Health and Family Welfare Boards / Undertakings / PSU Closing in 16 days TDR #56690020

Tender For Supply Installation Testing and Commissioning of Hvac System For Ground Floor Ahu Room At Cri Actrec

Issued by Boards / Undertakings / PSU · Raigad, Maharashtra
Tender Value
11.27 Lakhs
Estimated cost
Bid Submission
17 Aug 2026
16 days left
EMD
22560
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Raigad → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Supply Installation Testing and Commissioning of Hvac System For Ground Floor Ahu Room At Cri Actrec

BOQ

Name of Work:- SITC of HVAC system for Ground Floor AHU room at CRI ACTREC
Sl. No. Item Description
1HVAC BOQ
2chilled water Ductable AC
3Supply, Installation, Testing and Commissioning of chilled water Ductable ( Ceiling Suspended Duct able 5.5TR to 6.0 TR ) complete with G.I. casing, with Side/bottom return Air Plenum (5mm PE insulation) or as per site requirement (ABS casing) , Filter box with 8mm Nylon Filter, min 3 Row Deep cooling coil with coper tube diameter is 9.52 mm and thickness 0.33 mm with hydrophilic Aluminium fins. Complete coil must be designed for standard working pressure is 1.6 MPa(16bar) and the test pressure is 3.3MPa(33bar). Unit to be provided with SS drain pan with 7mm PE insulation and +200 mm extended. Direct driven EC FAN (three speed) motor, operated on 450 volts, Three phase, 50Hz, AC supply or single phase as per manufactur recommanded. Unit to be provided with Wireless remote. It shall also have RS485 Modbus communication function for BMS control. ESP for the Fan Coil Unit be 50 pa Minimum. Units need to BIS/Euro vent Certified. The unit included with Infrared Remote Control,micro-controller, drain pump & necessary supporting arrangement with ready made Valve Station with tray complete with butterfly Valves / Gate valves , PIBCV Valves with Actuators, (Actuator and control make Siemens)–Strainer,Pressure cum balancing valves. total valve station require 5 nos of Valves including bypass line. The entire skid shall be coated with Zinc-chromate primer coating and then painted with enamel paint. Price should be included for Electrical cable 10M connection from MCB/Isolator to chilled water unit shall be done by HVAC contractor. Pipe line require from the main header (appx 20 Mtr)also to be considered with nitrile rubber insulation with GC cloth factory fitted as per manufacturer recommandation. no additional cost given for the same. Minimum Capacity should be as follows:
4Min 5.5TR to 6.0TR (min 2100 CFM)
5Hi wall Split Unit (Invertor Type)
6Supplying, Installation, Testing and Commissioning of Hiwall split type air conditioning invertor type machine with each having a capacity and details as mentioned below suitable for operation on R 32/R-410A /R-407 or any other Green refrigerant comprising of Scroll type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system Suitable capacity squirrel cage induction motor having class 'B' insulation suitable for operation on 230/415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine Isolation / disconnect switch, valves and accessories to inter connect compressor and condenser including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L ,U/V, phase reversal protection, single phase preventors i/c copper conductor control and power cable and drain pipe of suitable size and length etc complete as required. The total cooling capacity/heating capacity of tested unit shall have a capacity as per relevant IS code. The lab testing reports as per IS: 8148 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per ISO/International Electro-technical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per specification as required. Note:- Outdoor stand to be consider no additional cost given for the same.
7Hi wall Split Unit 3.0 TR (Invertor Type)
8REFRIGERANT COPPER PIPING
9Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping complete with fittings, with suitable adjustable ring type hanger supports, inting/brazing including accessories,insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastomeric nitrile rubber with GC cloth tubular sleeves sections of specified thickness as given below for Suction and Liquidlines, all accessories as per specifications etc. Note:- individual piping will not be measured All pipe should be laid in ladder/perforated type tray. External pipe should be cover with GI caping cable tray.
1015mm, 28 mm\\" with 1.2mm tube thickness and insulation as per OEM standard. Or equivelent to the unit of 3.0 TR
11COPPER CABLE
12Supply, laying & termination of copper cable from Departmental power supply to IDU & between IDU and ODU unit. Complete with lug fitting, ferruling, gland fitting etc. All Cable should be laid in GI cable tray.
134C x 4 sqmm
144Cx 2.5 sqmm
154Cx 1.5 sqmm
16Supply, Installation, Testing and commissioning of PVC (minimum 15kg/sqcm pressure rated) drain water piping complete with fittings(elbows, tees, reducers,sockets,u trap etc.) supports, jointing insulated with XLPE class O tubular insulation and any other item required to make the system complete. Nominal diameters of pipe in mms as indicated below:
1740 mm dia pipe, Insulation thickness - 19 mm
1832 mm dia pipe, Insulation thickness - 19 mm
1925 mm dia pipe, Insulation thickness - 19 mm
20Supplying, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/ round ducting complete with neoprene rubbergaskets, elbows, splitter dampers, vanes, hangers,supports, bends, transitions, reducers, end caps,collars etc as required complete in all respect in confirmation to IS : 655 and approved drawings andspecifications of following sheet thickness complete asrequired
21Thickness: 0.63 mm Sheet (24 G)
22Supplying and fixing of following thickness dulylaminated aluminium foil of mat finish closed cellNitrile rubber (Class \\"O\\") insulation on existing ductafter applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thickself adhesive nitrile rubber tape insulation complete as per specifications and as required.
23SITC of Extruded aluminium powder coated diffuser/ Grill without volume control damper with all necessary supports as per directed and as instructed by OIC-ES
24Dismatling FCU including piping, valve station, cabling , drain etc as per instruction and as directed by OIC-ES
25Re-installtion of FCU with valve station ,cables etc as per instruction and as directed by OIC-ES
26Chilled water piping PPR-CT (FCU units)
27SITC of PP-RCT (PPR-CT) piping for chilled water circulation.The PP-RCT piping shall conform to ISO 15874 and DIN 8077/8078 standards and shall be manufactured from pressure-rated PP-RCT material of minimum PN 20 rating. Pipes and fittings shall be sourced from the same manufacturer and joined by thermal socket fusion using approved fusion tools; threaded joints shall be permitted only at equipment, valve, and accessory connections using suitable transition fittings with brass inserts. Adequate supports, anchors, guides, and expansion provisions shall be provided in accordance with the manufacturer's recommendations. All chilled water piping shall be insulated with closed-cell elastomeric insulation of minimum 19 mm thickness with GC cloth for pipes hydrostatically tested at 1.5 times the working pressure and maintained for a minimum of two hours without any leakage or pressure loss before insulation and commissioning. Note:- Piping to be laid down in cable tray.
2825 mm PPRCT piping or equivalent to 1.0 TR FCU
29Shutdown acitivity of chilled water piping for connection of 5.5 TR FCU for the first floor by removing chilled water and re-filling as per require pressure for the system which include butterfly valve of 40mm -2 nos with same insulation as per the already have with PUF insulation with 26G Al cladding as per instructed and as directed by OIC-ES.
30Electrical BOQ:
314 x 4 sqmm copper armoured cable Supplying, erecting & terminating FR XLPE insulated, galvanised steel wire armoured (round) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
32Submain Wiring from DB to sockets
33SITC of Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire including PVC conduicts , bends , and all fixing accessories ( Rate for one mtr circuit i.e. 3 x 2.5sqmm wire) for power points
34SITC Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, singlecore cable including surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire FOR POWER POINTS
35Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
36SP MCB C TYPE
37Double pole C Type MCB
38DP MCB Enclosure box Metal type IP 67 TYPE C MCB
39TPN C Type MCB
40TPN MCB Enclosure box Metal type IP 67 TYPE C MCB
41LIGHTING
42LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material andconstruction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operatingvoltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internalsurge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver& electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completein all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copperconductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120 lm/Watt output.LM79 & LM80 Test report and all testing requiredfor LED fixtures as per BIS shall be submitted.Shape size and CCT shall be as approved byEngineer-in-Charge as per requirement. (Thermalmanagement: heat sink of aluminium housingsuch that LED junction temperature shall not riseabove 90°C).
43Powder Coated CRCA Sheet Body (Thickness >0.50 mm) 36 watt
44Supply, Installation, Testing and Commissioning ofceiling fan with Brush Less Direct Current (BLDC)Motor, class of insulation: B, 3 nos. metal( Aluminiumalloy) blades, 30 cm long down rod, 2 nos. canopies,shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance asper IS : 374-2019), THD (Total Harmonic Distortion)less than 10%, suitable for operation with regulatorfor speed control and all remaining accessoriesincluding safety pin, nut bolts, washers, temperaturerise=75 0C (max.), insulation resistance more than 2mega ohm, suitable for 230 V, 50 Hz, single phase ACsupply, Ceiling Fan compliant to IS 374:2019 fan i/cexternal connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cableand earthing etc. as required.
451200mm, service value ≥ 6.0 CM/Min/Watt, airdelivery 210 CM/Min (Minimum)
46Supplying and fixing two module stepped typeelectronic fan regulator on the existing modular plateswitch box including connections but excludingmodular plate etc. as required
47Point wiring
48SITC of Primary point wiring for light point/ fan point/ exhaust fan point/ call bell point with 2 x 1.5sqmm + 1 x 1.5sqmm FRLS PVC insulated copper conductor single core cable in surface / recessed including medium class PVC conduit Heavy(HMS) / casing capping , with modular switch , modular plate, suitable GI box for concealled , suitable PVC box for surface , ceiling fan rose , PVC junction box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. (Average circuit lenght 20 mtr)
49SITC Secondary point wiring light to light looping with 2 x 1.5sqmm + 1 x 1.5sqmm FRLS PVC insulated copper conductor single core cable in surface / recessed including medium class PVC conduit Heavy(HMS) / casing capping , with modular switch, modular plate, suitable GI box for concealled , suitable PVC box for surface , ceiling fan rose , PVC junction box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. ( Average circuit length 10 Mtr )
50PVC casing capping
51Supplying and erecting HMS PVC casing capping 32mm dia. with PVC accessories on wall/ceiling as per specification no. WG-MA/CON
52Supplying and erecting HMS PVC conduit 32mm dia. with PVC accessories on wall/ceiling as per specification no. WG-MA/CON
53Supplying and fixing following size/ modules, PVC / GI box alongwith modular base & cover plate for modular switches in surface or recess etc. as required. • All the power socket tagging to be provided , PVC tags to be provided.• All the power sockets inside and power panel inside wiring ferruling to be done as instructed by EIC ES
543 Module
556 Module
56Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required.
57Modular switch 6A/16A
58Modular Socket 6A/16A
59Removing of existing electrical fixtures , wiring , PVC conduicts , casing cappings , LAN wiring , IT devices , Fire alarm devices , etc as directed by EIC ES
60Civil BOQ
61Removing existing false ceiling of any material and any size with all necessaryallied works, removing out debris out of ACTREC premises as directed by Engg-incharge.
62Providing and fixing Aluminium Composite Panel (ACP) curtain wall system of 4mm thick matching existing ACP Panel or approved colour and make fixing over aluminium frame of 50mm x 25mm thick in grid form including cutting bending, ACP to required size and shape, fixing on Aluminium frame with weather Silicon sealant and finishing the groove with black colour sealant as per manufacturer’s specification complete all inclusive of wastage, labour, shifting, transportation etc. as directed and instructed by Engineer incharge.
63Providing and fixing high density (7.75gm/cc) steel plate to the existing concrete surface using holdfast and hot press technique. Also, the footing required to carry weight of steel plate would be included as per approved design by the consultant.
64Fire Fighting BOQ
65Clean Agent Modular Type-5 kg Capacity Fire Extinguisher with bracket
66Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
67Supplying, installation, testing & commissioning of fault isolator complete with base as required.
68Supplying, installing, testing and commissioning of addressable fire monitor module for flow switches, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device complete as required. Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 Reed relays, EN 54/VdS / UL & FM approved with 3 years equipment replacement warranty.
69Supplying, installing, testing and commissioning of addressable firecontrol/ relay module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs etc., Module shall conforming to IS 5051 Part 2 (Sec 1 to 3) : 1982 reed relays / EN 54/VdS / UL & FM approved with 3 years equipment replacement warrant.
70Supplying, installation, testing & commissioning of addressable manual call point complete as required.
71Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
72Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVCinsulated wire laid in provided conduit/ trunking/ inside pole/ Bus bars or any other places. as per specification No:
73Supplying, installation, testing & commissioning of Response indicator Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56690020
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 11.27 Lakhs
LAST DATE 17-08-2026
Authority
Authority Name Tata Memorial Centre
Work Description Tender for Supply Installation Testing and Commissioning of Hvac System For Ground Floor Ahu Room At Cri Actrec
Basic Detail
Tender No HT/ET-31/AHU Room CRI/2026
Bidding Type Tender
Location
City Raigad
State Maharashtra
Key Dates
Publish Date 27 Jul 2026
Submission Date 17 Aug 2026
Open Date 18 Aug 2026
Finance
Tender Value 11.27 Lakhs
Tender Fee Ref. Documents
EMD 22560
Exemption Not Available
Document List
458f0d6a-b253-4e0d-9902-13480946c415.html
AnnexureForm.xls
BOQ_966115.xls
TDET31.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 27, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 17, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 16 days
Aug 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 17 days

Tender Documents

Download All (ZIP) ↓
html

458f0d6a-b253-4e0d-9902-13480946c415.html

xls

AnnexureForm.xls

xls

BOQ_966115.xls

pdf

TDET31.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders