Tender For Design, Supply, Construction, Installation, Testing And Commissioning Of Ehv 110Kv Xlpe Insulated Power Cables And Construction Of Ehv Bay With Abt Metering Arrangement And Scada At Msetcls Vasai Receiving Stations On Boq Basis For Vasai T
Tender Overview
Project Description
Tender for Design, Supply, Construction, Installation, Testing And Commissioning Of Ehv 110Kv Xlpe Insulated Power Cables And Construction Of Ehv Bay With Abt Metering Arrangement And Scada At Msetcls Vasai Receiving Stations On Boq Basis For Vasai Tss In Borivali-Virar Section Of Western Railway In Mumbai Under Mutp-3A.
BOQ
| Sl. No. | Item Description |
| 1 | Cable work for EHV incoming Power supply arrangement to Proposed Vasai Railway Traction Substation |
| 2 | Modification of incoming EHV Power supply arrangement at Vasai MSETCL Receiving Stations |
| 3 | Construction of Gantry & Equipment Foundation at Vasai MSETCL Receiving Stations |
| 4 | SHE Provision for Vasai TSS |
| 5 | 2.0 Cable work for EHV incoming Power supply arrangement to Proposed Vasai Railway Traction Substation |
| 6 | Detailed surveying of the Cable route along the alignment fixed by the owner & preparation of profile drawing for cable laying and preparation of final cable route in 6 sets of hard & soft copy in a scale of 1:10 indicating the position of cable jointing chambers, earthing details, position of cable route marker, land marks etc., after completing the work & energizing for the use of permanent record, GPS mapping of utilities to be indicated in the drawing complete. |
| 7 | Supplying, multiple loading/ unloading, storing, laying and commissioning of 110 kV 1C x 630 Sq.mm. Cu XLPE, lead Theroplastic sheath cables suitable for 110 kV rated voltage (RMS), 123 kV maximum voltage (RMS) and generally confirming to IEC 60502 2 latest |
| 8 | Supply |
| 9 | Laying & commissioning. |
| 10 | Excavation of Cable trenches as per approved drawings with proper wooden shoring, de watering arrangement & with sufficient clearances from all sites. |
| 11 | Excavation in all types of soil except hard murum, earth rock/debries, backfilled earth |
| 12 | Excavation in all types of soil hard murum, earth rock, debris, backfilled earth, |
| 13 | Supplying, multiple loading/ unloading, storing, laying of HDPE pipes for EHV cable (OD 200 mm & 5 Mtr length) |
| 14 | Supplying, multiple loading/ unloading, storing and laying of 660x500x60 mm cable tiles considering 10 tiles per meter |
| 15 | Supply |
| 16 | Laying in trench |
| 17 | Supplying, multiple loading/ unloading, storing and making joint of Sealing End for GIS termination with 110 kV 1C x 630 Sq.mm. Cu XLPE Cable generally confirming to IEC 61171 209 latest |
| 18 | Supply |
| 19 | Making joint, testing and commissioning (Erection) |
| 20 | Supplying, multiple loading/ unloading, storing and making joint of Sealing End for O/D termination / straight joint/ cross bonding with 110 kV 1C x 630 Sq.mm. Cu XLPE cable generally confirming to IEC 61171 209 latest |
| 21 | Supply of Sealing End for O/D termination |
| 22 | Supply of cross bonded straight joints |
| 23 | Making joint/ cross bonding, testing and commissioning (Erection) |
| 24 | Supplying of all material, multiple loading/ unloading, storing for construction of cable jointing chamber (RCC types) along with Below ground Earth mat for Joint bay of suitable dimensions as mutually agreed for 1 circuits consisting of 5 nos. of cable with link boxes, earthing as per site requirement and specifications. Including supply & filling submerged (Including supply and filling of STB) [10.0 Mtr] |
| 25 | Supplying, multiple loading/ unloading, storing, testing and commissioning of link boxes, Coaxial Cables, Sheath cables, Lugs, Connectors etc. for bonding and earthing |
| 26 | Three Phase link box with SVL for cross bonding |
| 27 | Three Phase link box without SVL |
| 28 | Single Phase link box with SVL for sheath bonding |
| 29 | Single Phase link box without SVL |
| 30 | Coaxial Cable along with Lugs and Connectors for bonding at joint location |
| 31 | Supply of Sheath bonding cable for sheath bonding |
| 32 | Installation of Link Box in Termination/joints including earthing (Erection) |
| 33 | Supplying, multiple loading/ unloading, storing, laying and commissioning of Fibre optic cable along with patch cord |
| 34 | Supply of Fibre optic cable (Quantity considered 2 no. 96 Core FO cable per circuit) |
| 35 | Supply of Patch Cord for 96C Optic Fiber cable (Each station 50 nos.) |
| 36 | Services for 40 mm Dia duct for 96F optical fibre cable complete |
| 37 | Laying and commissioning of optical fibre cable 96 Fibre of specified type along the cable trench through HDPE pipe (Erection) |
| 38 | Services for OFC splicing & termination (Erection) |
| 39 | Line interfacing unit with patch cord |
| 40 | Supplying, multiple loading/unloading, storing, laying of 40 mm. dia. HDPE pipes for 96C FO cable |
| 41 | Supply of HDPE pipes |
| 42 | Insertion of 96C FO cable in HDPE pipe and laying in trench/open rout (Erection) |
| 43 | Supplying, multiple loading/ unloading, storing, laying of Fiber termination Rack (One rack at both ends) complete |
| 44 | Supply |
| 45 | Installation and commissioning (Erection) |
| 46 | Supplying, multiple loading/ unloading, storing, laying of 96C FOP joint boxes for Fiber Optic cable (2 Nos. at both ends and no. per KM per cable) complete |
| 47 | Supply |
| 48 | Installation and commissioning (Erection) |
| 49 | Supplying, multiple loading/ unloading, storing, laying of FO termination kit required for each station/end complete |
| 50 | Supply |
| 51 | Installation and commissioning (Erection) |
| 52 | Construction of FO cable hand hole (FO hand hole per km and one in each substation) (Erection) |
| 53 | Supplying, multiple loading/ unloading, storing, transporting to site, fabrication of Galvanised Steel structure for cable Cleating arrangement, mounting structure for outdoor termination, cable cleats, connectors etc. complete |
| 54 | Supply of Galvanised Steel structure |
| 55 | Supply Cable Cleats |
| 56 | Fabrication of Structural Steel for cable cleating arrangement |
| 57 | Supply of Mounting structure for outdoor cable termination |
| 58 | Supply Terminal connector for Outdoor termination |
| 59 | Fabrication, installation, testing and commissioning of outdoor cable termination (Erection) |
| 60 | Installation of Mounting structure for outdoor cable termination (Erection) |
| 61 | Trial Pits (Erection) |
| 62 | Testing & Commissioning (Per Circuit) (Erection) |
| 63 | Supply of Desktop Computer and printer (MRVC approval for specification) |
| 64 | Providing vehicles (Innova/Ertiga/Scorpio) for 18 Month |
| 65 | Supply of all material, multiple loading/ unloading, storing, installation, fixing, testing & commissioning of 2.0-ton capacity Minimum Energy Efficiency Ratio 4.5 inverter technology split air Conditioner of approved make with Copper Coiling, including connecting Copper piping with thermal insulation & insulated drain piping, core cutting & 2.5sq.mm x 3 core copper cable for indoor to outdoor & supply cable. The cost also included the required length of connecting copper pipe anti-corrosion treated with sleeve, drain pipe 3 core copper cable, and outdoor condenser 'L' type stand/ painted bracket/cage if required as per site condition with all accessories/ GI nut, bolt, hardware, material required for fixing, HD PVC/ Flexible pipe, etc. The cost shall also include the manufacturer's warranty of 2 years for replacing parts against any defects. |
| 66 | Supply - 1.5 ton |
| 67 | Erection - 1.5 ton |
| 68 | Providing fully furnished porta cabin with partition & urinal on hire of minimum size 9.14 m x 3.05 m fully wired, one Table with Chair, two Visitor chairs, small Almira, one side table, AC , computer, printer, stationaries etc. in one side of partition and 1 big table with eight chairs on other side of partition as directed by Engineer. Rate includes contractor's material, labour, transportation, lead & lift, etc. complete. The cost also includes maintenance, security, electricity & cleaning during contract period. |
| 69 | One site safety enforcer/site supervisor |
| 70 | Daily Document Entry/Recorder operator/ Site assistance (Skilled/Clerical) |
| 71 | Supply & Laying of 1Cx70 sq mm earthing Cable |
| 72 | Drilling of hole, and cleaning minimum 38 mm diameter holes in rock / concrete with drifter or other suitable means (for 20 mm diameter bolts / anchors) including grouting of anchors, rock bolts, perfobolts, etc. In cement mortar 1:1 by using conbextra GP-ii chemical or equivalent. Depth of hole is 1.00 mtr. including supply of Bolts |
| 73 | 2.0 Modification of incoming EHV Power supply arrangement at Vasai MSETCL Receiving Stations |
| 74 | Supplying, multiple loading/ unloading, storing, erection, testing and commissioning of 132 kV CB for 3P trip along with support structure 1600A - 145KV, 40KA/3 Sec. Mechanically Gang Operated including required modification of existing foundation as per drawings with erection of support structure its levelling, mechanism, pole, required piping cabling and termination up to MB, earthing of CB poles and structures , MB etc. with filling of SF6 if required to specified pressure, fixing of related accessories etc. complete as directed by the Mfg. manual and assisting testing and attending the problems if any up to commissioning |
| 75 | Supply |
| 76 | Erection and Commissioning |
| 77 | Supplying, multiple loading/ unloading, storing, erection, testing and commissioning of following isolators with support structure tightening, levelling, support insulator erection , erection of male female contacts, piping, MOM box fixing, cable laying and termination with alignment of Isolator mechanically and electrically as per Mfg manual with minor alteration at base complete |
| 78 | Supply of 132 kV Isolator with EB, along with insulator and with support structure 1250A - 145KV, 40KA - 3 Sec. |
| 79 | Supply of 132 kV Isolator without EB, along with insulator and with support structure1250A-145kV,40 kA-3 sec. 145 kV, 3625mm Crip, 4 KN |
| 80 | Erection and Commissioning |
| 81 | Supplying, multiple loading/ unloading, storing, erection, testing and commissioning of following types of Current Transformer/ Potential Transformer on provided support structure WITH NECESSARY MODIFICATION with connecting the terminal connectors and jumpers on both sides with required connection with available cables to the terminal box |
| 82 | Supply of 132 kV Current Transformer 145KV, 800-400/1A, 5C, 0.2 S |
| 83 | Supply of 132 kV Current Transformer 145KV, 500/1A, 1C, 0.2 S |
| 84 | Supply of 100 kV Metering PT 100/√3kV / 110 / √3V, 1 Core, 0.2 Cl |
| 85 | Supply of Stud, single (C10b) CT/ CC/ PT |
| 86 | Erection And Commissioning of CT/PT |
| 87 | Supplying, multiple loading/ unloading, storing, erection, testing and commissioning of following Control & Relay panels / BCU's in Main Control Room or in BCR with suitable anchoring as directed with cables glanding and termination etc. withearthing connection as directed |
| 88 | 132 or 100 kV Numerical Feeder Control & Relay Panel with BCU for all type of Bus configuration. 220 V DC with line differential relay. |
| 89 | Erection And Commissioning of panels |
| 90 | 0.4 ACSR Zebra Conductor |
| 91 | Supply of Palm connector for CB Aluminium, 4-holes - Comp type |
| 92 | Erection of Cutting of conductor to required length, fixing of clamps/connector at both end and jumpering to the equipment.132/110/100 kV Jumps |
| 93 | Supply of Additional Hardware (Including BCU, Ethernet Switches, LIU, patch cord, Media converter, etc.) and necessary changes/enhancement in the existing substation automation system in order to integrate the additional (new) bay in the SAS - (For Same Make as that of existing system) |
| 94 | 100 kV Lightning Arrestor Along with power connectors & discharge counter |
| 95 | Supply |
| 96 | Erection And Commissioning |
| 97 | Earthing Pit with Station type Cast Iron Pipes, including earthing materials and Excavation of earth pit, fixing of C.I. and G. I. pipe, backfilling with coal, salt and black soil in layer etc. as per standard procedure that to the extent to get satisfactory results. |
| 98 | Supply |
| 99 | Erection And Commissioning |
| 100 | Supply & Erection of 50 x 8 mm, GI Earthing strips |
| 101 | Taking out the riser connection with provided G.I. Flat with excavation at required place up to main mat and welding the riser to main mat with required bending/ fabrication etc. and taking this riser to the required place of support structure foundation with making it flush with the foundation surface |
| 102 | 120 terminals, outdoor type Marshalling box |
| 103 | Control cable |
| 104 | Cu conductor, 2 core, 2.5 sq.mm steel Armoured, FRLS control cable |
| 105 | Cu conductor, 4 core, 2.5 sq.mm steel Armoured, FRLS control cable |
| 106 | Cu conductor, 7 core, 2.5 sq.mm steel Armoured, FRLS control cable |
| 107 | Cu conductor, 12 core, 2.5 sq.mm steel Armoured, FRLS control cable |
| 108 | Cu conductor, 19 core, 2.5 sq.mm steel Armoured, FRLS control cable |
| 109 | Aluminium conductor, 4 core, 10 sq.mm Armoured, FRLS cable |
| 110 | 3.5 Core, 35 sq.mm. Armoured EC grade aluminium PVC insulated FRLS |
| 111 | 10 core x 2.5 sum control cable |
| 112 | 3.5 core, 35 sq.mm cable, 1100 V, Armoured, E.C grade aluminium PVC insulated FRLS |
| 113 | Structure & Nuts Bolts |
| 114 | Galvanised Gantry structure, equipment support structure including foundation bolts. |
| 115 | Nuts & Bolts |
| 116 | Copper earth bonds |
| 117 | Earth pit with station type cast iron pipes, including earthing materials |
| 118 | PVC pipes ( 110 mm Dia) |
| 119 | AMR Panel suitable for housing 8 Nos of IEM(Interface energy Meters), 1 No DCU, 2 Nos of Network switches, 1 No LIU (if required) with provision for TTBs for CT/PT secondary wiring to IEMs, TBs for terminating cables of AC/DC supply, with separate MCB for AC/DC supply to DCU, Network switch with necessary internal pane wiring up to TBs. |
| 120 | 3 Phase 4 Wire IEM, Rated Current -/1A, rated voltage - 3 x 63.5V (P-N), Frequency - 50Hz, Accuracy class-0.2 S , Standard applicable - IS 14679, IEC 62052-11, ICE 62052-22, CBIP 325, Power Consumption - As per IS 14679, Ingress protection - IP51, Energy Measurement - 4 Quadrant measurement of kWh, kVArh and kVAh, Comm interface - RS232/RS 485/ TCP/IP, Protocol Support - IEC/DLMS/MODBUS. IEM shall be DLMS compliant and suitable for AMR system implemented in MSETCL |
| 121 | Fire extinguisher |
| 122 | 9 Kg DCP Type Fire Extinguisher |
| 123 | 4.5 Kg CO2 Type Fire Extinguisher |
| 124 | Safety Equipments |
| 125 | 220kV FRP Earthing Discharge Rod |
| 126 | 18' 4S FRP Tel. Discharge Rod -132kV |
| 127 | 33/22kV FRP Discharge Rod |
| 128 | Electrical Hand Gloves |
| 129 | Industrial Safety Helmet (IS:2925) |
| 130 | Tools |
| 131 | Tools & Tackles set for Maintenance |
| 132 | First-aid box |
| 133 | 2.0 Construction of Gantry & Equipment Foundation at Vasai MSETCL Receiving Stations |
| 134 | Removing grass, gazer grass and disposing off out of building premised including making clean the ground by shovel and phavaras etc. complete. |
| 135 | Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means |
| 136 | Excavation for foundation in earth, soils of all types, sand, gravel and soft murum, including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m to 3.0m) By Mechanical Means |
| 137 | Excavation for foundation in hard murum, including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m ) By Mechanical Means |
| 138 | Excavation for foundation in hard murum and boulders including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5m) By Mechanical Means |
| 139 | Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 50 metres beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift upto 1.5m) By Mechanical Means |
| 140 | Excavation for foundation in Hard rock by blasting including trimming and levelling the bed by chiselling where necessary and removing the excavated material and stacking it in measurable heaps within distance of 50 metres from the building area including dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift upto 1.5m ) By Mechanical Means |
| 141 | Providing dry/ trap/ granite/ quartzite/ gneiss rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete. |
| 142 | Providing dry trap /rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete Boulders will be supplied by department at free of cost |
| 143 | Providing and laying Cast in situ/Ready Mix cement concrete in M-10 of trap/ granite/ quartzite/ gneiss metal for foundation and bedding including bailing out water, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing if required and curing complete, with fully automatic micro processor based PLC without SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 144 | Providing and laying in situ/Ready Mix cement concrete M-20 of trap/ granite/quartzite/gneiss metal for RCC work in foundation like raft ,strip foundations. Grillage and footings bailing out water, steel centering formwork, laying/pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Cruched sand VSI Grade) |
| 145 | Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite/quartzite/gneiss metal for RCC pardi of required thickness including steel centering, formwork, cover blocks, laying /pumping, compacting, curing, finishing and roughening them if special finish is to be provided and curing complete (Excluding reinforcement and structural steel) etc. With fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 146 | Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite/quartzite/gneiss metal for RCC column as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete (Excluding reinforcement and structural steel) etc. With fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 147 | Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite/quartzite/gneiss metal for RCC slabs and landing as per detailed designs and drawing including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete (Excluding reinforcement and structural steel) etc. With fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 148 | Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite/quartzite/gneiss metal for RCC work in foundations like raft, strip foundations, grillage and floorings of RCC columns and steel centering, formwork, cover blocks, laying/pumping, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. Complete with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 149 | Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite/quartzite/gneiss metal for RCC pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compaction and roughening them if special finish is to be provided and curing complete (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 150 | Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite/quartzite/gneiss metal for RCC coloums as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing complete (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 151 | Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite/quartzite/gneiss metal for RCC slabs and landing as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc complete (Excluding reinforcement and structural steel) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 152 | Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardies, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. |
| 153 | Supplying & filling sand at the cable trench, including conveying and stacking etc. complete |
| 154 | Supplying and spreading 40mm metal By Blasting (Hand broken) trap/granite/quartzite/gneiss/ laterite stone metal at the road side for metal including conveying & stacking etc. complete. |
| 155 | Providing and laying approved factory made precast M20 or as directed RCC cable protection cover of required size and thickness as per detailed drawing, with embossing MSETCL letters and as directed by Engineer-in-charge, transporting up to work site and stacking as directed, etc. complete |
| 156 | Providing and laying weep holes of 100 mm diameter PVC pipes as per drawing for abutment returns, return walls etc. complete |
| 157 | Dewatering on BHP basis by using water pump including diversion of stream, providing cofferdams, earthen bunds etc. as may be necessary for foundation and other parts of the works and pumping out water during and after excavation as may be required by using 5.00 to 9.0 BHP pump etc. complete (prior approval of Superintending Engineer will be necessary) |
| 158 | Providing factory made M-35 Grade Prestressed concrete cable trench covers of 75 mm thick (length upto 1.20 to 2.5m) sizes having 7 number of 4 mm dia. H. T. wire cast with necessary required tensioning. Compacting with vibrator, providing handles for lifting, pond curing & finishing top surface & sides faces with necessary cutting of HT wire by Gas welding /welding/Grinder etc. all complete |
| 159 | Providing and fixing cable route marker M15 concrete stone of size 600x150x300 block including curing, painting lettering etc. complete as per directives of Engineer in charge. |
| 160 | Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting , fabricating, hoisting, erecting, fixing in position making rivoted /bolted/ welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete |
| 161 | Providing and erecting chain link fencing 1.6 M height with G. I. chain link of size 50 x 50 mm, 8 gauge thick and fixed 75 mm above ground level on vertical MS Angles of 40x40x6 mm size, including excavating pits for foundation and embedded in C. C. Block of 1:4:8 mix of size 450x450x670 mm at 1.75 M. c/c with iron bar 16mm Dia as hold fast including welding link with angle frame at 30 cm c/c with nuts and bolts and horizontal M.S. Angles at top and bottom of 25x25x5 mm size and vertical M. S. flat 35 x 5 mm and 25 x 5 mm horizontal including cross support of 40x40x6 mm angles both side at every corner or bend embedded in concrete blocks of 1:4:8 of size 450x450x670 mm including 3 coats of oil painting etc. complete. |
| 162 | Transportation of debris/ excavated material outside the premises, including stacking in measurable heaps, loading, conveying, uploading with a lead of 10 km etc. complete (including all payments to respective authorities) for one trip equal to EA (each) |
| 163 | Filling in plinth and floors with approved excavated material in 15 cm to 20 cm layers including watering and compacting etc complete. |
| 164 | Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 cm to 20 cm including watering and compacting etc. complete. |
| 165 | Proving Horizontal Directional Drilling of 200 mm Dia for laying of provided HDPE pipe of 160 mm Dia for Road crossing to correct grade & alignment using Horizontal Directional Drilling Method (HDD) & Pushing of pipe in any type of soil including soft rock/hard rock at 4m depth etc. as directed by Engineer-in-charge, excluding the cost of HDPE pipe, including all necessary excavations & preparing of platform, filling of gap between the bore and pipe by guniting, sealing of joints by using sealant, etc. including all arrangements of tools & all needed machinery, including the cost of repairing /replacing of assets in case of any damage to the assets, etc. complete |
| 166 | Cutting of trees more than 60 cm girth including depositing the wood at nominated locations with loading, transporting etc. The contractor shall obtain necessary approval from concerned authorities for cutting/transplanting trees. The required payment to concerned authority for obtaining permission will be made by MRVC. |
| 167 | Girth of tree over 60 cm and upto 120 cm |
| 168 | Girth of tree over 120 cm and upto 180 cm |
| 169 | Girth of tree over 180 cm |
| 170 | Transplanting of existing trees by uprooting, shifting & placing in pits excavated of suitable size within one KM distance and refilling with manure & soil and maintaining the plant for 12 months. (i) 40% payment will made after proper transplanting of trees. (ii) 30% payment will be made after maintenance of 6 months for survived trees. (iii) 30% payment will be made after maintenance of one year for survived trees. The trees transplanted under this item will not be considered for payment under item 21 for cutting. |
| 171 | Obtaining administrative approval from tree authority for the cutting/transplanting of trees coming in the way of proposed work including preparation of drawing showing the details of trees, processing for the sanction etc. complete. Note:- 1. Fees for obtaining permission of tree cutting/transplanting etc. will be paid separately by MRVC. 2. The required permission/all formalities from concerned tree authority will be obtained by contractor. 3. One job means permission for tree cutting/transplanting in all locations of the project as applicable and specified by Engineer |
| 172 | Credit for taking away already cut wood. |
| 173 | 2.0 SHE Provision for Vasai TSS |
| 174 | Payment for ensuring implementation and monitoring of all provisions in Safety, Health and Environmental Manual (SHE Manual) of MRVC during execution of works through entire contract period including deployment of required SHE organization as mentioned in SHE manual and explanatory note with required qualification, arranging training to all workers and staff engaged for work, regular health check up of labours, arranging SHE meetings, SHE Inspection, SHE audit, SHE communication i.e. posters/signages/VIDEO/Audio, SHE housekeeping, Safety training, provision of protective wears, labour welfare measures, Environmental management, traffic management of vehicles for construction activities, etc. complete as detailed in Safety, Health and Environment manual of MRVC. Note:-1. Payment against the BOQ will be made at quoted price of item for work done & billed in each interim payment.2. Separate SHE organization/team shall be deployed with required adequate support staff as mentioned.3. Penalty will be imposed for failure or violations in implementation of SHE manual provisions as mentioned in Part V of SHE Manual.4. Persistent failure or violation of SHE manual provision may attract termination of contract.5. Payment will be released with each interim payment as per quoted price by the contractor for the item after recovering penalties imposed for violation of provisionagainst manual, if any.6. In case of no progress of work, no payment will be made under the item.7. The works regulations and operational guidelines regarding Safety, Health and Environment are applicable and the above item of implementation/compliance includes the same.8. Payment for this item will be released only after certification by Dy. CPM/ Dy. CEE/ AGM. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 29 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 29 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender