Tender For Supply Installation Testing and Commissioning of Panels, Distribution Boards, Cable Trays, Earth Pits, Cable Laying In Underground And Other Associated Works For Proposed Canteen Building At Inrp(O), Nrb, Barc Tarapur
Tender Overview
Project Description
Tender for Supply Installation Testing and Commissioning of Panels, Distribution Boards, Cable Trays, Earth Pits, Cable Laying In Underground And Other Associated Works For Proposed Canteen Building At Inrp(O), Nrb, Barc Tarapur
BOQ
| Sl. No. | Item Description |
| 1 | Supplying ,laying,testing and commisioning of following 1100 volt grade FRLS XLPE insulated PVC inner sheathed and FRLS PVC outer sheathed copper conductor armoured cables as per specification burried underground,in existing trenches, cable trays, ducts, clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning. |
| 2 | Supply of 4C x 35 sq. mm 2XWY |
| 3 | laying ,testing and commisioning of 4C x 35 sq. mm 2XWY |
| 4 | Supply of 4C x 10 sq. mm 2XWY |
| 5 | laying ,testing and commisioning of 4C x 10 sq. mm 2XWY |
| 6 | Supply of 4C x 6 sq. mm 2XWY |
| 7 | laying ,testing and commisioning of 4C x 6 sq. mm 2XWY |
| 8 | Supply of 4C x 4 sq. mm 2XWY |
| 9 | laying ,testing and commisioning of 4C x 4 sq. mm 2XWY |
| 10 | Supply of Cable End Terminations for following types & sizes of cables brass gland & copper lugs |
| 11 | 4C x 35 sq. mm 2XWY |
| 12 | 4C x 10 sq. mm 2XWY |
| 13 | 4C x 6 sq. mm 2XWY |
| 14 | 4C x 4 sq. mm 2XWY |
| 15 | Installation of Cable End Terminations for following types & sizes of cables brass gland & copper lugs |
| 16 | 4C x 35 sq. mm 2XWY |
| 17 | 4C x 10 sq. mm 2XWY |
| 18 | 4C x 6 sq. mm 2XWY |
| 19 | 4C x 4 sq. mm 2XWY |
| 20 | Design, Fabrication, Supply, Unloading, Handling, Installation, Commissioning of GI Ladder / Perforated cable tray along with coupler plates and G.I Hardware and 2.50 Metre long and rung spacing of 250 mm. of following sizes, suspended from ceiling or fixed vertically on wall / column as per route directed at site, as approved complete as per technical specifications, drawings & relevant standards & site conditions. Hot Dipped Galvanized Perforated Cable Trays (PCT) of following sizes |
| 21 | 100mm (W) x 50mm (H) X 2mm (T) PCT |
| 22 | LT PANELS:Supply, Assembly, installation, testing and commissioning of LT Distribution panels. suitable for 415 V, 3 phase, 50 Hz, 4 wire as per the SLD.Panels shall be fabricated out of 2 mm thick powder coated CRCA sheet steel in cubical formation, compartmentalized in Form 3b Construction, floor mounted, free standing / wall mounting and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel as per annexure and drawings. |
| 23 | Supply of EPCC Panel Ground Floor(Suitable for outdoor)Incomer: 250A, 4P, 70kA MCCB(LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,as per SLD), Analog voltmeter , CT , LCD type Load manager Outgoing feeders (8 Nos): 160A TPN MCCB,50kA with A-meter and indication lamp(on,off,trip)- 03 Nos., 40A TPN MCCB, 50kA-05 Nos. |
| 24 | Assembly, installation, testing and commissioning of EPCC Panel Ground FloorIncomer: 250A, 4P, 70kA MCCB(LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,as per SLD), voltmeter , CT , LCD type Load manager Outgoing feeders (8 Nos): 160A TPN MCCB,50kA with A-meter and indication lamp(on,off,trip)- 03 Nos., 40A TPN MCCB, 50kA-05 Nos. |
| 25 | Supply of Kitchen Panel Ground FloorIncomer: 125A, 4P, 70kA MCCB(LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,)as per SLD),voltmeter , CT , LCD and Load Manager,Outgoing feeders (6nos): 40A TPN MCCB, 50kA-06 Nos. |
| 26 | Assembly, installation, testing and commissioning of Kitchen Panel Ground FloorIncomer: 125A, 4P, 70kA MCCB(LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,)as per SLD),voltmeter , CT , LCD and Load Manager,Outgoing feeders (6nos): 40A TPN MCCB, 50kA-06 Nos. |
| 27 | supply of NPCC Panel(Suitable for outdoor)Incomer: 250A, 4P, 70kA MCCB (LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,)as per SLD),voltmeter , CT , LCD and Load Manager,Outgoing feeders(15 Nos):125A TPN MCCB, 50kA with A-meter and indication lamp(on,off,trip)- 02 No.63A TPN MCCB, 50kA with A-meter and indication lamp(on,off,trip)- 08 Nos.40A TPN MCCB, 50kA-05 Nos. |
| 28 | Assembly, installation, testing and commissioning NPCC PanelIncomer: 250A, 4P, 70kA MCCB (LSIG BASED O/L,S/C,E/F PROTECTION ) BMS Compatible with Indication lamp(ON,OFF,TRIP,R,Y,B etc.,)as per SLD),voltmeter , CT , LCD and Load Manager,Outgoing feeders(15 Nos):125A TPN MCCB, 50kA with A-meter and indication lamp(on,off,trip)- 02 No.63A TPN MCCB, 50kA with A-meter and indication lamp(on,off,trip)- 08 Nos.40A TPN MCCB, 50kA-05 Nos. |
| 29 | FINAL DISTRIBUTION BOARDS:Supply of the following Double Door, IP43, MCB DBs including switch gears. |
| 30 | 12 Way TPN DB (ELDB-1 For Ground Floor)Incomer: 32A 4P MCB, 10kA-01 No.,Sub Incomer: 16A DP ELCB, 300mA- 03Nos.,Outgoing: 10A, SP MCB, 10kA-30Nos. |
| 31 | 12 Way TPN DB (ELDB-2 For Kitchen Floor)Incomer: 32A 4P MCB, 10kA-01 No., Sub Incomer: 25A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 32 | 12 Way TPN DB (ELDB-3 For First Floor)Incomer: 32A 4P MCB, 10kA-01 No.,Sub Incomer: 25 A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 16kA-30Nos., |
| 33 | 12 Way ETPN DB (LDB-1 For Ground Floor)Incomer: 32A 4P MCB, 10kA-01 No., Sub Incomer: 25A DP ELCB, 300mA- 03Nos., Outgoing: 10A, SP MCB, 10kA-30Nos., |
| 34 | 16 Way ETPN DB (LDB-2 For First Floor)Incomer: 40A 4P MCB, 10kA-01 No.,Sub Incomer: 16A DP ELCB, 300mA- 03Nos., Outgoing: 10A, SP MCB, 10kA-42Nos. |
| 35 | 12 Way ETPN PDB-1 (PDB-1 For Ground Floor)Incomer: 40A 4P MCB, 10kA-01 No.Sub Incomer: 32A DP ELCB, 300mA- 03Nos.Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 36 | 12 Way ETPN PDB-2 (PDB- For First Floor)Incomer: 40A 4P MCB, 10kA-01 No., Sub Incomer: 32A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 37 | 40A, TPN RCBO, 100mA with Enclosure for VRV ODU & Lift , |
| 38 | 63A, TPN RCBO, 100mA with Enclosure VRV ODU & Lift , |
| 39 | Installation, testing and commissioning of the following Double Door, IP43, MCB DBs including switch gears. |
| 40 | 12 Way TPN DB (ELDB-1 For Ground Floor)Incomer: 32A 4P MCB, 10kA-01 No.,Sub Incomer: 16A DP ELCB, 300mA- 03Nos.,Outgoing: 10A, SP MCB, 10kA-30Nos. |
| 41 | 12 Way TPN DB (ELDB-2 For Kitchen Floor)Incomer: 32A 4P MCB, 10kA-01 No., Sub Incomer: 25A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 42 | 12 Way TPN DB (ELDB-3 For First Floor)Incomer: 32A 4P MCB, 10kA-01 No.,Sub Incomer: 25 A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 16kA-30Nos., |
| 43 | 12 Way ETPN DB (LDB-1 For Ground Floor)Incomer: 32A 4P MCB, 10kA-01 No., Sub Incomer: 25A DP ELCB, 300mA- 03Nos., Outgoing: 10A, SP MCB, 10kA-30Nos., |
| 44 | 16 Way ETPN DB (LDB-2 For First Floor)Incomer: 40A 4P MCB, 10kA-01 No.,Sub Incomer: 16A DP ELCB, 300mA- 03Nos., Outgoing: 10A, SP MCB, 10kA-42Nos. |
| 45 | 12 Way ETPN PDB-1 (PDB-1 For Ground Floor)Incomer: 40A 4P MCB, 10kA-01 No.Sub Incomer: 32A DP ELCB, 300mA- 03Nos.Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 46 | 12 Way ETPN PDB-2 (PDB- For First Floor)Incomer: 40A 4P MCB, 10kA-01 No., Sub Incomer: 32A DP ELCB, 300mA- 03Nos., Outgoing: 16A, SP MCB, 10kA-30Nos. |
| 47 | 40A, TPN RCBO, 100mA with Enclosure for VRV ODU & Lift , |
| 48 | 63A, TPN RCBO, 100mA with Enclosure VRV ODU & Lift , |
| 49 | Supply, of Pipe in pipe Maintenance free Chemical Earthing System., Model 3 Meters, Outer Electrode dia 50 mm inner dia 25 mm,filled with highly conductive material with outer electrode coated up to 70-100 micron galvanisation with HDG and inner electrode coated upto 200-250 micron galvanisation Tightly filled with Crystalline Conductor Mixture with HDG along with 2 bags of back fill compound (BFC) 25 Kg each complete . Rigid PVC Rectangular inspection chamber approximately 1'X11/2' with removable cover etc complete, test link etc complete including boring, refilling, levelling etc. to obtain Earth Resistance up to Approx. 1 OHM. |
| 50 | For Panel & DBS. Earthing |
| 51 | Installation & Commissioning of Pipe in pipe Maintenance free Chemical Earthing System.Model 3 Meters, Outer Electrode dia 50 mm inner dia 25 mm,filled with highly conductive material with outer electrode coated up to 70-100 micron galvanisation with HDG and inner electrode coated upto 200-250 micron galvanisation Tightly filled with Crystalline Conductor Mixture with HDG along with 2 bags of back fill compound (BFC) 25 Kg each complete . Rigid PVC Rectangular inspection chamber approximately 1'X11/2' with removable cover etc complete, test link etc complete including boring, refilling, levelling etc. to obtain Earth Resistance up to Approx. 1 OHM. |
| 52 | For Panel & DBS. Earthing |
| 53 | Air termination |
| 54 | Supply of 10 mm dia and 1mtrs length solid copper blunt tip Air termination with Base plate (Vertical air terminal with accessories:Providing of Air terminals along with concrete block for fixing at on Terrace with all mounting accessories with Supporting Mast Fabricated from GI pipe of 48 mm dia, 1000mm length providing with all necessary hardware andguide wire for mounting arrangement for the downconductor and complte it's accessories. |
| 55 | Installation & Commissioning of 10 mm dia and 1mtrs length solid copper blunt tip Air termination with Base plate (Vertical air terminal with accessories:Providing of Air terminals along with concrete block for fixing at on Terrace with all mounting accessories with Supporting Mast Fabricated from GI pipe of 48 mm dia, 1000mm length providing with all necessary hardware andguide wire for mounting arrangement for the downconductor and complte it's accessories. |
| 56 | Supplying, laying (on cable trays or through pipes provided by others or on walls/ columns or in dug up trench (to be made by bidder) to a depth of 300mm) and connecting the following continuous earth conductors. Note: Any joint in the copper earth conductor shall be made by the process of brazing: |
| 57 | 25x3 mm cu strip |
| 58 | 8mm dia CU Conductor |
| 59 | 4 sqmm pvc insulated copper flexible cable |
| 60 | 6 sq. mm. PVC insulated copper flexible cable |
| 61 | 8 SWG bare cu conductor |
| 62 | SAFETY ITEMS:SUPPLY AND INSTALLATION OF SAFETY ITEMS |
| 63 | Supply and fixing of Shock Treatment Chart in electrical room, with 3 mm thick wooden frame & glass cover, along with hanging arrangement or to be mounted on a wall as per directions of the Engineer-In-Charge (To be provided in Languages : Hindi & English) |
| 64 | Supply & installation of 415 V DANGER caution board of designated size (6\\"x 6\\"), made of Mild Steel, at least 2 mm thick & painted vitreous enameled white on both sides, & with inscriptions in signal red colour on front side( to be mounted on doors of electric shafts, electric room, etc.)(To be provided in Languages : Hindi & English) |
| 65 | Providing the A2 Colour size print of the Final Plan / SLD duly framed out on Glass for Electrical room and also the soft copy . |
| 66 | Supply & Laying of 1m Wide , 2m long , 3mm thick polymer mat in front of LT panels, ISI marked as per IS: 15652-2006, 11kV grade , Class - B . |
| 67 | Supply of First Aid Box with accessories, conforming to IS: 2217-1963 Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender