| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable of Polycab / Finolex /Anchor / Salzer /RR Cables /Grandlays /APAR make to be laid in surface / recessed medium class PVC conduit (25 mm dia PVC Unbreakable conduits of Anchor /Finolex /Ravinder /Paraflex make including cutting of walls and refacing of walls to original position with cement concrete ,pop and painting of cutting portion inorder match to existing walls ), with 6 Amps modular switch, modular plate of Anti backteria series ( Anti bacteria series of ABB /L&T /Legrand /Simens make , ) , suitable GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(P+N+E is to be provided sperately for normal and invertor points ) .The job futher includes providing and fixing of Lighting Conceal deeps /Fan deeps Junction boxes of heavy guage sheet steel dully powder coated paint of standard make dully ISI Marked. |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor (Polycab Green/Havell Life guard/ Fenolex/ Salzer/RR/Apar make as desired by engineer incharge ) single core cable in surface / recessed medium class PVC conduit, 2way modular switch,Antibacterial series ( Legrand /ABB / Siemens make.) modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable of Polycab / Finolex /Anchor / Salzer /RR Cables /Grandlays /APAR/Havell make in surfacel recessed medium class PVC conduit (25 mm dia PVC Unbreakable conduits of Anchor /Finolex /Ravinder /Paraflex make including cutting of walls and refacing of walls to original position with cement concrete ,pop and painting of cutting portion inorder match to existing walls ) alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Complete job |
| 4 | Wiring for Circuits / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface l recessed medium class PVC conduit as required. of Polycab / Finolex /Anchor / Salzer /RR Cables /Grandlays /APAR make.(25 mm dia PVC Unbreakable conduits upto 6 sq.mm and 32/38 mm dia conduits above 6 sq.mm wires of Anchor /Finolex /Ravinder /Paraflex make including cutting of walls and refacing of walls to original position with cement concrete ,pop and painting of cutting portion inorder match to existing walls ) |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 2 X 16 sq. mm + 1 X 6 sq. mm earth wire |
| 9 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, Antibacterial series ( Legrand /ABB / Siemens make.)connections etc. as required. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,modular plate, suitable GI box , connections etc. as required. Modular Switch & Socket:- Antibacterial series ( Legrand /ABB / Siemens make.) |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- Antibacterial series ( Legrand /ABB / Siemens make.) |
| 14 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 15 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required.Antibacterial series ( Legrand /ABB / Siemens make.) |
| 16 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.Antibacterial series ( Legrand /ABB / Siemens make.) |
| 17 | Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, with cement plaster, wall putty , paint, complete |
| 18 | 25 mm |
| 19 | 40 mm |
| 20 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).(legrand / Schinider/ L&T ./ABB/equivalent standard make as directed by engineer incharge.) |
| 21 | 8 way (4 + 24), Double door |
| 22 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(legrand / Schinider/ L&T ./ABB/equivalent standard make as directed by engineer incharge.) |
| 23 | Single Pole |
| 24 | Single pole and neutral |
| 25 | Triple pole |
| 26 | Supplying and fixing 40 A to 63 A rating, 240/415 V, 10 kA, \\"C\\"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(legrand / Schinider/ L&T ./ABB/equivalent standard make as directed by engineer incharge.) |
| 27 | Single pole and neutral |
| 28 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 29 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 110 < 135 lm/Watt )Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc.as required with Minimum 5 year OEM warranty. System lumen efficacy ≥110and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim ), Philips/ Wipro/ Regent/Endo/LT make / sample to be approved before installation.. |
| 30 | 18 watt |
| 31 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy>135 lm/Watt) Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with inimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).), Philips/ Wipro/ Regent/Endo/LT make / sample to be approved before installation.. the job includes suitable bracket for its installation on the wall ( Complete job) |
| 32 | 70 watt |
| 33 | Supply installation testing and commissioning of Ceiling Fan 3 Star Rated with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. ), USHA/ Crompton /Orient make / Helonix /sample to be approved before installation.. |
| 34 | 1200 MM |
| 35 | Supply,Installation,Testing and Commissioning 486 Cu.m/Hr. AC 220-240 Volts, 50 Hz exhaust fan made out of Metal Body with inbuilt thermo cutoff Protection and Noise Level not exceeding 37 dB of Following Sizes including connection etc. complete as required .), USHA/ Crompton /ORIENT/Helonix make / sample to be approved before installation.. |
| 36 | 200-250 mm |
| 37 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker shouldbe below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).),Philips/ Wipro/ Regent/Endo/LT make / sample to be approved before installation.. |
| 38 | 40 watt |
| 39 | Design, Fabrication, Supplying, Installation, Testing and Commissioning of following panel, duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required.( As per approved design,size may vary as per site requirement) |
| 40 | Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required. |
| 41 | Normal INCOMING: |
| 42 | a)160A 4P MCCB 25 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make. |
| 43 | b) 4 No. of Aluminium Bus Bar of 300 Amp. |
| 44 | c)Digital meters and phase indicators -1 set. |
| 45 | d) onload Change over switch 100 Amp for generator.Front operated. |
| 46 | e) 4 No. of Aluminium Bus Bar of 200 Amp. |
| 47 | c)Digital meters and phase indicators -1 set. |
| 48 | INVERTER INCOMER: |
| 49 | a)100A DP MCCB 16 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make. |
| 50 | b) 2 No. of Aluminium Bus Bar of 200 Amp. |
| 51 | OUTGOING: |
| 52 | c) 40-63amp DP MCB |
| 53 | c) space for 12 way MCB's |
| 54 | Supply, Installation, Testing & Commissioning of 6 KVA single-Phase IN single-Phase out ON Line UPS System to provide backup time of 60 minutes at full load, With In-Built Isolation Transformer of reputed make dully ISI Marked (APC Schineider/ETON/VERTIV/ equivalent standard make ) (Compitable to Genrator Supply having varing frequency) With on line double conversion topology, high frequency techonology, with front LCD,automatic bypass for fault tolerance & complete with required Number, 12 Volts 65 AH SMF VRLA Batteries ( Exide/ Amaron/Quanta make) with connecting links with angle iron battery stand complete job, complete with battery rack with two year warranty against any manufacturing defect. The job further includes AMC for UPS and batteries for a period of three years with replacement warrenty reckoned from date of sucessfull commissioning. |
| 55 | Supply of advance maintenance free Chemical Gel Earthing of Dual Pipe Technology (GI) of 3 mtrs long 80 mm dia of outer shell (MS) with the 50 mm dia of inner shell (MS) of 80-100 microns galvanized CHEMRODE filled with highly conducting metallic compounds with the permenant sealings at both the ends with the lead terminal of 50x10mm size at the top. The electrode shall be duly tested and certified by CPRI (Central Power Research Institute), Govt of India for a peak short circuit withstanding capacity of 60 KA. including Supply/ fixing of environment friendly rust proof heavy duty weather proof polyplastic earth pit chamber. |
| 56 | Supplying and laying 25 mm x 5 mm G.I. strip at 0.50m. below ground level as strip earth electrode, including soldering etc. as required. |
| 57 | supply, laying underground, testing and commissioning of PVC alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size. |
| 58 | c)50 sq.mm 3.5 core Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysAug 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender