Housing Urban and Rular Development Boards / Undertakings / PSU Closing in 8 days TDR #56651325

Tender For Construction Of 33/11 Kv Sub-Station (2X5 Mva) At Bhoomi Vikas Evam Grishthan Yojna, Bahraich.

Issued by Boards / Undertakings / PSU · Shravasti, Uttar Pradesh
Tender Value
4.80 Crore
Estimated cost
Bid Submission
06 Aug 2026
8 days left
EMD
9.60 Lakhs
Bank guarantee accepted
Document Fee
7080
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Shravasti → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of 33/11 Kv Sub-Station (2X5 Mva) At Bhoomi Vikas Evam Grishthan Yojna, Bahraich.

BOQ

Name of Work:- Construction of 33/11 KV Sub-Station (2x5 MVA) at Bhoomi Vikas Evam Grishthan Yojna, Bahraich.
Sl. No. Item Description
1Supply, Installation, tesing and commissioning of INDOOR TYPE 33KV, HT VCB Panel Board having 2 Nos. Incomers, 1 No. Bus-coupler and 2 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 33KV, 1250Amp, 31.5kA rms-3s, pannel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC. The Board shall consist of following panels :
233KV INCOMER VCB PANEL :
333KV, 1250Amp, 31.5KA rms-3s panel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)
4Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 600/300/5+5A, Core 1 : Class 5P10, 15VA and Core 2 : Class 0.5, 15VA
5Potential Transformers : 1 set of 3 Nos. Single Phase Fixed Type PTs having ratio 33KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection
6Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device
7Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy
8Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make
9Protection & Auxiliary Relays :
101 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%).
111 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V).
121 No. Trip Circuit Supervision Relay
131 No. High Speed Master Trip Relay
14Additional Accessories and Features :
15Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies
16Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As Per Page No. Make:- ABB/Schneider/Siemens/as per direction of Engineer E.I.
1733KV OUTGOING VCB PANEL :
18Same description as INCOMER PANEL above except following changes :
19Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels
20Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 400/200/5+5A PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)
21Additional Protection Relays :
221 No. Numerical Transformer Protection Relay shall have Transformer Differential Protection, Restricted Earth Fault Protection, Over Current + Earth Fault Protection. Relay shall have complete control features.
232 No. Auxiliary Relays for Transformer OTI, WTI & Buchholz - Alram & Trip Protection
241 No. Trip Circuit Supervision Relay
251 No. High Speed Master Trip Relay
26Additional Accessories and Features :
278 Window Annunciator along with Hooter (As per page No. )Make:- ABB/Schneider/Siemens/as per direction of Engineer E.I.
2833KV BUS-COUPLER VCB PANEL :
29Same description as INCOMER PANEL above except following changes :
30Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens/as per direction of Engineer E.I.
31Supply, Installation, tesing and commissioning of INDOOR TYPE 11KV, HT VCB 1250Amp 25KA rms-3sec pannel with SCADA Campatibility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 9 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC.. The Board shall consist of following panels :
3211KV INCOMER VCB PANEL :
3311KV, 800Amp, 18.4KA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)
34Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)
35Potential Transformers : 1 set of 3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection
36Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device
37Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy
38Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make
39Protection & Auxiliary Relays :
401 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%).
411 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V).
421 No. Trip Circuit Supervision Relay
431 No. High Speed Master Trip Relay
44Additional Accessories and Features :
45Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies
46Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As per page No. )Make:- ABB/Schneider/Siemens/as per direction of Engineer E.I.
4711KV OUTGOING VCB PANEL :
48Same description as INCOMER PANEL above except following changes :
49Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels
50Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA. (As per page No. )Make:- ABB/Schneider/Siemens
5111KV BUS-COUPLER VCB PANEL :
52Same description as INCOMER PANEL above except following changes :
53Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens/as per direction of Engineer E.I.
54Supply, Installation, testing commissioning with loading, unloading etc. 33/11 K.V. Power Transformer 5 MVA outdoor distribution Transformer, Tapping range +5% to -15% in step of 2.5% each step with H.T./L.T. bushing, OTI, WTI, Buchholz, Marshalling box OLTC, AVR & RTCC Panel Having Losses-No load losses : 08KW & Load losses : 50 KW as per Latest Specification of UPPCL (Make: TRANSTRON/MODERN/ELECON/as per direction of Engineer E.I. or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report)
55Supply Installation, and Commissioning of 63 KVA, 11/0.433 KV Transformer including loading, unloading, local carriage with all material, labour, T&P required for proper completion of the work. (Make: TRANSTRON/MODERN/ELECON/as per direction of Engineer E.I.or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report)
56Construction of Power Transformer Plinth of Size 3.50 x 3.50 x 1 Mtr. and the top of Plinth 30 cm R.C.C. Work 1:2:4 with fixing of 02 Nos. Rail l.b. complete in all respect with required all material such as steel bar, brick, coarse sand, cement, labour and T&P etc for proper completion of the work as per specification of M.V.V.N.L.
57Construction of Plinth for 63 KVA Transformer of size 2.00 x 1.25 x 1.0 Complete with all material, labour & T&P required for proper completion of work as per specifiaction drawing and direction of E/I.
58Supply,Installation, testing & commissioning of 11 KV Indoor APFC pannel 12.65KV, 3960KVAr, 3- phase, 50 C/s housed in indoor type CRCA panel, capacitor bank having two variable steps of 1188 KVAR.and two variable steps 792 KVAR Aluminium busbars, Epoxy insulators, HT HRC fuse, Surge Suppressor etc. with details are follows-(10 11 KV, aluminium wound, Dry type series reactors a) 1188 KVAR, 11KV 0.2% for 1188 KVAR step-6 Nos., b) 0.792KVAr for 1188 KVAr 0.2% for 792 KVAR step-6 Nos., (2) 11 KV, 3- Phase dry type RVT-1 No. (3) 12 KV 3 Phase indoor type metal enclosed vaccum contactor-12 Nos. (4) Indoor type automatic PFcorrector unit-1 No. (5) IP 42, Indoor CRCA cubicle panel for accommodationg capacitors,series reator, Vaccum contactor, surge suppressor etc. -1set.
599 KV,10 KA, Class lll surse arrestor
60Control cables, lungs/thimble, Junction Box etc.
6111 KV 3 core al, XLPE Insulated 3x300 mm sq. Cable
6211 KV XLPE cable (3x300sq.mm) heat shrinkable jointing kit indoor.
6311 KV VCB Switchgear for capacitor bank with complete arangement Adddisnal pannel for connetion with existing 11 KV bus bar.
64Casting of civil foundation.
65Cable trench for laying of power/control cables.
66Earthing for panel by Chemical pipe earthing.Make ABB/Schneider/Siemens/Crompton/as per direction of Engineer E.I.
67Construction of Plinth for 33 KV RMU of size 2.25 x 2.25 x 0.75 Mtr.Complete with all material, labour & T&P required for proper completion of work as per specifiaction drawing and direction of E/I.
68Supply & Fixing of 200Amp./ 415volt Heavy Duty bouble break complete with HRC fuse and 200A 4way Al Bus Bar on angle iron frame complete in all respect
69Supply & Fixing of 32Amp. 415V. Metal clad TPN requireable type switch fuse unit on angle iron frame complete in all respects. PWD SI No. 315-2018 Cat.B
70Providing necessary T&P and furniture for maintenance staff as per Item Given below.
7112 mm thick Rubber mat of size 2x 1 m PWD S.O.R. 2018 Item No. 1136 No. 4
72Brass Earth chain(MR) Nos. 2
73Rubber hand gloves tested on 1100V. Pair 4
74Maximum load/ minimum load tripping board complete with all necessary equipments. No. 1
75Single line diagram with board complete. No. 1
76Notice board. No. 1
77Wall clock No. 1
78First aid boxNo. 1
79Sign. board of S/S with stand. No. 1
80Key board No. 1
81Table with drawer & sunmica Armed chair No. 1
82Armed chair No. 6
83Rack No. 2
84Bench No. 2
85Making fire fighting arrangements in the control room building as per Item Given below. Page No-
86Cost of Fire extinguisher 4.5 kg capacity complete with stand No. 4
87Cost of Fire bucket complete No. 6
88Cost of Fire bucket stand for 6 Nos. bucket made of M.S. Angle 45x45x6mm. No. 1
89Supply & Laying of Armoured control cable As per page No. Make Polycab/Gloster/Havells/Universal/KEI/Finolex/as per direction of Engineer E.I.
904x2.5 Sqmm
916x2.5 Sqmm
92Supply, Installation, Testing & Commissioning of 24V, 20A Trickle cum Boost Battery Charger suitable for 24V 70AH Battery Bank and also to feed 5A Power to External Load such as Emergency Light etc.70AH, 30V Battery Bank SMF batteries with Mounting Rack & along with connecting Leads and other associated accessories. The Charger shall be suitable to operate Emergency Light Load along with 33kV HT VCB Closing / Opening and also 11kV VCB Closing & Opening. As per page No.
93Construction of control cable trench of required size 0.30x0.45 Mtr. M-15 class brick work including plastering etc. and covered with R.C.C. slab (0.50x0.60M) size complete with all material, labour and T&P etc. required for proper completion of work. Detail analysis of Page No-
94Supply & Filling of 20mm stone grit in yard 100mm thick complete in all respects. As per page No.
95Supply & Laying of Al. conductor 33 KV (E) XLPE cross linked polyethylene) over all served cable with flat galvanised steel strip armouring at a depth of 1.0M below ground level over a cushion of 75mm thick sand bed alround and protect with bricks on sides and top surface 300x3x4 mm red stone the cable run shall be fixed on M.S clamp etc of suitable size and crossing the road cable shall run through 150mm dia hume pipe proper completion of work. Make Polycab/Gloster /Havells/Universal/KEI /Finolex/as per direction of Engineer E.I.
96(i) 300Sqmm 3 core
97Supply & jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 33KV 3Core Complete in all respects. Make:- Raychem/3M/Densons/as per direction of Engineer E.I.
98Out door 240-300 Sqmm As per DSR 2025 SI No. 23.8.3
99In door 240-300 Sqmm As per DSR 2025 SI No. 23.7.3
100Supply & Laying of following type high conductivity aluminum strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest amendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. Make Polycab/Gloster/Havells /Universal/KEI /Finolex/as per direction of Engineer E.I.
10170 Sqmm 3 core as per PWD SOR 2018 S.No. 506(d)
102300 Sqmm 3 Core as per page No.
103400 Sqmm 3 core as per page No.
104Supply & Jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 11KV 3Core Complete in all respects.Make:- Raychem/3M/Densons/as per direction of Engineer E.I.
105Indoor type 300-400 Sqmm As per DSR 2025 SI no. 23.4.4
106Indoor type 70 Sqmm As per DSR 2025 SI no. 23.4.1
107Outdoor type 300-400 Sqmm As per DSR 2025 SI no. 23.5.4
108Outdoor type 70 Sqmm As per DSR 2025 SI no. 23.5.1
109Supply and Erection of cable stand of size 3.00x0.50m above G.L. duly grouted with cement concrete upto 50 cm. depth for laying cables made of angle iron size (65x65x6mm) having welded M.S. flat of size 50x6mm on top middle, and 45mm above ground level for fixing cable by clamping with M.S. flat of 40x4mm size as per direction of E/I.
110Supply & Laying of Al. conductor PVC insulated armoured served. sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side and top. On surface the cable run shall be fixed on M.S clamps of suitable size and crossing the road cable should run through 150mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I wire climpped at several places also armouring of cable shall be properly connected with earth conductor/terminal the job include the cost of all material, labour and T & P required for proper completion of the work. Make Polycab/Gloster/Havells /Universal /KEI /Finolex/as per direction of Engineer E.I. As per PWD SOR 2018 S.No. 501 h) & (l)
11110sqmm 4 core
11250 Sqmm 3½core
113Supply and fixing of palm or pin copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects as per PWD SOR 2018, S.I. No. 504
11410 Sqmm
11525 Sqmm
11650 Sqmm
117Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of E/I.
11810 Sqmm 4 core As per PWD SOR 2018 SI no. 503 (h)
11950 Sqmm 3½ core As per PWD SOR 2018 SI no. 503 (L)
120Supply & fixing of 7mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thick) having 3mm thickness with Single arm bracket (1Mtr length) on RCC foundation including the cost of 4 way connector with bakelite sheet fixed in G I Pole ,foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. UP PWD SOR 2018 SI No-641 Make:- Vallmont/Bajaj/RRISPAT CONSOUL/as per direction of Engineer E.I.
121Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser/Reflector with 1.0 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 6 Amp SPMCB Complete driver set suitable for 30 to 40 watt. Confirming to IP 65 Protection Including Street light Bracket (60 cm long) with pole cap suitable for Street light Fittings complete in all respect as per direction of E/I.PWD SOR 2018 SI No-1420 CAT-AAA Make:- Philips/Havells/Polycab/Jaquar/as per direction of Engineer E.I.
122Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D)
123Supply and Burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 727 (D)
124Making suitable earth of GI pole with 2.5 Mts. long 20mm M.S rod connected with 7/16 SWG G.S. wire duly clamped & binded on pole including the cost of materials, labour and T & P required for proper completion of work as per direction of E/I.
125Supply and laying of 32mm x6 mm G.I strip from Earth Electrode directly in the ground as required complete in all respect as per PWD SOR-2018 item no. 717
126Supply and laying of 32mm x6 mm Copper strip Comlete As per PWD SOR 2018 SI. No. 720
127Supply & Fabrication of 8 SWG G.I. Wire mesh Security fencing by providing vertical supports of 50 x 50 x 6mm long including cutting bending at top at a distance of 0.60 Mtr. Including welding, cutting and Bending at bottom at a distance of 0.15 Mtr. Drilling of 04 Nos. Holes of 6mm Dia on Top for Holding the Barbed Wire at a distance of 125 mm hole to hole and 7 Hole in vertical position of 10mm Dia at a distance of 280mm hole to hole for riveting the chain link mesh of size 2\\" x 1\\" and MS Flat 50 x 6mm & 25x3mm and fixing the vertical support in plumb including brick work in repair wall with supply of all material, labour, T&P etc. required for proper completion of the work (Drawing Enclosed) as per MVVNL Specification
128Supply & Fixing of 1200 mm Sweep of Ceiling Fans with Fan Motor of A.C. Permanent insulation capacitor rating confirming BEE 5 Star rating and IS: 374/79 and also comply with IS:1709/1984 with Latest ammendment. The rated voltage 220/240 Volts, 50 Hz, I-ph AC the fan assemble should consists of down rod blades, shackle canopies etc. and double ball bearing system. complete in all respect ( Make Havells, Bajaj, Crompton)/as per direction of Engineer E.I.
129Supply & Fixng of 300 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect ( Make Havells, Bajaj, Crompton)/as per direction of Engineer E.I.
130Supply & Fixng of 450 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect ( Make Havells, Bajaj, Crompton)/as per direction of Engineer E.I.
131Supply & Fixing of 16 SWG M.S Drum with Livers duly painted including making hole in the wall for exhaust fan and finishing properly complete in all respect as per PWD SOR 2018 SI No. 1122 (A)
132Supply & Fixing of Shock Treatment Chart (Prescribed Under I.E. Rules) duly framed with glass and supported from back with hard board or soft board with supply of all material, labour, T&P for proper completion of work. Complete in all respect. as per PWD SOR 2018 SI No. 1134
133Supply & Fixing of Recess/ Surface/ Pendent Mounting Round 10 to 15 Watt L.E.D. Down lighter having powder coated Die cast Aluminium Housing with Heat Sink, Diffuser/ Reflector and Driver set complete in all respect as per PWD SOR 2018 S. No. 1402 Cat AAA
134Supply & Fixing of L.E.D. Tubelight with Batten suitable for up to 1x22 Watt L.E.D. Tubelight including Tube on surface complete in all respect as per PWD SOR 2018 S.No. 1413 Cat AAA
135Supply & Fixing of L.E.D. Street Light Fittings having Die cast Aluminium Body and diffuser/ Reflector with 1.0sqmm 3 core Multistrand copper unarmoured cable suitable length ,1 no. 6 Amp. SPMCB complete Driver Set suitable for 45 to 50 Watt confirming to IP 65 Protection including street light Bracket (60 cm long) with Pole cap suitable for street light fittings complete in all respect as per Direction of E/I. PWD SOR 2018 S.No. 1421
136Making & Fixing of Retro Radium Board frame with 50sqmm Hollow M.S. Pipe & ACP Sheet 3mm & Retro Radium base 3mm thick including all materials, Labour, T&P etc. and Fixing at Site Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56651325
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 4.80 Crore
LAST DATE 06-08-2026
Authority
Authority Name Uttar Pradesh Housing And Development Board
Work Description Tender for Construction Of 33/11 Kv Sub-Station (2X5 Mva) At Bhoomi Vikas Evam Grishthan Yojna, Bahraich.
Basic Detail
Tender No 699/M-6 ED-I/151 DT. 20.07.2026
Bidding Type Tender
Location
City Shravasti
State Uttar Pradesh
Key Dates
Publish Date 25 Jul 2026
Submission Date 06 Aug 2026
Open Date 06 Aug 2026
Finance
Tender Value 4.80 Crore
Tender Fee 7080
EMD 9.60 Lakhs
Exemption Not Available
Document List
8f6d5925-6825-4b30-8d45-0d2e2b49439e.html
bid.pdf
BOQ_2201287.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 25, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 06, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Aug 06, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
html

8f6d5925-6825-4b30-8d45-0d2e2b49439e.html

pdf

bid.pdf

xls

BOQ_2201287.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail