Tender For Special Repair/ Replacement Of Pumping Motor Pump Sets, Motor Starter Panels And Cables At installation Hamla Under Ge (Nw) Bhandup
Tender Value
24.80 Lakhs
Estimated cost
Bid Submission
15 Aug 2026
14 days left
EMD
49600
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai Suburban → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair/ Replacement Of Pumping Motor Pump Sets, Motor Starter Panels And Cables At installation Hamla Under Ge (Nw) Bhandup
BOQ
| Sl. No. | Item Description |
| 1 | S & F GI Tubes 80 mm size, 'Medium grade', galvanised, with all fitting arrangements by means of sockets or welded flanged laid in trenches / floor / UG sump / OH tank complete all as specified and directed. |
| 2 | S & F Sluice valve of size 80 mm, Class PN 1.6 cast iron with brass stem with all fixing arrangements complete all as specified and directed. |
| 3 | S & F Non Return valve of size 80 mm, PN 1.6 cast iron with brass stem with all fixing arrangements complete all as specified and directed. |
| 4 | S & F submersible cable of size 10 sqmm 3 core copper cable with flexible pvc conduit including thimbles, lugs, from soft starter to motor pump set complete all as specified and directed. |
| 5 | S & F GI tubes 15 mm size, 'Medium grade', galvanised, with all fitting arrangements from suction to delivery line complete all as specified and directed. |
| 6 | Supply and fixing of 15 mm bore gun metal gate valve heavy duty with iron wheel screwed both ends for iron pipe and fixed of ISI marked complete all as specified and directed. |
| 7 | Supply and laying, jointing and testing, of XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 95 sqmm 3.5 core laid in trenches, ducts, pipes complete all as specified and directed |
| 8 | All as per item no. 7 above, but size 70 sqmm complete all as specified and directed. |
| 9 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth not exceeding 10 sqm for laying of cable and foundation of poles stays and getting out in soft / loose soil complete all as specified and directed. |
| 10 | Returning filling in trenches including spreading levelling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 11 | Removing of excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 12 | M & L for sand cushioning to underground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed.Note: Punned thickness of sand shall be measured. |
| 13 | Supply and laying old size bricks covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230 mm x 115 mm x 75 mm, complete all as specified and directed. |
| 14 | Supply, installation, testing and commissioning of Soft Starter Control Panel suitable for operation of 3-phase induction motor driven water supply pump of capacity 10 & 7.5 HP capacity two soft starter and one standby inbuilt in one control panel, confirming to relevant IS/IEC standards, comprising of the following:Floor / wall mounted, cubicle type, dust, corrosion and vermin proof, CRCA sheet steel enclosure, powder coated, IP-54 protection (IP-65 for outdoor) complete with gland plates, earthing studs and internal wiring.Microprocessor based digital soft starter suitable for 415V, 50 Hz AC supply with adjustable voltage ramp, current limit, soft start / stop features and inbuilt protections including overload, phase failure, phase reversal, under / over voltage and motor stall protection.Automatic bypass contactor arrangement complete with interlocking.Incoming FP MCCB of suitable rating with adjustable trip.Outgoing motor feeder complete with MCCB, contactor and overload protection.Electrolytic copper busbars with PVC sleeves mounted on SMC supports.Control circuit complete with control transformer, push buttons (start / stop / reset), selector switches, indication lamps for power ON, motor ON, trip / fault conditions.Digital multifunction meter for voltage, current, frequency, PF, kW, kWh measurement.Cable termination suitable for aluminium / copper conductor cables including glands and lugs.(for C & A Zone)Including all internal wiring with FRLS copper conductor cables, ferruling, dressing, testing and commissioning including functional trial of pump motor complete all as specified and as directed. |
| 15 | Supply, installation, testing and commissioning of Soft Starter Control Panel suitable for operation of 3-phase induction motor driven water supply pump of capacity 02 nos of 10 HP & 02 nos of 15 HP capacity four soft starter and one standby inbuilt in one control panel , confirming to relevant IS/IEC standards, comprising of the following:Floor/wall mounted, cubicle type, dust,corrosion and vermin proof, CRCA sheet steel enclosure, powder coated, IP-54 protection (IP-65 for outdoor), complete with gland plates, earthing studs and internal wiring.Microprocessor based digital soft starter suitable for 415V, 50 Hz AC supply with adjustable voltage ramp, current limit, soft start/stop features and inbuilt protections including overload, phase failure, phase reversal, under/over voltage and motor stall protection.Automatic bypass contactor arrangement complete with interlocking.Incoming FP MCCB of suitable rating with adjustable trip.Outgoing motor feeder complete with MCCB, contactor and overload protection.Electrolytic copper busbars with PVC sleeves mounted on SMC supports.Control circuit complete with control transformer, push buttons (start / stop / reset), selector switches, indication lamps for power ON, motor ON, trip / fault conditions.Digital multifunction meter for voltage, current, frequency, PF, kW, kWh measurement.Cable termination suitable for aluminium/copper conductor cables including glands and lugs.(for KV & Main P/H)Including all internal wiring with FRLS copper conductor cables, ferruling, dressing, testing and commissioning including functional trial of pump motor complete all as specified and as directed. |
| 16 | Supply, installation, testing and commissioning of Soft Starter Control Panel suitable for operation of 3-phase induction motor driven water supply pump of capacity 02 nos of 10 HP capacity two soft starter and one standby inbuilt in one control panel , confirming to relevant IS / IEC standards, comprising of the following:Floor / wall mounted, cubicle type, dust,corrosion and vermin proof, CRCA sheet steel enclosure, powder coated, IP-54 protection (IP-65 for outdoor), complete with gland plates, earthing studs and internal wiring.Microprocessor based digital soft starter suitable for 415V, 50 Hz AC supply with adjustable voltage ramp, current limit, soft start / stop features and inbuilt protections including overload, phase failure, phase reversal, under / over voltage and motor stall protection.Automatic bypass contactor arrangement complete with interlocking.Incoming FP MCCB of suitable rating with adjustable trip.Outgoing motor feeder complete with MCCB, contactor and overload protection.Electrolytic copper busbars with PVC sleeves mounted on SMC supports.Control circuit complete with control transformer, push buttons (start / stop / reset), selector switches, indication lamps for power ON, motor ON, trip/fault conditions.Digital multifunction meter for voltage, current, frequency, PF, kW, kWh measurement.Cable termination suitable for aluminium/copper conductor cables including glands and lugs.(for KV & Main P/H)Including all internal wiring with FRLS copper conductor cables, ferruling, dressing, testing and commissioning including functional trial of pump motor complete all as specified and as directed. |
| 17 | Earthing complete with galvanised cast iron earth plate electrode of size 600 x 600 x 6.3 mm thick as earth electrode with top edge of the earth plate not less than 1.5 mtr below ground level using GI Strip 32 x 6 mm as earth continuity conductor connected to earth plate by means of GI thimbles nuts, bolts & washers including providing earth wire protection pipe GI light grade 15 mm dia from earth plate to main panel board, motor foundation, watering pipe 20 mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC (1:3:6) adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil removal of surplus excavated material all as site and specified in SSR Part-I 2009 or as directed by Engineer-in-charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 25, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysAug 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender