Tender For General-Government Secretariat, Thiruvananthapuram- Replacement Of Damaged Panel Boards For Floor Control Installed In 5Th And 6Th Floors Of Annex-1 Building.-Replacement Of Panel Boards - 5Th And 6Th Floor - Secretariat Annex 1 -General E
Tender Overview
Project Description
Tender for General-Government Secretariat, Thiruvananthapuram- Replacement Of Damaged Panel Boards For Floor Control Installed In 5Th And 6Th Floors Of Annex-1 Building.-Replacement Of Panel Boards - 5Th And 6Th Floor - Secretariat Annex 1 -General Electrical Work
BOQ
| Sl. No. | Item Description |
| 1 | Part-1- Electrification |
| 2 | OD198153/2023-2024:Supply and providing Sub Main Distribution Board(Load Bank) with IP42 protection complying to IEC 61439-2 with copper bus bar neutral link earth bus etc suitable for providing 4/3 pole MCCBs as incoming and 3pole MCCBs outgoing fixed on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc. as required MCCB Load Bank L&T Enersys-s or equivalent 125A/160A BUS 8way outgoings (Category No.DA20D1084CZZ0) |
| 3 | OD198150/2023-2024:Supply and providing METERING EXTENTION BOX for the existing(8way/12way) Sub Main Distribution Board with IP42 protection complying to IEC61439-2,Fixing on wall using necessary anchor bolts including cutting hole on thewall , making good the damages, colour washing etc. L&T make (categoryNo.CM90439OOPO) or equivalent |
| 4 | OD198151/2023-2024:Supply and providing BOTTOM CABLING BOX for the existing(8way/12way)Sub Main Distribution Board with IP42 protection complying to IEC 61439-2,Fixingon wall using necessary anchor bolts including cutting hole on the wall , making goodthe damages, colour washing etc. L&T make (category No.CM90437OOOO) orequivalent |
| 5 | OD198152/2023-2024:Supply and providing CORNER BOX for the existing(,8way/12 way) Sub MainDisribution Board with IP42 protection complying to IEC 61439-2,Fixing on wallusing necessary anchor bolts including cutting hole on the wall , making good thedamages, colour washing etc. L&T make (category No.CM91089OOOO) orequivalent |
| 6 | OD198154/2023-2024:Supply and providing LEFT &RIGHT SIDE CABLING BOX for the existing(160A bus,-8way) SubMain Distribution Board with IP42 protection complying to IEC 61439-2, fixing onwall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc. L&T make (category No.CM91085OFOO and CM91086OFOO) orequivalent |
| 7 | 2.25:Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for tripple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 8 | OD235701/2023-2024:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 25/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 9 | 90.14.10.1:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 10 | OD198155/2023-2024:Supply and fixing LED indicator (6 V AC/DC, 12V AC/DC, 24 V AC/DC, 48V AC/DC, 63.5V AC/DC, 110 V AC/DC, 220V DC, 240 V AC), 22.5 mm cut out dia Red, Green, Black, Yellow, Orange colours |
| 11 | OD198156/2023-2024:Supply and fixing LED indicator ( 110 V AC/DC, 220V DC, 240 V AC), Blue colour LED indicator, AC/DC, 22.5 mm cut out dia. |
| 12 | OD198157/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.50 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.<br> |
| 13 | OD95832/2026-2027:Supply and fixing ofSelf-adhesive vinyl sticker for lettering and figures of sizes and colour selected by the Engineer in charge for the identification mark to fan, AC, SB, DB, panel board , fire etc as required |
| 14 | OD198160/2023-2024:Supply and fixing of 2.00 mm thick, 3.3 kV, Synthetic elastromeric fire retardant insulating sheet on the floor with using synthetic a2.00 mm thick, 3.3 kV, Synthetic adhesive as required. |
| 15 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 16 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 17 | 9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 18 | 90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 19 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 20 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 21 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 22 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 23 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 24 | 2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 25 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 26 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 27 | 2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 28 | 90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 29 | 2.4.3:Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way(4+24), Double door |
| 30 | 90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface |
| 31 | 90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 32 | 90.10.1.4:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )4 module moulded plastic box on surface |
| 33 | 90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface |
| 34 | 90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface |
| 35 | OD90107/2026-2027:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )12 module moulded plastic box on surface |
| 36 | 90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator |
| 37 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 38 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 39 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 40 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 41 | 1.24.8:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push |
| 42 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 43 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 44 | 1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module |
| 45 | 1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 46 | 1.28.3:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module |
| 47 | 1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module |
| 48 | 1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module |
| 49 | 1.28.6:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.12 Module |
| 50 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 51 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender