Tender For Work Of Renovation Of Overhead Lt Distribution Network Of 22 Nos Of Distribution Transformer Centres And Improvement Of Voltage At Different Locations Under Canacona Constituency Of Sub-Division-Iii, Canacona, Div-Xvi, Margao
Tender Overview
Project Description
Tender for Work Of Renovation Of Overhead Lt Distribution Network Of 22 Nos Of Distribution Transformer Centres And Improvement Of Voltage At Different Locations Under Canacona Constituency Of Sub-Division-Iii, Canacona, Div-Xvi, Margao
BOQ
| Sl. No. | Item Description |
| 1 | Supply |
| 2 | Supply of 9.0 meters long R.C.C. Pole. |
| 3 | Supply of 7.5 meters long R.C.C. Pole. |
| 4 | Supply of stay set for 7.5 Mtrs long RCC Pole as per technical specification [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 5 | Supply of HDGI stay rod with plate complete for 9 mts. Long RCC pole as per technical specification [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 6 | Supply of Enamelled danger board as per DRG No. CEE/490 |
| 7 | Supply of Hot dip galvanised structure material for mounting Distribution box [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 8 | Supply of HDGI L.A./S.A. cross arm clamps suitable for 9mts RCC pole as per Drg No. CEE/E-524. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 9 | Supply of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 10 | Supply of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 400Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have 'magnetic hold' arrangement to ensure that the box doors always remains in 'closed' positiion when shut even without latching. |
| 11 | Supply of Loss Level-II 200KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer as per technical specification. |
| 12 | Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete with brick masonary. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 13 | Supply of AAC ' ANT ' conductor of size 7/3.14mm. The stringing rate includes transportation, jointing, etc. 7.44 Kms of conductor shall be strung as phases for LT line. The conductor shall be comply to the technical specification. |
| 14 | Supply of AAC ' GNAT ' size 7/2.21mm conductor for neutral, streetlight and jumpering as well as guarding. The conductor shall be comply to technical specification. |
| 15 | Supply of HDGI 4 pin LT cross arm channel type as per Drg. No. CEE/E/705. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 16 | Supply of HDGI 2 pin LT cross arm channel type as per Drg. No. CEE/E/704. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 17 | Supply of a) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN & b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. |
| 18 | Supply of a) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers. |
| 19 | Supply HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½\\" x 5/8\\" or 4\\" x 5/8\\",6\\"x5/8\\", 8\\"x5/8\\" or as per the requirement. |
| 20 | Providing of Low Tension metering to the DTC by Suplying of following Materials: 1) Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date 2) Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category \\"A\\" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. 3) 1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.4) Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) 5 Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug. |
| 21 | Supply of CAMR Modem as per technical specification. |
| 22 | Supply of XLPE cable armoured 3 ½ core 185 sqmm 1.1kv grade. |
| 23 | Supply of XLPE cable armoured 3 ½ core 120sqmm 1.1kv grade. |
| 24 | Supply of Aluminium Lugs, size 185 sq.mm as per technical specification |
| 25 | Supply of Aluminium Lugs, size 120 sq.mm as per technical specification |
| 26 | Supply of XLPE cable 11KV 3C X 300 sq.mm armoured |
| 27 | Supply of XLPE cable 11KV 3C X 95 sq.mm armoured |
| 28 | Supply of H.S 11K V Straight through joint 3 core, 300 SQMM |
| 29 | Supply of H.S.11 KV Termination kit indoor 300 sqmm. XLPE 3 core |
| 30 | Supply of H.S.11 KV Termination kit indoor 95 sqmm. XLPE 3 core |
| 31 | Supply of H.S.11 KV Termination kit outdoor 95 sqmm. XLPE 3 core |
| 32 | 3 WAY RMU, 11KV, 630A, 21 kA 3Sec, SF6 Outdoor RMU – 2LBS + 1CB Extensible/Non-Extensible Two (2) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU. |
| 33 | Supply and filling of sand in plinth under floors , trenches including waterin ,ramming consolidating ,dressing complete. |
| 34 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m nominal size)excluding cos t of centering and shuttering and finishing for foundations.ALL WORKS UPTO PLINTH LEVEL |
| 35 | Providing Centering and shuttering including struttings, propping etc and removal of formwork |
| 36 | Supply and Providing of 12mm cement plaster 1:4 (1 - cement: 4 - fine sand) for foundations. |
| 37 | Brick work using common burnt building bricks in cement mortar 1:4 (1 cement : 4 coarse sand) with bricks of class designation 75 kgs/ cm2 (wire cut bricks) |
| 38 | Supply and laying of burnt clay wire cut bricks of 75 Kgs/cm2 class.Wire cut bricks. |
| 39 | Supply of GI Tubular Fencing complete with gate and side dismantling syatem as per the specification for distribution transformers and feeder Pillars (size 4M X 3M X 2M) with concreting for GI fencing supports with plinth(0.3x0.3x0.5) Cu.mx12 nos. Each ratio 1:3:6 and brick masonary [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT, suitable for high salinity coastal areas]. |
| 40 | Supply of underground cable protective cover as per specification as given below:PCC precast cable protective cover of size 480mmX250mmX50mm casted by confined mold vibratory cast of concrete mix M30, having strength of 30N/mm2 at 28 days. |
| 41 | Supply of Class B HDGI pipe of diameter 150 mm dia. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 42 | Supply of Class B HDGI pipe of diameter 100 mm dia for cable rising. |
| 43 | Supply of GI Flat 25 x 5 mm. [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas] |
| 44 | Supply of RCC Cable route Marker |
| 45 | Single Phase 4KVA CCMS Panel |
| 46 | LED Street Light 30Watts |
| 47 | Supply of AAC ' Weasel conductor for connecting earthings. |
| 48 | COST OF ERECTION |
| 49 | Erection of 9.0 meters long R.C.C. Pole. |
| 50 | Erection of 7.5 meters long R.C.C. Pole. |
| 51 | Erection of stay set for 7.5 Mtrs long RCC Pole as per technical specification |
| 52 | Erection of HDGI stay rod with plate complete for 9 mts. Long RCC pole as per technical specification |
| 53 | Erection of Enamelled danger board as per DRG No. CEE/490 |
| 54 | Fabrication, transportation and erection of Hot dip galvanised structure material for mounting Distribution box |
| 55 | Fixing of HDGI L.A./S.A. cross arm clamps suitable for 9mts RCC pole as per Drg No. CEE/E-524. |
| 56 | Fixing of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524. |
| 57 | Erection and commissioning of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 400Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have 'magnetic hold' arrangement to ensure that the box doors always remains in 'closed' positiion when shut even without latching. |
| 58 | Erection, testing and commissioning of Loss Level-II 200KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer as per technical specification. |
| 59 | Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete with brick masonary. |
| 60 | Stringing of AAC ' ANT ' conductor of size 7/3.14mm. The stringing rate includes transportation, jointing, etc. 7.44 Kms of conductor shall be strung as phases for LT line. The conductor shall be comply to the technical specification. |
| 61 | Supply and Stringing of AAC ' GNAT ' size 7/2.21mm conductor for neutral, streetlight and jumpering as well as guarding. The conductor shall be comply to technical specification. |
| 62 | fixing of HDGI 4 pin LT cross arm channel type as per Drg. No. CEE/E/705. |
| 63 | fixing of HDGI 2 pin LT cross arm channel type as per Drg. No. CEE/E/704. |
| 64 | Fixing of a) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN & b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. |
| 65 | Fixing of a) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers. |
| 66 | fixing HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½\\" x 5/8\\" or 4\\" x 5/8\\",6\\"x5/8\\", 8\\"x5/8\\" or as per the requirement. |
| 67 | Providing of Low Tension metering to the DTC by Installing and commissioning of following Materials: 1) Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date 2) Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category \\"A\\" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. 3) 1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.4) Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) 5 Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug. |
| 68 | Erection of XLPE cable armoured 3 ½ core 185 sqmm 1.1kv grade. |
| 69 | erection of XLPE cable armoured 3 ½ core 120sqmm 1.1kv grade. |
| 70 | crimping of Aluminium Lugs, size 185 sq.mm as per technical specification |
| 71 | crimping of Aluminium Lugs, size 120 sq.mm as per technical specification |
| 72 | Erection of XLPE cable 11KV 3C X 300 sq.mm armoured |
| 73 | Erection of XLPE cable 11KV 3C X 95 sq.mm armoured |
| 74 | Erection of H.S 11K V Straight through joint 3 core, 300 SQMM |
| 75 | Erection of H.S.11 KV Termination kit indoor 300 sqmm. XLPE 3 core |
| 76 | Erection of H.S.11 KV Termination kit indoor 95 sqmm. XLPE 3 core |
| 77 | Erection of H.S.11 KV Termination kit outdoor 95 sqmm. XLPE 3 core |
| 78 | 3 WAY RMU, 11KV, 630A, 21 kA 3Sec, SF6 Outdoor RMU – 2LBS + 1CB Extensible/Non-Extensible Two (2) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU. |
| 79 | Earthwork in excavation by mechanical means (hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed in |
| 80 | Refilling the pipeline/foundation trenches plinth sides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 M and all lifts and disposal of surplus earth as directed by Engineer in Charge. |
| 81 | Disposal of exavated soil |
| 82 | Erection of GI Tubular Fencing complete with gate and side dismantling syatem as per the specification for distribution transformers and feeder Pillars (size 4M X 3M X 2M) with concreting for GI fencing supports with plinth(0.3x0.3x0.5) Cu.mx12 nos. Each ratio 1:3:6 and brick masonary [Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT, suitable for high salinity coastal areas]. |
| 83 | Laying of underground cable protective cover as per specification as given below:PCC precast cable protective cover of size 480mmX250mmX50mm casted by confined mold vibratory cast of concrete mix M30, having strength of 30N/mm2 at 28 days. |
| 84 | Laying of Class B HDGI pipe of diameter 150 mm dia. |
| 85 | Laying of Class B HDGI pipe of diameter 100 mm dia for cable rising. |
| 86 | Erection of GI Flat 25 x 5 mm. |
| 87 | Erection of RCC Cable route Marker |
| 88 | Removing of the existing 7.5 m RCC pole. |
| 89 | Removing of the existing 9.0 m RCC pole. |
| 90 | Removing of the existing 11.00m 90lb/yb Rail pole. |
| 91 | Removing and re-fixing of the existing service conenction single phase.-(PVC wire 2C x 4sq.mm 1.1 KV Grade) |
| 92 | Removing and re-fixing of the existing service conenction three phase.(PVC wire 2C x 6sq.mm 1.1 KV Grade) |
| 93 | Removing of 4 Pin cross arms assembly with Clamps, Nut & Bolt for 7.5/ 9.00 Mtr RCC poles/ rail pole. |
| 94 | Removing of 2 Pin cross arms assembly with Clamps, Nut & Bolt. |
| 95 | Removing of LT shackle insulator with metal parts. |
| 96 | Removing of LT Pin Insulator with G.I. pin. |
| 97 | Removing of the existing Old deteriorated ANT conductor. |
| 98 | Removing of the existing Old deteriorated GNAT conductor. |
| 99 | Removing & Re Fixing of LED Street Lights |
| 100 | Removing & Re fixing of Eixing of Street Light clamp 25mm pipe (Top/bottom) |
| 101 | Removing & Re Fixing of G.I Bent Pipe 1mx25mm |
| 102 | Single Phase 4KVA CCMS Panel |
| 103 | LED Street Light 30Watts |
| 104 | Stringing of AAC ' Weasel conductor for connecting earthings. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender