Tender For Construction Of Pankhudi (Mahila Hut) In Red Cross Building Patiala.(Electrical Work)
Tender Value
5.91 Lakhs
Estimated cost
Bid Submission
03 Aug 2026
3 days left
EMD
11900
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Patiala → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of Pankhudi (Mahila Hut) In Red Cross Building Patiala.(Electrical Work)
BOQ
| Sl. No. | Item Description |
| 1 | RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):-Wiring Computer terminal point having 3 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16 Amp. switch with indicator and 1No. blanking plate (Modular accessories). |
| 2 | RECESSED AIR CONDITIONER SUPPLY TERMINAL POINT (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Wiring air conditioner supply terminal point recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):-Wiring AC supply terminal point having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height. |
| 3 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES:Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½\\" deep for walls and CI 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):-Wiring fan point (Without fan box) |
| 4 | Wiring light point |
| 5 | Wiring 6Amp. wall socket point |
| 6 | Wiring 6Amp. Plug control comprising wall socket point |
| 7 | Wiring 16/20Amp. power plug control point |
| 8 | PVC INSULATED FR COPPER CONDUCTOR CABLES:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-Overall size 1 sq.mm (Un-sheathed) |
| 9 | Overall size 1.5sq.mm (Un-sheathed) |
| 10 | Overall size 2.5sq.mm (Un-sheathed) |
| 11 | Overall size 4sq.mm (Un-sheathed) |
| 12 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed) |
| 13 | Medium Gauge PVC Conduit Pipe 25mm dia. (On Surface) |
| 14 | SUPPLY AND ERECTION OF WIRING ACCESSORIES:Supply and erection of switches, sockets and other accessories (flush piano type/ modular accessories) in the existing bakelite/ modular cover frame including fixing & connections and petty material etc.:-16/20amp. One Way Modular Switch with Indicator (One Module) |
| 15 | 3 Pin Plug Top 25Amp. (ISI marked) |
| 16 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:-MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 17 | MCB Double Pole 50, 63amp. (10kA, Curve-C) |
| 18 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's:Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color- coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:-SP&N Double Door Distribution Board 12 way each |
| 19 | Fixing additional Length of earthing with 8 S.W.G. (4mm dia.) copper wire in G.I. pipe with sockets, elbows, steel hooks and GI saddle clamps including painting etc.:-Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (Flushed) |
| 20 | Supply and erection of Wall fan 400mm Swing 16 Inch high speed including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. |
| 21 | Supply, Installation Testing & Comissioning of Split Air conditioning units of 1.5 TR capacity, 3 Star Rating inclusive of Indoor & Outdoor unit, Outdoor stand and 3 meter Refrigerant Pipe & Copper Wire with 1 year warranty. complete in all respect upto the entire satisfaction of the Engineer-in-charge of work. |
| 22 | Supply, Installation & Comissioning of 4 KVA Stablizer complete in all respect upto the entire satisfaction of the Engineer-in-charge of work. |
| 23 | Supply and erection of Copper pipe & Copper PVC flexible wire flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. |
| 24 | Supply and erection of LED Street Light 45watt, Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED (with wattage 1 to 5 Watt) with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab. |
| 25 | Supply and erection of LED recessed downlighter 18watt LED (including constant LED driver) with High quality Presure die cast aluminium with efficacy of LED fixture minimum 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP 20 (as per BIS standards) , surge protection 2.5kv and above (as per (IS/IEC standards) wattage of each low powers LED less than 1 watt input AC frequency 50 Hz ± 3 % 5 year warranty including their drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter no AT-2021/GL 1410-1422 Dated 06/05/2021. Besides this the lighting fixture manufactures should have in house NABL accredited labortary. |
| 26 | Supply and erection of BEE 3-Star rating AC Ceiling Fan 1200mm (48\\") suitable for 230 V single phase with double ball bearing, copper wound, full aluminium body, 3Nos. of blades, white in colour. The mounting type is down rod mount. The product should possess a minimum air deleivery of 218 CMM. The rated speed of the the product must be minimum of 300 revolutions per minute and 5Nos. of speeds. The product should have a manufcaturer's guarantee /warranty of minimum 2 years. The product should be complete in all aspects with fan motor, bladeset, down rod, conopy set, shackle kit, twisted wire etc., including erection & testing of ceiling fan having connection with PVC insulated PVC sheathed two single core copper conductor (FR) cable 0.75 sq. mm complete in all respects as per satisfcation of the Engineer in-charge at site. |
| 27 | Supply and erection of Plastic Body 250MM, 10\\" Ventilation Fan including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. |
| 28 | Supply, Installation & Testing of Chemical Earthing (Maintenance Free Earthing) System with UL Approved Copper Bonded Rod and exothermically welded Cu Busbar both tested by CPRI at 50kA Fault Current. A Copper bonded steel rod shall have 3000 mm length and 17.2 mm dia. with copper bonding thickness of minimum 250 microns. Along with Earth enhancement compound tested by ROHS complying IEC 62561-7 in a sealed bag of minimum 50 kg (25 kg Bag x 2). A Copper clad steel solid ground wire of 8 mm dia. For interconnecting earth pits including earth pit covers is required.Each earth pit shall be covered with heavy duty weather proof environment friendly polyplastic earth pit chamber.The grounding minerals should not be pollute the ground water.The grounding minerals shall be tested & certified for the resistivity of less than 0.12ohm mtr. |
| 29 | Supply, Erection, Testing & Successful Commissioning of 4 MP IP Camera Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 30 | Supply, Erection, Testing & Successful Commissioning of NVR 8 Channel Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 31 | Supply, Erection, Testing & Successful Commissioning of POE Switch 8 Channel Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 32 | Supply, Erection, Testing & Successful Commissioning of 4 TB Hard Drive Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 33 | COPPER CONDUCTOR CABLES FOR SPECIAL ELECTRICAL SERVICES:Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in- charge:-CAT 6 LAN cable |
| 34 | Supply, Erection, Testing & Successful Commissioning of 2U Rack Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 35 | Supply, Erection, Testing & Successful Commissioning of RJ45 Connector Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 36 | Supply, Erection, Testing & Successful Commissioning of 4 Port Extension Board Complete in all respect as approved and desired by the Engineer in-charges at site. |
| 37 | Supply& erection of 27 inches Screen Full HD 1920 x 1080, IPS Technology, Tilt adjustability,5ms response time, Aspect Ratio 16:9, Viewing angle 178 degree x 178 degree, Panel Mount, HDCP Supported, Glass Hardness 3H, Refresh rate 100 Hz, Color supported 16.7 Million colors, Contrast Ratio 1,000:1, Brightness 250cd/m2, Pixel Per Inch- 81 PPI with 01 No. HDMI Port, 01 No VGA Port, Input Voltage 100Vac to 240V ac, Maximum Power Consumption 28Watt with 01 No. Power cable, 01 HDMI cable 1.80 meter, Energy star 8.0, compatible with all type of computers and laptop with 2 year warranty. Make Dell |
| 38 | Supply and erection of sine wave inverter 1000-1100 VA with Tubular Battery180-200AH with Trolley stand complete in all respects as approved and desired by the Engineer in-charge at site. |
| 39 | Supply and Erection of LED strip Light with profile strip Lights for Ceiling, Balcony, Home Decor, Interior Decoration. complete in all respects as approved and desired by engineer in charge at site. |
| 40 | Supply, Installation, testing & Commissioing of Grid interactive PV System Solar Power Plant (i.e connected to utility grid) of Minimum4KWp including required quantities of SPV modules (High power density Monocrystalline/ Top conn (efficiency 20 to 23%) based single module of capacity+400W) formed into arrays, their mounting arrangement, Power conditioning units (i.e String Solar Inverter), required DC & AC distribution panels with surge protection units, cabling from terrace to main distribution board through Cable tray, Bi Directional Energy Meter, Chemical copper bonded rods (i.e. 1 Nos. GI Structure, 2Nos. for String Inverter, AC & DC Distribution System)Provsion of Lighting arrester and 2 Nos. G.I. chemical earthing with copper bonded rods. Hot Dip Galvanized MS Mounting Structure be Designed to with stand the Speed for the Wind Zone of the Location(Rated Wind Speed 150-170Kph) Complete with transportaion, fabrication, labour & Civil Work.Features:- 1. Solar PV Module Warranty 25 Years aproved in ALMM-I & ALMM-II as per MNRE, GOI latest specifications / Standards.2. Power Conditioning Unit (String Solar Inverter) & Certified under IEC/EN 62109-1,IEC / EN 62102-2 , EN 61000-6-2, EN61000-6-3, IEC61683, EN 50530 , IEC 60068-2-1,2,14,30,EN 60529, IES 60947 Part 1,2,3 IS 60947 Part 1&2 , IES 60227/IS 694,IES 60502/IS 1554 BIS Certificates & MNRE, GOI latest specifications / Standards.3. Structure : 25 Years Service Life with AMC & Certified under IS 2062:20114. Complete Plant Insurance for the period of 5 Years (Excluding Theft of the material) 5. Annual Maintenance Contarct for the period of 5 Years Conditions:- 1. The Plant will be installed as per MNRE and GOI guidelines specifications.(Detail of Material as per Annxeure -1 Attached) 2. The Work will got done from approved MNRE (Ministry of New and Renewable Energy)/ PEDA (Punjab Energy Development Agency) Contractors.PWD enlisted contractor subject to condition that PWD Enlisted contractor will get work done from MNRE (Ministry of New and Renewable Energy)/ PEDA (Punjab Energy Development Agency) approved Conractors.The Rates are inclusive of Bi-directional meter testing charges, PSPCL Connection Charges, Unidirectional meter cost and all type of taxes including GST Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysAug 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender