Tender For Repair / Maintenance Of Lt Electric Supply And Allied Works In Rv Area Under Ge (Af) Palam, Delhi Cantt - 10
Tender Overview
Project Description
Tender for Repair / Maintenance Of Lt Electric Supply And Allied Works In Rv Area Under Ge (Af) Palam, Delhi Cantt - 10
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 01-Aug-2026 | CORRIGENDUM NO 1 | BOQ | 15-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling concrete poles/steel tubular poles, struts of any size complete all as specified and as directed by Engineer-in-Charge. |
| 2 | Supply and fixing steel tubular swaged poles with cast iron base plate, final taper plug bolts, nuts, screws as specified type 410 SP-31 (9.0 Mtr long) including embossing the manufacturers name and IS No of pole and erecting in position all as specified and directed including painting the exposed portion with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat red oxide primer and painting of 30 cm wide blue and white strips upto 1.5 mtr from bottom of the errected pole including marking of pole number complete with all accessories including demolition of concrete complete all as specified and as directed. Note:- Necessary excavation, earth work and PCC shall be measured and paid for separately. |
| 3 | Excavation in trenches in soft/loose soil not exceeding 1.50 Mtrs wide and not exc. 1.5 Mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and as directed. |
| 4 | Excavation in trenches in soft/loose soil exceeding n exc 1.50 Mtrs wide and exc. 1.5 Mtr but n exc 3.0 mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and as directed. |
| 5 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm thick after the cable have been laid, tested complete all as specified and as directed. |
| 6 | Removal of excavated surplus soil to a distance not exc. 50 Mtrs and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and as directed. |
| 7 | M&L for cement concrete (1:2:4) type B-2 (using 40mm graded stone aggregates) as foundation filling in mass concrete complete all as specified and as directed. |
| 8 | M&L for cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregates) as in pedestal/coping including necessary weathering and form work and finishing the exposed surface fair and even complete all as specified and as directed. |
| 9 | Taking out old unserviceable LT under ground cable any type from trenches, pipes & poles complete all as specified and as directed. |
| 10 | Supply and laying in replacement of XLPE LT 1100 Volt Grade, armoured under ground cable of size 10 Sqmm 2 core with stranded aluminium conductor in trenches /passing through pipes/ on poles etc complele all as specified and as directed. |
| 11 | Description all as per srl item No 10.00 above but 16 Sqmm 2 core complele all as specified and as directed. |
| 12 | Description all as per srl item No 10.00 above but 16 Sqmm 4 core complele all as specified and as directed. |
| 13 | Description all as per srl item No 10.00 above but 25 Sqmm 4 core complele all as specified and as directed. |
| 14 | Description all as per srl item No 10.00 above but 35 Sqmm 3.5 core complele all as specified and as directed. |
| 15 | Description all as per srl item No 10.00 above but 50 Sqmm 3.5 core complele all as specified and as directed. |
| 16 | Description all as per srl item No 10.00 above but 70 Sqmm 3.5 core complele all as specified and as directed. |
| 17 | Description all as per srl item No 10.00 above but 95 Sqmm 3.5 core complele all as specified and as directed. |
| 18 | Description all as per srl item No 10.00 above but 120 Sqmm 3.5 core complele all as specified and as directed. |
| 19 | Description all as per srl item No 10.00 above but 150 Sqmm 3.5 core complele all as specified and as directed. |
| 20 | Description all as per srl item No 10.00 above but 185 Sqmm 3.5 core complele all as specified and as directed. |
| 21 | Description all as per srl item No 10.00 above but 240 Sqmm 3.5 core complele all as specified and as directed. |
| 22 | Description all as per srl item No 10.00 above but 300 Sqmm 3.5 core complele all as specified and as directed. Note for ser item No. 10 to 22:- Excavation, earth work and protection of cable shall be measured and paid seperately under respective items of BoQ. |
| 23 | M&L for augering of holes in true horizontal position under road /pavement by means of mechanical rig after doing ultrasound technique to prevent any damage to existing cables/pipe lines coming in route 1.5 Mtr deep and not exceeding 15 Mtrs long including laying HDPE pipe of 150mm dia complete all as specified and as directed. |
| 24 | M&L for defect rectification LT cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc. including and additional excavation in normal alluvial strata required for exposing the cable fault, removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 400 Sqmm 3.5 core. The fault locating equipments shall be brought to site within the hours of instructions from Engr-in-Charge |
| 25 | Supply & jointing heat shrinkable straight through joint kit suitable for LT 1100 Volt grade XLPE cable of size 240-150sqmm 3.5 core complete with treating of cable to make ready for jointing etc complete all as specified and as directed. |
| 26 | Description all as per item No. 25.00 here in before but suitable for cable size 70-95 sq mm complete all as specified and as directed. |
| 27 | Description all as per item No. 25.00 here in before but suitable for cable size 25-50 sq mm complete all as specified and as directed. |
| 28 | M&L for galvanised steel tube, light grade with all fitting complete laid in trenches/ road / Path/ on pole of 80 mm bore complete all as specified and as directed. |
| 29 | M&L for preparing existing old surface of steel tubular poles including cross arms and clamp of any type 09 Mtr/ 11 Mtr long and painting one coat of aluminium paint on the surface of steel tubular pole, with white /blue 30 cm wide strip upto the height of 1.5 mtr above ground level and marking the pole No in 4” dia yellow paint complete all as specified and as directed. |
| 30 | Supply and fixing MCCB 400 Amps 4 pole 50 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 31 | Supply and fixing MCCB 315 Amps 4 pole 36 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 32 | Supply and fixing MCCB 250 Amps 4 pole 25 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 33 | Supply and fixing MCCB 200 Amps 4 pole 25 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 34 | Supply and fixing MCCB 160 Amps 4 pole 25 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 35 | Supply and fixing MCCB 100 Amps 4 pole 16 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 36 | Supply and fixing MCCB 125 Amps 4 pole 16 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed. |
| 37 | Disconnection of electric supply and taking out old unserviceable LT outdoor panel complete all as specified and directed by Engr in charge. |
| 38 | Supply, installation, testing and commissioning in replacement of outdoor type, weather proof, cubical panel board made out of 3.15mm thick MS/CRCA steel sheet mounted on 75cm long legs made out of (40 x 40 x 6) mm equal angle, embedded in PCC (1:2:4) type B-1 blocks of size (15 x 15 x 20)cm, front and back openable, double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable for 3 phase 4 wire 415 volts 50 Hz , factory fabricated with suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 kA for one second and similar design and technology shall be adopted for fabrication of panel. Copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels. Suitable cable glands for cable entry shall be provided. The panel shall be suitable to accomodate the following equiptments :- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 600 amps for phases and neutral - 01 set (b) Digital multifunction meter of size (96 x 96)mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT of appropriate ratio. (c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job Incoming:- (a) MCCB 4 pole, Ics=100%Icu- 35 kA, 415 Volts, 400Amps, with thermal adjustable and fixed magnetic setting with extended terminals -01 Nos. Outgoing :- (a) MCCB 4 pole, Ics=100%Icu-35 kA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals -03 Nos. (b) MCCB 4 pole, Ics=100%Icu - 25 kA, 415 Volts, 125 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos. (c) MCCB 4 pole, Ics=100%Icu - 25 kA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals -01 No. (d) Spare space for MCCB 200 Amps - 01 No to be provided. Note:- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of aluminum lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge. |
| 39 | M&L for earthing in replacement of with galvanized mild steel earth plate electrode (60cm x 60cm) x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip (32x6)mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) with fair finish internal surface of concrete, chamber shall be given 15mm thick plaster in CM (1:4), funnel with wire gauge mesh, 80 mm thick RCC pit cover (320mm x 320mm) of RCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & as directed by Engr-in-Charge. |
| 40 | M&L for earthing in replacement of with galvanized mild steel earth plate electrode (60cm x 60cm) x 6.3mm thick buried directly in ground (earth pit not less than 2.50 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI wire 4mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) with fair finish internal surface of concrete, chamber shall be given 15mm thick plaster in CM (1:4), funnel with wire gauge mesh, 80 mm thick RCC pit cover (320mm x 320mm) of RCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI wire protected by 15 mm dia light grade pipe and watering pipe shall be 20mm bore light grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & as directed by Engr-in-Charge. |
| 41 | M&L for duct pipe double wall corrugated HDPE 63mm dia outer & 50mm inner dia, conforming to IS:16205 of approved colour with fittings for cable protection complete all as specified and as directed. |
| 42 | M&L for duct pipe double wall corrugated HDPE 77 mm dia outer & 63 mm inner dia, conforming to IS:16205 of approved colour with fittings for cable protection complete all as specified and as directed. |
| 43 | M&L for duct pipe double wall corrugated HDPE 110 mm dia outer & 100 mm inner dia, conforming to IS:16205 of approved colour with fittings for cable protection complete all as specified and as directed. |
| 44 | M&L for galvanised steel tube, light grade with all fitting complete laid in trenches/ road / Path/ on pole of 50mm bore all as specified and as directed. |
| 45 | Material & Labour for painting to existing LT panels, outdoor/indoor type, installed at various locations with super enameled spray painting of approved colour on exposed surface including preparation of surfaces and applying primer coat complete all as specified and as directed. |
| 46 | M &L in replacement of lugs/thimbles at termination of LT cable by cutting the end portion and removing insulation and fixing new aluminium lugs /thimble properly with crimbing tool of size 185 -400 sq mm complete all as specified and as directed. |
| 47 | All as per srl item No. 46.00 here in before but for cable size 50-120 sq mm complete all as specified and as directed. |
| 48 | Supply only PVC insulation tape of size 18 mm *6 mtr long FR grade (R/G/B/N colour code) complete all as specified and directed. |
| 49 | M&L for PVC insulated service cable flat or round sheathed, aluminium, multistranded conductor 1100V grade size 16 Sq mm 2 core complete all as specified and as directed. |
| 50 | M&L for PVC insulated service cable flat or round sheathed, aluminium, multistranded conductor 1100V grade size 10 Sq mm 2 core complete all as specified and as directed. |
| 51 | M&L for PVC insulated service cable flat or round sheathed, aluminium, multistranded conductor 1100V grade size 6 Sq mm 2 core complete all as specified and as directed. |
| 52 | Material and labour for submain wiring with two single core 10.0 sq mm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 10.0 Sqmm FRLS multistranded copper conductor cable as continuous earth wire complete all as specified and as directed. |
| 53 | Material and labour for submain wiring with two single core 6.0 sq mm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 6.0 Sqmm FRLS multistranded copper conductor cable as continuous earth wire complete all as specified and as directed. |
| 54 | Material and labour for submain wiring with two single core 4.0 sq mm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 4.0 Sqmm FRLS multistranded copper conductor cable as continuous earth wire complete all as specified and as directed. |
| 55 | Supply and fixing for Isolator 4 pole,100A not less than10kA complete all as specified and directed.. |
| 56 | Supply and fixing for Isolator TP 63A,10kA complete all as specified and directed. |
| 57 | Supply and fixing for MCB, SPN 40 A ,10kA complete all as specified and directed. |
| 58 | Supply and fixing for MCB, SP, 6-32A ,10kA complete all as specified and directed. |
| 59 | Supply and fixing for sheet metal enclosure for distribution board SPN (when MCBs to be used ) 8 way double door, 200 Amps rated bus bars and with neutral, earthing bar and din rail complete all as specified and as directed by Engr-in-Charge. |
| 60 | Supply and fixing for vertical type load line distribution board, double door, 12 way, AC 3 Phase, 415 volts, TPN, bus bar 200 Amps rating and earth bus & din rail suitable for MCCB as incomer complete all as specified and directed. |
| 61 | Supply and fixing for vertical type load line distribution board, double door, 4 way, AC, 3 Phase, 415 volts, TPN, bus bar 100 Amps rating and earth bus & din rail suitable for MCCB as incomer complete all as specified and as directed. |
| 62 | Supply and fixing for vertical type load line distribution board, double door, 8 way, AC, 3 Phase, 415 volts, TPN, bus bar 200 Amps rating and earth bus & din rail suitable for MCCB as incomer complete all as specified and as directed. |
| 63 | Supply only liberty 170 Prepaid energy meter shall be single-phase, two-wire, direct connected type, BIS and CEA compliant, Class 1.0 accuracy, suitable for AMI based prepaid sub-metering applications, manufactured by Secure Meters, rated for 230/240 V (L-N), 50 Hz supply with permissible voltage variation from −40% to +30% and current range of 05-60A, capable of operation in prepaid as well as accounting mode, and shall automatically identify and separately record energy consumption on mains and DG supply without additional wiring or hardware, maintaining separate registers for active and apparent energy and maximum demand; the meter shall support multiple tariff structures including slab-wise tariff, seasonal tariff and time-of-day (ToD) tariff as configured by the utility,provide emergency credit and friendly credit facility, time-based load limiting and remote connect/disconnect, record billing data, load survey and historical energy data, and detect and log all standard tamper and events including magnetic influence, neutral disturbance, current imbalance, reverse energy flow, cover open, bypass, earth fault and power outage/restoration; the meter shall support secure two-way communication through optical port and BLE for local/mobile interface, be compatible with HES, MDM and online vending systems including mobile application and payment gateway based recharge, support encrypted data communication with secure key management, allow remote configuration and firmware upgrade, be housed in IP54 rated sealed-for life engineering plastic enclosure with capacitive touch keypad and consumer display readable during power failure, and shall be suitable for residential, commercial, industrial and defence establishments with DG backed power supply, strictly as per OEM specifications and MES technical requirements. Including 10 year warranty for all the cases except burn, water and physical damage to the meter complete all as specified and directed by Engr in charge. |
| 64 | Fixing only decorative pole upto 4.5 mtr long, top 70 mm, bottom 150mm, section 1, thickness 3 mm, base plate (220mm x 220mm x 10mm), with cast aluminium embelishments type, double side lights with decorative ornamental brackets double arm 1000mm including pole foundation 'J' bolt 20mm x 750mm, nuts, washer etc. Note: (i) Decorative pole lights and arms shall be provided by department. (ii) The cost of cable for supply shall be measured and paid separately. |
| 65 | Supply and fixing in replacement of outdoor type cubical feeder pillar box upto (1000 x 800 x 500)mm size suitable for 3 phase, 4 wire, 415Volt, factory fabricated with CRCA sheet not less than 3 mm thick having modern fabrication process powder coating in approved shade provided with suitable gasket to make it dust and vermin proof and the panel should have upto 400 Amps aluminium Bus bar three phase & neutral mounted on insulators mounted on angle iron frame 40mmx40mmx6mm (angles duly painted with two coats of synthetic enamel paint with one coat of red oxide primer) and front opening type, with aprons for cable entry, with double door shutter and locking arrangement with MCCB 200 Amp 4 pole 25 kA Ics=100%Icu-100% with thermal adjustable and fixed magnetic setting with extended terminals as incoming and outgoing cables etc including PCC foundation in (1:2:4) type B-1 complete all as specified and directed by Engineer -in-charge. |
| 66 | S&F LED sleeky bldg security light (Lens) fitting of 35 watts, 6000K, including GI bracket bend to shape made out of GI pipe light grade of 25 mm, size up to 1.2 mtr long etc complete with two nos of bolts of suitable size, duly painted with two coats of synthetic enameled paint and all fixing arrangements to wall/ pole, including connecting up with 2 core copper flexible wire of size 23/00.0076 all as specified and directed. Make : Bajaj, Philips & Havells |
| 67 | M&L for cutting existing road / foot path bituminous macadam and PCC on foot path for laying protection pipe for cable and making good the disturbed surfaces of road/ foot path to match with the existing surface complete including PCC work all as directed at site by Engr-in-charge. |
| 68 | Supply and fixing chain link fencing 4mm dia galvanised steel wire (150x100)mm mesh including provision of binding wire complete all as specified and directed by Engr-in-charge. |
| 69 | Supply and fixing in replacement integral type automatic street lighting switching unit, single phase 440 Volts, 50 Hz of 5KW, IP 54, consisting of automatic switching unit/sensor (Nature Switch-02), power contactor, suitable MCB rating, 3 phase circuit board, internal wiring with suitable size copper conductor wires etc housed in a Pole mountable SMC enclosure (Sintex make) box with provision of lock and key complete including necessary fixing accessories like MS clamps, nuts, bolts etc complete all as specified and as directed. The automatic switching unit/sensor (Nature Switch-02) should incorporate the following features in it:- (a) Automatic switch ON at DUSK. (b) Automatic switch OFF at DAWN. (c) Over and Low Voltage sense, trip and auto reset. (d) Switching OFF selection from 4-8 hrs . |
| 70 | M&L for welding hinges to existing panel board with existing shutters and fixing to panel board complete all as specified and as directed. |
| 71 | M&L for replacement of shutter with 3 mm thick CRCA sheet as per existing size to match with the existing panel and welding hinges and fixing complete all as specified and as directed. |
| 72 | S&F in replacement LED flood light fitting 150 watt of colour cool white/warm white with internally prewired including electronic driver and connecting up with three core flexible copper conductor 1.5 sqmm cable complete all as specified and as directed. |
| 73 | S&F in replacement LED flood light fitting 100 watt of colour cool white/warm white with internally prewired including electronic driver and connecting up with three core flexible copper conductor 1.5 sqmm cable complete all as specified and as directed. |
| 74 | S&F in replacement LED flood light fitting 50 watt of colour cool white/warm white with internally prewired including electronic driver and connecting up with three core flexible copper conductor 1.5 sqmm cable complete all as specified and as directed. |
| 75 | S&F in replacement of LED 90 watt consisting of a high efficient LED street light made of aluminium die cast aluminium housing with lens, IP66 complete all as specified and as directed. |
| 76 | S&F in replacement of LED 70 watt consisting of a high efficient LED street light made of aluminium die cast aluminium housing with lens, IP66 complete all as specified and as directed. |
| 77 | S&F in replacement of LED 60 watt consisting of a high efficient LED street light made of aluminium die cast aluminium housing with lens, IP66 complete all as specified and as directed. |
| 78 | S&F in replacement of LED 45 watt consisting of a high efficient LED street light made of aluminium die cast aluminium housing with lens, IP66 complete all as specified and as directed. |
| 79 | Supply and fixing in replacement of globe Garden light of any type and colour with 4 feet long PVC pipe 40mm dia including PCC block for fixing of GI pipe complete with all accessories internally pre wired and including connecting up two core copper conductor cable complete all as specified and as directed by Engr-in-Charge. |
| 80 | S&F in repair premium category of LED spike light 10 Watt suitable for outdoor environment with IP65 including necessary jointing material on lugs, glands etc as required at site complete all as specified and as directed by Engr-in-Charge. Make:- Havells cat no LHEVACPBPN6K010 or equivalent in surya/Baja/Crompton/Phillips |
| 81 | S&F in repair 2W decorative LED step light | StepGlow surface mounted anthracite outdoor LED stair light | warm white including necessary jointing material on lugs, glands etc as required at site complete all as specified and as directed by Engr-in-Charge. Make:- Havells, surya/ Baja/ Crompton/ Phillips. |
| 82 | S&F in repair LED tube light 20 Watt | Waterproof LED tube light can be installed as outdoor wall lights for outdoor home, compound wall lights or waterproof tube lights for home (Cool White, 20W) complete all as specified and as directed by Engr-in-Charge. |
| 83 | S&F in repair floures surface spot light decorative surface mounted fixture with compact design available in different finish and colors to match with ceiling requirements. Ceiling cutout Ø 56 mm, height 66mm for 7 W including necessary jointing material on lugs, glands etc as required at site complete all as specified and as directed by Engr-in-Charge. Make:- Havells cat no LHEEAKPBIE1T007 or equivalent in surya/Baja/Crompton/Phillips. |
| 84 | Supply and fixing in repair LED rope Light round type colour warm white/green/pink /pink including connector flexishine plug n play flexible rope light for indoor and outdoor decorations complete all as specified and as directed by Engr-in-Charge. |
| 85 | Supply and fixing in repair LED strip light colour warm white/green/pink /pink including connector flexishine plug n play flexibloe rope light for indoor and outdoor decorations complete all as specified and as directed by Engr-in-Charge. |
| 86 | Supply and fixing in Starlit 12 Meter 72 LEDs string light for decoration | decorative LED string light Warm White/Cool White, Red, Green, Blue, Pink, and Amber, Pack of 1, Polycarbonate complete all as specified and as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 87 | Supply and fixing in Starlit 12 Meter 72 LEDs string light for decoration | decorative LED string light Warm White/Cool White, Red, Green, Blue, Pink, and Amber, Pack of 1, Polycarbonate complete all as specified and as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
TodayBid Submission Deadline
Online submission via eProcurement portal.
TodayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender