Tender For Installation & Commissioning Assistance Of 750 Kva Dg Set With Allied Electrical And Civil Works, Rev Of Pmcc & Associated Panels And Supply Installation Testing and Commissioning of Apfc, Avr And Ups With Battery Bank At North Guwahati Bp
Tender Overview
Project Description
Tender for Installation & Commissioning Assistance Of 750 Kva Dg Set With Allied Electrical And Civil Works, Rev Of Pmcc & Associated Panels And Supply Installation Testing and Commissioning of Apfc, Avr And Ups With Battery Bank At North Guwahati Bp
BOQ
| Sl. No. | Item Description |
| 1 | Installation & Commissioning assistance of 750 KVA DG Set with allied electrical and civil works, revamp of PMCC & associated panels and SITC of APFC, AVR and UPS with battery bank at North Guwahati BP |
| 2 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including taking out the excavated soil & disposal of surplus excavated soil as directed, within or outside the site at an unobjectionable place. |
| 3 | Half brick masonry with common burnt clay F.P.S.(non modular)brick of & class designation 7.5 in Cement mortar 1:3 (1 cement :3 coarse sand) IN FOUNDATION AND PLINTH |
| 4 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: PCC 1:2:4 |
| 5 | Reinforced cement concrete work in beams, suspended floors, roofs having & slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:2:4(1 cement:2 coarse sand:4 graded stone aggregate 20 mm nominal size) |
| 6 | Thermo-Mechanically Treated Bars of Fe- 500D grade or more, conforming to IS1786 |
| 7 | Centering and shuttering including strutting, propping etc. and removal of form work |
| 8 | 15 mm cement plaster of mix 1:4 (1 cement: 4 coarse sand) on rough side of & half or single brick wall |
| 9 | Providing neat cement finish |
| 10 | Structural steel work riveted, bolted or welded in built up sections, trusses & framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 11 | Supplying and fixing MS foundation bolts with necessary GI nuts and washers of specified sizes,all conforming to relevant Indian Standard sand as approved by Engineer-in-charge : 20mm dia x 600mm long with 100 mm dia x 6 mm thick plate |
| 12 | Providing and fixing Klippon Galvalume steel profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) of Cold rolled steel confirming to IS:513-2008 of base metal thickness0.50 mm, having Yield Stress of Min. 275 MPa. Steel surface shall have hot dip metallic coating of Al-Zinc alloy comprising 55% Alluminium,43.5% Zinc and 1.5% Silicon as per the ASTM-A792M, with total mass of coating on both sides shall be 150 gms/sqm. The steel shall have organic coating with Silicon Modified Polyester (SMP) /Super Durable Polyester (SDP) paint on continuous coil coating line. The thickness of coating on top side shall be 20-25 Microns (i.e. 15-18 microns SMP/SDP paint over 5-7 microns epoxy primer) and back side 8-10 Microns SMP/SDP paint over epoxy primer Total Coated Thickness (TCT)shall be 0.58 MM. Sheet shall have protective guard film of thickness of 25 microns minimum to avoid scratches while transportation and should be supplied in single length up to 6m or as desired by Engineer-in-charge. |
| 13 | Providing and fixing G.I. chain link fabric fencing of required width in mesh & size 50x50mm including strengthening with 2mm dia GI wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge using hot dipped galvanised wire of 4mm dia (The rate for civil works for excavation, brick masonry, PCC shall be paid separately): For fence height up to 1.2m from Ground |
| 14 | Supply of Galvanised Fire buckets (with stand) of 9 litre capacity, painted white inside and red outside with letters 'fire' in black, conforming to IS 2546-1974. |
| 15 | Supplying and fixing of 4.5kg CO2 fire extinguisher of approved make Conforming to IS 15683, portable high pressure type. Body seamless Manganese Steel, ISI marked conforming to IS 7285, discharge valve conforming to IS 324,polyethylene flat discharge horn with diffuser,1mwire braded rubber hose, powder coated wall mounting mild steelbracket, stainless steel safety pin of SS 316 grade, CO2 gas with99.5% purity. Extinguisher shall have anti corrosive treatment of phosphating by hot dipping process to thickness not less than 0.012mmboth internally and externally. Epoxy polyester powder coating of minimum 50 micron to all metallic external parts with two bands of yellow colored fluorescent adhesive tape of minimum 20mm thickness of body. Finish of the paint to be PO red as per shade 538 of IS:5 |
| 16 | SUPPLY & LAYING OF 400 sq.mm X 3.5 Core AL. LTXLP Armoured cable |
| 17 | SUPPLY & LAYING OF 24 C x 1.5 sq. mm. Cu. Armoured Control cable |
| 18 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including taking out the excavated soil & disposal of surplus excavated soil as directed, within or outside the site at an unobjectionable place : EXCAVATION OF EARTH FOR CABLE TRENCH |
| 19 | CABLE BRICK DUCT Providing & constructing underground brick duct 650mm below GL for laying of 3 cables of max. diameter 70mm, complete with supply and laying of sand, bricks & including Excavation and backfilling in all kind of soils : 450 mm (24 Bricks & 0.0494 cum per Mtr) |
| 20 | INSTALLATION OF DG AMF PANEL |
| 21 | CABLE TERMINATION GLANDS NON-FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination (NON FLP): Providing termination of 1.1 kV grade armoured cable for the following sizes including supply of NON FLP heavy duty Double Compression cable glands, crimping type lugs and allied jointing materials, etc. all complete as per specification and direction of Engineer In-charge. Glands and lugs shall be of approved make. Copper lugs for copper cables and aluminium lugs for aluminium cables shall be used. |
| 22 | Providing earthing with 100 mm dia, 3.0M long C.I pipe as per IS:3043 (with latest amendment) including & providing suitable earth bus for interconnection, providing a mixture of salt &charcoal, making earth pit chamber with chequered plate cover asper standard Drawing all complete as per specification &direction of Engineer In-charge |
| 23 | Supply & drawing/laying, jointing, connecting, testing and commissioning of earth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following : 50 x 6 mm G.I. Strip |
| 24 | DG Commissioning Assistance Charges. Job includes shifting of DG set to the designated area and installation of acoustic enclosures, Supply & Installation of exhaust piping including installation of glass wool cladding on exhaust pipes, . Supply & Installation of Diesel fuel lines . Job also includes commissioning charges which shall be charged by OEM M/s Jakson Limited for commissioning of the DG. |
| 25 | Installation of corporation supplied Draw out Panel & MLDB Panel Also job includes Dismantling of Existing Draw out Panel by Hydra / manual means including removal of old cables, sand/earth in trenches. Also, job includes Refurbishing/Revamping of old AMF panel for 750 KVA DG Set. Job also includes dismantling of floor etc, construction of panel foundation as per site requirement, installation , wiring, retrofit of panels including supply of spares, if any etc. Any and all jobs as per direction of Site In-charge |
| 26 | Supply & Installation of Automatic Power Factor Correction panel suitable for 350 kVAR capacitor bank and also job includes dismantling of existing panel |
| 27 | Supply & Installation of 2x 50 KVA UPS |
| 28 | Supply of 230 V AC UPS distributor board with 30 No feeders |
| 29 | Installation of 230 V AC UPS distribution board |
| 30 | Supply & Installation of Battery bank suitable supply of parallel battery bank(2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries, monitoring software etc |
| 31 | Supply, Installation, Testing and Commissioning of 2000 kVA AVR Systems Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender