Tender For Certain Essential Repairs To Central Ac Plants Of Cap 3X60 Tr At Hq Cicg Tg, 3 X 30 Tr At Nbc Lab, 3 X 11 Tr At Logistic Section, 2X25 Tr At Ard 3 Eth, 2X24 Tr At Erg 3 Eth, 2X7.5 Tr At Recoil Section In 505 Abw Under Ge (U) P&M Delhi Cant
Tender Overview
Project Description
Tender for Certain Essential Repairs To Central Ac Plants Of Cap 3X60 Tr At Hq Cicg Tg, 3 X 30 Tr At Nbc Lab, 3 X 11 Tr At Logistic Section, 2X25 Tr At Ard 3 Eth, 2X24 Tr At Erg 3 Eth, 2X7.5 Tr At Recoil Section In 505 Abw Under Ge (U) P&M Delhi Cantt-10
BOQ
| Sl. No. | Item Description |
| 1 | M&L for de-scaling condensers of central AC Plant of capacity 3x60 TR at HQ CICG TG, by opening side plate, flushing the condenser tubes, using de-scaling solution of suitable gravity, rodding the condenser tubes carefully removing all the deposited materials completely and raising the solution through condenser tubes till clear water starts to come out from the condenser as complete including re-fixing the side plates by replacing gasket and testing complete for satisfactory working complete all as specified and directed |
| 2 | ditto- all as per item no 1.00 above but Capacity of AC Plant 3 x 30 TR at NBC Lab, 505 ABW. |
| 3 | ditto- all as per item no 1.00 above but Capacity of AC Plant 2 x 25 TR at ARD 3 ETH, 505 ABW. |
| 4 | ditto- all as per item no 1.00 above but Capacity of AC Plant 2 x 24 TR at ERG 3 ETH, 505 ABW. |
| 5 | M&L for servicing condensers of Package type AC Plant of capacity 3 x 11 TR( 2 Nos condensers per unit) at Logistic section, 505 ABW by scraping/ removing the deposit materials from condenser coil using vamuklin 2RA, clean solution and cleaning condenser coil by pressurized water using pump through blower, detection of leakage, repair of damaged condensing coil tubes with necessary welding/ brazing and lubricating the all bearings, checking motor foundation, nuts, bolts, washers, etc. and replacing the same if required and testing complete for satisfactory working complete all as specified and directed |
| 6 | ditto- all as per item no 5 above but Capacity of AC Plant 2x7.5 TR at 505 ABW. |
| 7 | Servicing and repairing of electrical operated hot water generator of Capacity 75 KW complete with automatic and safety controls such as safety valve, purge valve, high limit cut out, automatic and manual reset, low level cut out stop controller, thermostat, heaters including replacement of defective/ unserviceable parts complete all as per specified and directed |
| 8 | Servicing and repairing of electrical operated hot water generator of Capacity 30 KW complete with automatic and safety controls such as safety valve, purge valve, high limit cut out, automatic and manual reset, low level cut out stop controller, thermostat, heaters including replacement of defective/ unserviceable parts complete all as per specified and directed |
| 9 | Disconnecting from mains/taking out existing unserviceable/defective Monoblock Pump set of capacity 3/5 HP and repair/ replacement of bushings, worn out nuts, bolts washers, gaskets, gland and with super enamelled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, etc and positioning the pump set and connecting up in existing position and testing complete all as specified and as directed |
| 10 | Disconnecting from mains/taking out existing unserviceable/defective Monoblock Pump set of capacity 7.5/10 HP and repair/ replacement of bushings, worn out nuts, bolts washers, gaskets, gland, seal and bearings positioning the pump set and connecting up in existing position and testing complete all as specified and as directed |
| 11 | Opening the electric induction motor of capacity 40 HP and taking out the unserviceable winding wire complete and cleaning the slots, rewinding the motor with super enamelled copper winding wire of gauge same as existing gauge including all other insulating material, (i.e. cotton tap, PVC tap, PVC sleeve glass pipe, varnish) complete all as specified and as directed. |
| 12 | Disconnecting from mains/taking out existing unserviceable/defective Cooling tower motor of capacity 20 HP of any size, type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enamelled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installation, testing and commissioning complete all as specified and as directed |
| 13 | Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 10/7.5 HP of any size, type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enamelled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installation, testing and commissioning complete all as specified and as directed |
| 14 | Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 3/5 HP of any size, type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enamelled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installation, testing and commissioning complete all as specified and as directed |
| 15 | Material and Labour for frame work with angle iron for frame support, with fabrication, welding joining including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 including taking down old unserviceable one complete all as specified and as directed |
| 16 | Material and labour for leakage detection of chiller and condenser pipe lines by charging dry Nitrogen Gas and with standing pressure for 24 hours, rectification of leakages, evacuation of the system as per manufacturer’s instruction complete all as specified and directed for capacity of 3x60 TR at CICG.Note :- The rates quoted by the contractor shall deemed to include the cost of Nitrogen gas, charges for T&P and empty cylinders. |
| 17 | ditto- all as per item no 16.00 above but Capacity of AC Plant 3 x 30 TR at NBC Lab, 505 ABW. |
| 18 | ditto- all as per item no 16.00 above but Capacity of AC Plant 2 x 25 TR at ARD 3 ETH, 505 ABW. |
| 19 | ditto- all as per item no 16.00 above but Capacity of AC Plant 2 x 24 TR at ERG 3 ETH, 505 ABW. |
| 20 | ditto- all as per item no 16.00 above but Capacity of AC Plant 3 x 11 TR at Logistic Section, 505 ABW. |
| 21 | ditto- all as per item no 16.00 above but Capacity of AC Plant 2 x 7.5 TR at Recoil Section, 505 ABW. |
| 22 | Supply only in replacement rubber insulating mat class A type, chequered, size 2 Mtr x 1 mtr x 25 mm thickness, for working voltage 3.3 KV complete all as specified and as directed. Make : Jyoti /Dunlop or Equivalent |
| 23 | Supply and fixing in repair Drier Cores filter for chiller unit of package type AC plant of Cap. 2X 7.5 TR (Make:- Denfoss/Indfoss) |
| 24 | Supply and fixing in repair Drier Cores filter for chiller unit of central AC plant of Cap 15 to 30 TR (Make:- Denfoss/Indfoss) |
| 25 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 630 Amps, adjustable type, 3 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed (Make- L&T or equivalent in ABB/Legrand/Havells) |
| 26 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 400 Amps, adjustable type, 4 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed (Make:- L&T or equivalent in ABB/Legrand) |
| 27 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 250 Amps, adjustable type, 4 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed (Make:- L&T or equivalent in ABB/Legrand) |
| 28 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 160 Amps, adjustable type, 4 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 29 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 100 Amps, adjustable type, 4 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 30 | Supply and fixing in replacement moulded case circuit breakers(MCCB) 63 Amps, adjustable type, 4 Pole, 25kA, compete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 31 | Supply and fixing in replacement miniature circuit breaker (MCB) 63 Amps, TPN , 10 KA 'C' curve complete all as specified and directed. (Make:- L&T or equivalent in ABB/Legrand) |
| 32 | Supply and fixing in replacement miniature circuit breaker (MCB) 32 Amps, TPN , 10 KA 'C' curve complete all as specified and directed (Make:- L&T or equivalent in ABB/Legrand) |
| 33 | Supply and fixing in replacement miniature circuit breaker (MCB) 25 Amps, TP , 10 KA 'C' curve complete all as specified and directed. (Make:- L&T or equivalent in ABB/Legrand) |
| 34 | Supply and fixing in replacement 'C' curve miniature circuit breaker (MCB) 6-32 Amps, single pole (SP), 10 KA complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 35 | Supply and fixing in repair overload relay 3.5-5 amps, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 36 | Supply and fixing in repair overload relay 6.7-9.7 amps, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 37 | Supply and fixing in repair overload relay 17-25.5 amps, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 38 | Supply and fixing in repair overload relay 40-57 amps, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 39 | Supply and fixing in replacement power contactor, 9 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 40 | Supply and fixing in replacement power contactor, 12 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed . (Make:- L&T or equivalent in ABB/Legrand) |
| 41 | Supply and fixing in replacement power contactor, 18 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed. (Make:- L&T or equivalent in ABB/Legrand) |
| 42 | Supply and fixing in replacement power contactor, 25 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed. (Make- L&T or equivalent in ABB/Legrand) |
| 43 | Supply and fixing in replacement power contactor, 32 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed . (Make- L&T or equivalent in ABB/Legrand) |
| 44 | Supply and fixing in replacement power contactor, 40 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed. (Make:- L&T or equivalent in ABB/Legrand) |
| 45 | Supply and fixing in replacement power contactor, 50 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed. (Make:- L&T or equivalent in ABB/Legrand) |
| 46 | Supply and fixing in repair solid state single phasing preventer type VSP2 complete all as specified and directed (Make:- Minilec/ L&T/ Siemens/Legrand/ ABB/ C & S) |
| 47 | Supply and fixing in replacement Star Delta starters for motors of 20 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and directed. (Make -L&T/Siemens/Legrand/ ABB/Crompton) |
| 48 | Supply and fixing in replacement Star Delta starters for motors of 12.5/10 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and directed (Make -L&T/Siemens/Legrand/ ABB/Crompton) |
| 49 | Supply and fixing in replacement DOL starters for motors of 5/7.5 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and directed (Make -L&T/Siemens/Legrand/ ABB/Crompton) |
| 50 | Supply and fixing in replacement DOL starters for motors of 3/2.5 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and directed. (Make -L&T/Siemens/Legrand/ ABB/Crompton) |
| 51 | Supply and fixing in replacement Digital type Ammeter Flush mounted 3 phase, with suitable rating current transformers suitable for measuring range minimum (0-60) Amps with selector switch suitable for mounting on LT panel, compete all as specified and directed . (Make:L&T,ABB,LEGRAND) |
| 52 | S&F in replacement Digital type Voltmeter Flush mounted 3 phase, with suitable rating current transformers suitable for measuring range minimum (0-600) Volts with selector switch suitable for mounting on LT panel, compete all as specified and directed (Make:- L&T or equivalent in ABB/Legrand) |
| 53 | Supply and fixing in repair/replacement star/delta timer range 3-30/120 seconds, suitable for LT panels complete all as specified and directed (Make- L&T or equivalent in ABB/Legrand) |
| 54 | Supply and fixing Phase indication lights of suitable colour, 240V AC suitable for mounting on LT panel, complete all as specified and directed . (Make ESBEE) |
| 55 | Supply and fixing on/off/trip indication lights of suitable colour, 240V AC, suitable for mounting on LT panel compete all as specified and directed . Make ESBEE |
| 56 | Supply and fixing on/off push buttons suitable for mounting on LT panels, complete all as specified and directed . 'C' curve |
| 57 | Supply and fixing in repair humidity self priming motor pump set of cap 0.5 HP single phase 240 volt complete all as specified and directed (Make:- Usha/ M/s Seetal /HP/Amcrate ) |
| 58 | Material and labour for dismantling the old broken existing PVC tank and Supply and fixing in replacement 200 Litre capacity Rotational moulded polyethylene water storage tank, triple layered, food grain plastic (rectangular shape with closed top), hoisted and fixed in position on existing wall, stage, roof or RCC staging complete all as specified in SSR Part-I including supply and connecting tank nipple, float valve etc., making complete connection of inlet and out let pipe, fixing of GI pipe (over flow) & washout to the nearest rain water drain complete all as specified and as directed. (Make:-Sintex/ Sheetal/ Rotex). |
| 59 | Material and labour for Overhauling and repairing of any size refrigerant suction/ delivery liquid line valve including servicing of valve, replacement of packing material, sealing rings, Teflon washers and testing complete all as specified and as directed |
| 60 | Supply and fixing in repairs thermostat for AHU room, as per existing size & specification complete all as specified and as directed. (Make:-SIEMENS/ DANFOSS/ INDFOSS/ANERGY). |
| 61 | Supply and topping up of refrigerant Gas R - 22/407/134A complete all as specified and as directed. (Make:- Mefron or equivalent ISI approved as directed) |
| 62 | Supply and fixing in repairs of Pre filter 10 micron of size 600mm x 600x 50mm made of out of GI wire mesh interspaced with two crimp layers and three flat layers flanged deep box type and efficiency 90% as per existing size and pattern for the all three AC Plant air handling unit complete all as specified and directed. (complete all as specified and as directed.) |
| 63 | ditto all as per item No. 62 above but size 600mm x 300mm x 50mm. |
| 64 | ditto- all as per item No 62 above but size 300mm x 300mm x 50mm. Please Enable Macros to View BoQ information |
| 65 | ditto- all as per item No 62 above but size 300mm x 300mm x 50mm. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender