Tender For Supply Installation Testing and Commissioning of Lt Cubical Panel Of Damodar Sub-Station At Jnu.
Tender Value
17.87 Lakhs
Estimated cost
Bid Submission
17 Aug 2026
18 days left
EMD
35745
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply Installation Testing and Commissioning of Lt Cubical Panel Of Damodar Sub-Station At Jnu.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing and commissioning of floor mounted indoor type cubical LT Panel suitable for operation on 415 ± 10 % Volt, 50 Hz AC, 3-ø, 4-wire Supply System made of 2 mm thick CRCA Sheet enclosures fully compartmentlized double door type both side openable treated with 7-tank chemical pre-treatment process dust & virmin proof, neoprene type gaskets on the doors to ensure IP-54/55 protection complete with Aluminium bus bar for phase, neutral & earthing, sleeves, SMC/DMC insulators, Base frame, lifting lugs, Sign writting, Gland plate for entry of cable for Top/Bottom including the following Switchgears mounted theron complete with connection, interconnection, control wiring etc. as required.-(The main panel should comply with CPWD specification & relevant IS Code and detailed scope of work enclosed as annexure-'A')1) Main Incomer-:a)- 1250A, 4-Pole, 65kA Microprocessor-based Release providing comprehensive LSIG(Overload, Short-circuit, Instantaneous, and Earth Fault) protection ACB EDO Type with NO-NC Contacts, shunt trip coil, closing coil and spring chanrging motor etc. all system accessories - 01 Set2) Metering:-a)- Digital Flush Type Class - 1 Accuracy 3-Phase MF METER - 01 No.b)-Current Transformers Of 1600/1 A Ratio, 5 VA Class 1 Metering. - 03 Nos. c)-Three Phase R,Y,B Indicating Lamps Along With 6A SP Mcb Backup Protection - 01 setd)-ON/OFF/Trip indication Lamps Along With 6A Sp Mcb Backup Protection- 01 set3)1600A, 4-Pole, High-conductivity Electrolytic Grade Aluminium Busbars - 01 Lot4) Outgoing:-a)-630A, 4-Pole, 50kA Thermal-Magnetic Release MCCB with LED-type Indication Lamps (ON/OFF/TRIP) ,3-Phase Digital Ammeter a set of 3 Nos. Current Transformers (630/5A Ratio, Class 1.0 accuracy, 5VA Burden). Extended Rotary Operating Handle (ROM), Aux. coil Shunt Trip Coil, Phase Barriers, and Terminal Spreaders etc. all system accessories - 02 Set.b)-400A, 4-Pole, 50kA Thermal-Magnetic Release MCCB with LED-type Indication Lamps (ON/OFF/TRIP) ,3-Phase Digital Ammeter a set of 3 Nos. Current Transformers (400/5A Ratio, Class 1.0 accuracy, 5VA Burden). Extended Rotary Operating Handle (ROM), Aux. coil Shunt Trip Coil, Phase Barriers, and Terminal Spreaders etc. all system accessories - 06 Set.c)-250A, 4-Pole, 50kA Thermal-Magnetic Release MCCB with LED-type Indication Lamps (ON/OFF/TRIP) ,3-Phase Digital Ammeter a set of 3 Nos. Current Transformers (250/5A Ratio, Class 1.0 accuracy, 5VA Burden). Extended Rotary Operating Handle (ROM), Aux. coil Shunt Trip Coil, Phase Barriers, and Terminal Spreaders etc. all system accessories - 02 Set.Location- Damodar Sub station |
| 2 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required |
| 3 | Supplying & laying 25 mm x 5 mm GI strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required (jointing shall be done by overlapping and with 2 seats of G.I. nut bolt & spring washer spaced at 50mm) |
| 4 | Providing & fixing 25mm x 5mm G.I.strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut , bolt,spring, washer excavation and re-filling etc. as required. |
| 5 | Dismantling of existing electrical cubical panel i/c Switch fuse units, old cables connection, glands, earhing etc. as required & Buy back the old LT Panel i/c old LT Breaker, switch fuse unit, Doors,covers, Gland Plate & base frame angle etc. as required. |
| 6 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 7 | 3½ X 25 sq. mm |
| 8 | 3½ X 70 sq. mm |
| 9 | 3½ X 95 sq. mm |
| 10 | 3½ X 120 sq. mm |
| 11 | 3½ X 150 sq. mm |
| 12 | 3½ X 185 sq. mm |
| 13 | 3½ X 240 sq. mm |
| 14 | 3½ X 300 sq. mm |
| 15 | Supply, Installation, Testing & Commissioning of wall mounted ON-Load 415 Volt 630A 4P Manual Changeover in SS enclosure box & end terminal box on both side i/c Terminal Shrouds, source separator, Phase Barrier and Operating handle etc. as required. |
| 16 | Supply, Laying , Testing & Commissioning of 1100 V rated aluminium conductor steel wire/ strip armored XLPE power cable of following sizes as per IS-7098 part-I in the existing masonary open duct as required. |
| 17 | 3½ x 300 sq. mm Armoured Alluminium cable |
| 18 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/ sub main wiring/cable as required. |
| 19 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 20 | 3½ X 300 sq. mm |
| 21 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 22 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 23 | 120 mm dia (OD-120 mm & ID-103 mm nominal) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 17, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysAug 19, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender