Tender For Repair / Maintenance Lt Electric Supply Earthing Infrastructure, Voltage Stabilizer And Allied Works In C Area Under Ge (Af) Palam, Delhi Cantt - 10

Issued by Statutory Bodies & Commissions/Committees · New Delhi, Delhi
Tender Value
38 Lakhs
Estimated cost
Bid Submission
15 Aug 2026
1 days left
EMD
76000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Maintenance Lt Electric Supply Earthing Infrastructure, Voltage Stabilizer And Allied Works In C Area Under Ge (Af) Palam, Delhi Cantt - 10

BOQ

Name of Work:- REPAIR / MAINT LT ELECTRIC SUPPLY EARTHING INFRASTRUCTURE, VOLTAGE STABILIZER AND ALLIED WORKS IN C AREA UNDER GE (AF) PALAM, DELHI CANTT - 10
Sl. No. Item Description
1Dismantling of ACSR or AAC conductor of any description or size complete all as specified and as directed.
2Dismantling cross arms of MS channel or angle sections etc complete and setting/stacking for reuse or to be issued under credit complete all as specified and as directed.
3Disamntling insulators any type any size complete all as specified and as directed.
4Dismantling earth wire or copper conductor, service feedre or distribution span complete all as specified and as directed.
5Dismantling concrete poles/steel tubular poles, struts of any size complete all as specified and as directed by Engineer-in-Charge.
6Supply and fixing steel tubular swaged poles with cast iron base plate, final taper plug bolts, nuts, screws as specified type 410 SP-31 (9.0 Mtr long) including embossing the manufacturers name and IS No of pole and erecting in position all as specified and directed including painting the exposed portion with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat red oxide primer and painting of 30 cm wide blue and white strips upto 1.5 mtr from bottom of the errected pole including marking of pole number complete with all accessories including demolition of concrete complete all as specified and as directed. Note:- Necessary excavation, earth work and PCC shall be measured and paid for separately.
7Excavation in trenches in soft/loose soil not exceeding 1.50 Mtrs wide and not exc. 1.5 Mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and as directed.
8Excavation in trenches in soft/loose soil exceeding n exc 1.50 Mtrs wide and exc. 1.5 Mtr but n exc 3.0 mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and as directed.
9Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm thick after the cable have been laid, tested complete all as specified and as directed.
10Removal of excavated surplus soil to a distance not exc. 50 Mtrs and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and as directed.
11M&L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm) complete all as specified and as directed. Note:- Punned thickness shall only be measured and paid.
12M&L for brick laid in trenches for cable protection of burnt clay sub class ‘B’ complete laid dry flat complete all as specified and as directed.
13M&L for cement concrete (1:2:4) type B-2 (using 40mm graded stone aggregates) as foundation filling in mass concrete complete all as specified and as directed.
14M&L for cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregates) as in pedestal/coping including necessary weathering and form work and finishing the exposed surface fair and even complete all as specified and as directed.
15Taking out old unserviceable LT under ground cable any type from trenches, pipes & poles complete all as specified and as directed.
16Supply and laying in replacement of XLPE LT 1100 Volt Grade, armoured under ground cable of size 16 Sqmm 2 core with stranded aluminium conductor in trenches /passing through pipes/ on poles etc complele all as specified and as directed.
17Description all as per srl item No 16.00 above but 16 Sqmm 4 core complele all as specified and as directed.
18Description all as per srl item No 16.00 above but 25 Sqmm 4 core complele all as specified and as directed.
19Description all as per srl item No 16.00 above but 35 Sqmm 3.5 core complele all as specified and as directed.
20Description all as per srl item No 16.00 above but 70 Sqmm 3.5 core complele all as specified and as directed.
21Description all as per srl item No 16.00 above but 95 Sqmm 3.5 core complele all as specified and as directed.
22Description all as per srl item No 16.00 above but 120 Sqmm 3.5 core complele all as specified and as directed.
23Description all as per srl item No 16.00 above but 150 Sqmm 3.5 core complele all as specified and as directed.
24Description all as per srl item No 16.00 above but 185 Sqmm 3.5 core complele all as specified and as directed. Notes for ser item No. 16.00 to 25.00:- Excavation, earth work and protection of cable shall be measured and paid seperately.
25Relaying of old serviceable LT cables of any size complete all as specified and as directed. Note:- Old LT Cable shall be retrieved from item No. 15.00 above.
26M&L for augering of holes in true horizontal position under road /pavement by means of mechanical rig after doing ultrasound technique to prevent any damage to existing cables/pipe lines coming in route 1.5 Mtr deep and not exceeding 15 Mtrs long including laying HDPE pipe of 150mm dia complete all as specified and as directed.
27M&L for defect rectification LT cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc. including and additional excavation in normal alluvial strata required for exposing the cable fault, removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 400 Sqmm 3.5 core. The fault locating equipments shall be brought to site within the hours of instructions from Engr-in-Charge
28Supply & jointing heat shrinkable straight through joint kit suitable for LT 1100 Volt grade XLPE cable of size 240-150sqmm 3.5 core complete with treating of cable to make ready for jointing etc complete all as specified and as directed.
29Description all as per item No. 28.00 here in before but suitable for cable size 70-95 sq mm complete all as specified and as directed.
30Description all as per item No. 28.00 here in before but suitable for cable size 25-50 sq mm complete all as specified and as directed.
31M&L for galvanised steel tube, light grade with all fitting complete laid in trenches/ road / Path/ on pole of 40 mm bore complete all as specified and as directed.
32Description all as per srl item No 31.00 above but GI pipe of 50mm bore complete all as specified and directed.
33Description all as per srl item No 31.00 above but GI pipe of 80mm bore complete all as specified and directed.
34M&L for preparing existing old surface of steel tubular poles including cross arms and clamp of any type 09 Mtr/ 11 Mtr long and painting one coat of aluminium paint on the surface of steel tubular pole, with white /blue 30 cm wide strip upto the height of 1.5 mtr above ground level and marking the pole No in 4” dia yellow paint complete all as specified and as directed.
35Supply and fixing MCCB 630 Amps 4 pole 50 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
36Supply and fixing MCCB 400 Amps 4 pole 36 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
37Supply and fixing MCCB 315 Amps 4 pole 36 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
38Supply and fixing MCCB 250 Amps 4 pole 36 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
39Supply and fixing MCCB 200 Amps 4 pole 36 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
40Supply and fixing MCCB 160 Amps 4 pole 25 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
41Supply and fixing MCCB 125 Amps 4 pole 16 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
42Supply and fixing MCCB 100 Amps 4 pole 16 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
43Supply and fixing MCCB 63 Amps 4 pole 16 kA 415 Volts 50 Hz (Ics=Icu) with thermal adjustable magnetic settings, necessary conection including taking out old existing unserviceable MCCB from panels etc complete all as specified and as directed.
44Disconnection of electric supply and taking out old unserviceable LT outdoor panel complete all as specified and directed by Engr in charge.
45Supply, installation, testing and commissioning in replacement of outdoor type, weather proof, cubical panel board made out of 3.15 mm thick MS/CRCA steel sheet mounted on 75cm long legs made out of (75 x 75 x 6) mm equal angle, embedded in PCC (1:2:4) type B-1 foundation, front and back openable, double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable for 3 phase 4 wire 415 volts 50 Hz , factory fabricated with suitable foamed-in PU gasket to make it dust/vermin proof, IP 54 protection, Powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 kA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete ,suitable cable glands for cable entry. The panel shall be suitable to accomodate the following equiptments:- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 1200 amps for phases and neutral - 01 set (b) Digital multifunction meter of size (96 x 96) mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT of appropriate ratio (c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job INCOMING :- (a) ACB 4 pole 415V 630 amps, 50 kA capacity manual drawout type with microprocessor release, 50 kA, Ics=Icu - 01 No OUTGOING :- (a) MCCB 4 pole , 36 kA, 415 Volts, 200 Amps with thermal adjustable and fixed magnetic setting with extended terminals -02 Nos. (b) MCCB 4 pole, 25 kA, 415 Volts, 160 Amps with thermal adjustable and fixed magnetic setting with extended terminals -02 Nos. (c) MCCB 4 pole, 16 kA, 415 Volts, 125 Amps, with thermal adjustable and fixed magnetic setting with extended terminals -02 Nos. (d) Spare space for MCCB 100 Amps - 01 No to be provided. Note :- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of cable glands, aluminium lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge.
46Supply, installation, testing and commissioning in replacement of outdoor type,weather proof, cubicle panel board made out of 3.15 mm thick MS/CRCA steel sheet mounted on 75 cm long legs made out of 40 x 40 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 bocks of size 15x15x20 cm , front and back openable,double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable for 3 phase 4 wire 415 volts 50 Hz ,factory febricated with suitable foamed-in PU gasket to make it dust/vermin proof , IP 54 protection, Powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels.complete ,suitable cable glands for cable entry. The panel shall be suitable to accomodate the following equiptments :- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 amps for phases and neutral - 01 set (b) Digital multifunction meter of size 96x96 mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT of appropriate ratio. (c) Panel indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job INCOMING :- (a) MCCB 4 pole 415V 400 amps, 35 kA with thermal adjustable and fixed magnetic setting with extended terminals - 1 No OUTGOING :- (a) MCCB 4 pole, 35 kA, 415 Volts, 160 Amps with thermal adjustable and fixed magnetic setting with extended terminals -01 No. (b) MCCB 4 pole, 16 kA, 415 Volts, 125 Amps with thermal adjustable and fixed magnetic setting with extended terminals -04 Nos. (c) MCCB 4 pole, 16 kA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals -02 Nos. (d) Spare space for MCCB 100 Amps - 01 No to be provided. Note :- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of cable glands, aluminium lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information
47Supply, installation, testing and commissioning in replacement of outdoor type,weather proof, cubicle panel board made out of 3.15 mm thick MS/CRCA steel sheet mounted on 75 cm long legs made out of 40 x 40 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 bocks of size 15x15x20 cm , front and back openable,double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable for 3 phase 4 wire 415 volts 50 Hz ,factory febricated with suitable foamed-in PU gasket to make it dust/vermin proof , IP 54 protection, Powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels.complete ,suitable cable glands for cable entry. The panel shall be suitable to accomodate the following equiptments :- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 amps for phases and neutral - 01 set (b) Digital multifunction meter of size 96x96 mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT of appropriate ratio. (c) Panel indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos (d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job INCOMING :- (a) MCCB 4 pole 415V 400 amps, 35 kA with thermal adjustable and fixed magnetic setting with extended terminals - 1 No OUTGOING :- (a) MCCB 4 pole, 35 kA, 415 Volts, 160 Amps with thermal adjustable and fixed magnetic setting with extended terminals -01 No. (b) MCCB 4 pole, 16 kA, 415 Volts, 125 Amps with thermal adjustable and fixed magnetic setting with extended terminals -04 Nos. (c) MCCB 4 pole, 16 kA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals -02 Nos. (d) Spare space for MCCB 100 Amps - 01 No to be provided. Note :- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of cable glands, aluminium lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56671267
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 38 Lakhs
LAST DATE 15-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Maintenance Lt Electric Supply Earthing Infrastructure, Voltage Stabilizer And Allied Works In C Area Under Ge (Af) Palam, Delhi Cantt - 10
Basic Detail
Tender No 8026/A/T-47/E8
Bidding Type Tender
Location
City New Delhi
State Delhi
Key Dates
Publish Date 25 Jul 2026
Submission Date 15 Aug 2026
Open Date 22 Aug 2026
Finance
Tender Value 38 Lakhs
Tender Fee 500
EMD 76000
Exemption Available
Document List
3be53003-0554-4bac-80ee-bcf13087c354.html
BOQ_874679.xls
tender.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 25, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Aug 22, 2026

Bid Opening Date

Technical bids will be opened and evaluated.