval of Engineer in charge including cost of material and labour complete in all respects. |
| 93 | Shifting of Outer MS Box to make hydrant valve fully operational complete in all respects. |
| 94 | Painting of all exposed fire fighting ms pipe and accessories required Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 11, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysAug 11, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender