Tender For Renovation Of Station Earthing And Lightning Protection Along With Other Allied Works Of Distribution Wiring System At Kudghat Dps Under S&D Department.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
01 Aug 2026
5 days left
EMD
5000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
24 Paraganas South → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Renovation Of Station Earthing And Lightning Protection Along With Other Allied Works Of Distribution Wiring System At Kudghat Dps Under S&D Department.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying and fixing 240/415 V SP MCB of Breakingcapacity 10kA & C characteristics on din rail ofexisting DBs and necessary connection.6-32A |
| 2 | Supplying and fixing 63A ,415 V, TPN MCB of Breakingcapacity 10kA & C characteristics on din rail ofexisting DBs and necessary connection |
| 3 | Supply and fixing of phillips led tube light , mas led tube 1200 mm , 18W 865T8 I , 2100 lm. |
| 4 | Supplying & fixing of approved make Pedestal fan oscillating type of 450 mm sweep with base , blades , guards , speed regulator etc. A.C 230-250 volts .Make : Bajaj / Crompton / Havells / Usha or any reputed make. |
| 5 | Supplying and fixing double door Horizontal TPN MCBDistribution board with IP-42/43 protection, concealedin wall after cutting the wall & mending good thedamages to original finish incl. Inter connection withsuitable size of copper wire and neutral link & provisionfor earthing attachment.8 way |
| 6 | Supplying and Drawing 1.1 KV single core stranded 'FR'PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) of the following sizes in the prelaidpolythene pipe and by the prelaid GI fish wire and makingnecy. connection as required.4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC |
| 7 | Supplying & fixing of approved make 300 mm sweep , rpm 90 (12\\") exhaust fan heavy duty with mounting frames , blades , A.C 230-250 volts .Make : Bajaj / Crompton / Havells / Usha or any reputed make. |
| 8 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR'PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) in 19 mm bore, 3 mm thick polythenpipe (for horizontal & vertical run in wall and celingportion through prelaid polythen pipe) complete with allaccessories embedded in wall to light/fan/call bell points withPiano key type switch (Anchor make) fixed on sheet metal(16 SWG) switch board with bakelite/perspex (wall matchingcolour) top cover (3 mm thick) flushed in wall incl. mendinggood damages to original finish.2x22/0.3 (Ph. & N) and 1x22/0.3 as ECCAverage run 8 mtr |
| 9 | Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts.long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip(4 Mts. long), 20 mm dia x 125 mm long galvanized bolt,double nuts, double washers including finishing both ends bymaking holes etc. and S & F 80 mm dia GI pipe (ISI-Medium)protection (3 Mts. long) to be filled with bitumen partly underthe ground level and partly above ground level to an averagedepth of 3.65 Mts |
| 10 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm diax 80 mm long GI bolts, double nuts, double washers incl. S &F 15 mm dia GI pipe protection (1 Mts. long) to be filled withbitumen partly under the ground level and partly above groundlevel driven to an average depth of 3.65 Mts. below the groundlevel as below: By TATA-Medium GI pipe |
| 11 | Connecting the equipments body to earth busbar incl. S & F50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor withGI saddle as required and connection to equipments with incl.drilling holes, bolts, nuts,washers etc. |
| 12 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat65 mm x 8 mm on wall having clearance of 6 mm from wallincluding providing drilled holes on the busbar complete withGI bolts, nuts, washers, spacing insulators etc. as required |
| 13 | Excavation of soil for installation of Earth Electrode and filling& ramming. For soft soil |
| 14 | S & F Lightning conductor Air-terminals made of 15 mm dia 1500mm long GI pipe (ISI Medium) having five prongs of 4 SWG GI(Hot Dip) wire at top with 85 mm dia 6 mm thick GI base plate atbottom incl. necessary holes etc. duly grouted on the parapet etc.in CC mortar (4:2:1). |
| 15 | S & F of 4 SWG GI (Hot Dip) wire on wall for the lightningconductor as required (for vertical run) with GI Staples (40 mmlong) spaced not exceeding 1 Mtr. apart incl. mending good thedamages to building works (excluding hire charges of scaffolding). |
| 16 | Making soldered joints between conductors and down pipes/other metallic objects for 14 SWG GI (Hot Dip) wire includingsupply of necessary 4 SWG GI (Hot Dip) wire, jointing materialsand painting with 2 (two) coats of bituminous paint. |
| 17 | Supply & Fixing of Testing Joints by 20 mm x 3 mm thick GI (HotDip) strip 125 mm long grouted on wall having clearance of 6 mmfrom wall for making connection with thimbles at the end of 7/10SWG GI (Hot Dip) stranded Wire and 4 SWG GI (Hot Dip) wire ofvertical conductor and conductor from earth electrode completewith S & F thimbles, GI bolts, nuts, check-nuts, spring washersetc. as required. |
| 18 | Supply & Fixing 240 V, 6 A, 3 pin Modular type plugsocket (Brand approved by EIC) with 6A Modular typeswitch, without plug top on 4 Module GI Modular typeswitch board with 3 Module top cover plate flushed inwall incl. S&F switch board and cover plate and makingnecy. connections with PVC Cu wire and earth continuitywire etc. |
| 19 | Supply & fixing of 5 A, piano key type Switch of any reputed make. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 01, 2026
17:00 IST