Bids Are invited for Replacement Of Transformers Ht Panel Apfc Panel And Other Associated Works At Shimla Airport
Tender Overview
Project Description
Bids Are invited for Replacement Of Transformers Ht Panel Apfc Panel And Other Associated Works At Shimla Airport Sitc Of 315 Kva, 11Kv, 433V, 3 Phase Onan Oil Transformer - Supply, Installation, Testing & Commissioning Of Indoor Type 315 Kva,11Kv/433 Volts, 3 Phase , 50 Hz, Step Down , Delta / Star Connected (Dyn 11), Neutral Earthed, Copper Wound ,Core Type, Double Wound, Oil Immersed, Onan Cooled Transformer Having Level 2 Energy Efficiency With Octc (+) 10% To (-)10% In Step Of 2.5% Of Variation Of Hv, With Automatic Remote Tape Changer Panel Including Oil Conservator, Explosion Vent, 150 Mm Dial Type Themometer For Indicating Winding & Oil Temparature Fitted In A Marshalling Box, Silica-Gel Breather ,Buchholz Relay Complete With Weather Proof Cable End Termination Box On Ht Side Suitable For Termination Of Armoured Cable Of Size Upto 3 Core 300 Sq.Mm On Ht Side, End Termination Box On Lt Side Terminations Of Armoured Cables, Standard Fitting And Accessories , Including First Fill Of Filtered Dehydrated Oil Etc. Complete As Per Is 1180, Level-2 As Per Specification Enclosed.Job Includes, Dismantling 02 Nos. Of Existing 250Kva Transformers Including All Necessary Connection And Moving Them Within A Distance Of 100M Safely And Handing Them Over To Aai Dismantle Store As Per Directions Of Eic.
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | SITC of 315 kVA, 11kV, 433V, 3 phase ONAN Oil Transformer | Supply, installation, Testing & Commissioning of Indoor type 315 KVA,11KV/433 volts, 3 phase , 50 Hz, step down , Delta / Star connected (DYN 11), neutral earthed, copper wound ,core type, double wound, oil immersed, ONAN cooled transformer having Level 2 Energy Efficiency with OCTC (+) 10% to (-)10% in step of 2.5% of variation of HV, with automatic Remote tape changer panel including oil conservator, explosion vent, 150 mm dial type themometer for indicating winding & oil temparature fitted in a marshalling box, silica-gel breather ,Buchholz relay complete with weather proof cable end termination box on HT side suitable for termination of armoured cable of size upto 3 core 300 sq.mm on HT side, end termination box on LT side terminations of armoured cables, standard fitting and accessories , including first fill of filtered dehydrated oil etc. complete as per IS 1180, Level-2 as per specification enclosed.Job Includes, Dismantling 02 nos. of existing 250kVA transformers including all necessary connection and moving them within a distance of 100m safely and handing them over to AAI dismantle store as per directions of EIC. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender