Tender For Construction Of Internal Roads, Landscaping And Supply, Installation, Testing and Commissioning Of 400Kva Transformer Substation, 250Kva Dg Set, Area Lighting And Firefighting System For Goa College Of Veterinary And Animal Science At Curt
Tender Overview
Project Description
Tender for Construction Of Internal Roads, Landscaping And Supply, Installation, Testing and Commissioning Of 400Kva Transformer Substation, 250Kva Dg Set, Area Lighting And Firefighting System For Goa College Of Veterinary And Animal Science At Curti Ponda Goa (Civil + Electrical + Fire Fighting Work).
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling asbestos sheet roofing including ridges hips valley and gutters and stacking the material within 50 meters lead. |
| 2 | Dismantling steelwork in single sections in channels angles tees and flats including dismembering and stacking within 50 mts. lead |
| 3 | Demolishing laterite stone masonry in cement mortar including stacking of serviceable material & disposal of unserviceable material within 50 mts. lead. |
| 4 | Earthwork in surface excavation not exceeding 30 cm depth(but exceeding1.5 m width as well as 10 sq.m on plan) including disposal of excavated earth beyond work site for all leads lift disposed earth to be leveled and neatly dressed in a) Ordinary soil |
| 5 | Earthwork in excavation by mechanical means (hydraulic exca vator)/manual means over areas (exceeding 30 cm in depth 1.5 m in width as well as 10 sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading danger lighting guarding as directed in : a) All kinds of soil |
| 6 | Extra for additional depth of 1.5 m or part thereof in: a) All types of soil |
| 7 | Earthwork in excavation by mechanical means (hydraulic exca vator)/manual means in foundation pipeline trenches drain (not exceeding 1.5 m in width or 10 sq.m. on plan) including dressing of sides and ramming of bottoms lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 m.; a) All kinds of soil |
| 8 | Refilling the p ipeline/foundation trenches plinth sides foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 M and all lifts and disposal of surplus earth as directed by Engineer in Charge. |
| 9 | Rubble packing with hard laterite stone under floors including watering ramming and consolidating etc. in pipeline trenches and other foundations complete. |
| 10 | Providing & laying cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded granitic or basaltic stone aggrt. 20 mm. nominal size) excluding cost of centering shuttering and finishing in: a) All works upto plinth level |
| 11 | Providing and laying in position ready mixed concrete (RMC) with usage of Ordinary Portland Cement manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead upto 10kms having continuous agitated mixer manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from the transit mixer to the site of laying excluding the cost of centering shuttering finishing and reinforcement including the cost of admixtures in recommended porportions as per IS : 9103 to accelerate/ retard setting of concrete improve workability without imparing strength and durability as per the directions of the engineer- in-charge. All works upto floor V level;M-30grade of concrete |
| 12 | Centering and shuttering including struttings propping etc. and removal of formwork for : a) Foundations footings bases for columns and mass concrete. |
| 13 | Centering and shuttering including struttings propping etc. and removal of formwork for : b) vertical surfaces such as retaining walls return walls walls (any thk) including attached pilasters buttresses plinth and string courses fillets etc. |
| 14 | Centering and shuttering including struttings propping etc. and removal of formwork for : c) Columns Pillars piersabutments posts and strut square rectangular polygon in plan. etc. |
| 15 | Centering & shuttering including Strutting Propping & removal of forms for : iv) Sides and Soffits of beams Beam Haunchings Cantilever Girders Bressumers and Lintels plinth beams not exceeding 1m in depth |
| 16 | Centering & shuttering including Strutting Propping & removal of forms for : xiii) Suspended floors roofs landings shelves & their supports |
| 17 | Kotah stone slab flooring over 20 mm (average) thick base laid over & jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing & complete with base of cement mortar 1:4 (1 cement : 4 coarse sand); a) 20 mm thick. |
| 18 | b) Kotah stone slab flooring over 25 mm thick in risers of steps skirtings dado & pillars laid on 12mm (average) thick cement mortor 1:3 (1 cement : 3 coarse sand) & jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing & polishing complete. |
| 19 | Supplying and fixing of Precast RCC slabs(factory madethe factory should be ISO certified and registered under Dirctorate of Industries Govt. of India) at site in concrete Grade of M-25 with 20 mm nominal size Granitic or basaltic aggregate consolidated by means of mechanical platform vibration etc. with lifting hooks of M.s. 10mm bars and PVC cups including cost of reincforcement Certificate from manufacturer shall be produced indicating grade of concret and minimum content of steel in the product along with 5 year free replacement warranty in case of breakage complete and as directed by Engineer -in -charge.; c) size 750 x 400 x 100 mm cm with reinforcement not less than 4.2 kg perunit |
| 20 | Supplying and fixing Pre- cast cement concrete kerb- stones(factory madethe factory should be ISO certified and registered under Dirctorate of Industries Govt. of India) of M-20 with 20 mm nominal size granitic /basaltic aggregate properly consolidated by mechanical plat-form and vibrators with smooth finish including fixing at site complete as per specification.a) Size 30 cm L x 50 cm H x 15 cm T |
| 21 | Providing and laying factory made Shot blasted cement concrete interlocking paver block of minimum M35/M40 grade made by heavy duty block making machine with strong vibratory compaction and of aprpoved size and design / shape laid in 50 mm thick compacted bed of coarse sand filling the joints with coarse sand etc. all complete as per the direction of Engineer.- in I Wave Rectangular Square etc. shapes. The products should comply to IS 15658: 2006 and manfucatured by ISO9001: 2008 certified plant. The shot blasting should be done using 0.4- 0.5mm dia steel shots with a speed of 3200 rpm. a) 60 mm thick in all colours except grey (M35 grade) |
| 22 | Providing and laying upto floor five level cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size) including smooth finishing to exposed surfaces with cement mortar 1:3 (1 cement: 3 fine sand) including centering and shuttering etc. b) String courses copings bedplates anchor blocks plain window sills and the like. |
| 23 | Providing and laying in position (1:11/2:3) Reinforced cement conrete excluding the cost of centering shuttering finishing and reinfrocement (1 cement: 1½ coarse sand:3 graded stone agg 20mm nominal size) a) All works upto plinth level |
| 24 | Providing and laying in position (1:11/2:3) Reinforced cement conrete excluding the cost of centering shuttering finishing and reinfrocement (1 cement: 1½ coarse sand:3 graded stone agg 20mm nominal size) b) In walls (any thickness) including attached pilasters buttresses plinth and string courses fillets columns pillars piers abutments posts and structs etc. upto floor five level |
| 25 | Providing and laying in position (1:11/2:3) Reinforced cement conrete excluding the cost of centering shuttering finishing and reinfrocement (1 cement: 1½ coarse sand:3 graded stone agg 20mm nominal size);In beams suspended floors roofs having slope upto 15° landings balconies shelves chajjas lintels bands plain window sills staircases upto floor five level |
| 26 | Providing TMT steel reinforcement bars of (SAIL TATA. VIZAGJSW Steel Ltd.) ) (Confirming to IS 1786 of 1986) for RCC work (conforming to I.S. 1786 of 1986) including bending binding & placing in position in all the floors along with the factory made precast concrete cover blocks of specified sizes whose compressive strength is not less than that of surrounding concrete in the structural member. |
| 27 | Steel work in single sections (SAIL TATA. VIZAG & using electrodes of Ador or ES4B or Deh Secheron make only) including cutting hoisting fixing in position and applying a priming coat of red lead paint. b)In flats of all sizes |
| 28 | Steel work in built up tubular (round square or rectangular hollow tubes etc.) (Square Hollow Section (SHS) IS4923/Rectangular Hollow Section (RHS) IS4923/ Circular Hollow Section (CHS) IS1161 closed Structural Steel of (SAIL TATA. VIZAG JSWAPOLLO Steel Ltd.) make (Min Yeild Stress 310 Mpa)) trusses etc. including cutting hoisting fixing in position and applying a priming coat of approved steel primer including welding and bolted with special shaped washers etc. complete. |
| 29 | Providing and fixing G.I. chain link mesh 6.35cm x6.35 cm x 10 gauge (2.5” x2.5” x 10 gauge) fixed with angle iron posts and struts by G.I. or M.S. staples at 20cms apart with welding with the iron posts (placed at 3 meters centre to centre) including providing barbed wire stiffeners (shall weigh 9.33 kg. per 100 meters minimum) at top and bottom with barbed wire stiffers by binding wires at 50cms centre to centre complete as per the direction of the Engineer – in – charge (angle iron posts struts earthwork and concrete for fencing posts and struts to be paid separately) |
| 30 | Laterite masonry in neatly dressed stones of size as specified in cement mortar 1: 4 (1 cement : 4 coarse sand) in foundation and basement. |
| 31 | Laterite masonry in neatly dressed stones of size as specified in cement mortar 1: 4 (1 cement : 4 coarse sand) in foundation and basement. + Extra for laterite masonry in all sizes in superstructure from floor I level upto floor V level. |
| 32 | 12mm cement plaster 1: 3(1 cement ; 3 coarse sand) finished with a floating coat of neat cement. |
| 33 | 18mm cement plaster in two coats under layer 12mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand) and top layer 6mm thick with cement plaster 1: 3 (1 cement : 3 coarse sand) finished with sponge. |
| 34 | Providing and applying white cement based putty of average thickness 1.00 mm of approved brand and manufacturer over the plastered wall surface to prepare the surface even and smooth complete. |
| 35 | Applying one coat of cement primer of approved brand and manufacture on wall surface. |
| 36 | Wall painting (two or more coats) with plastic emulsion paint of approved brand and manufacture on new work to give an even shade. |
| 37 | Painting three or more coats with acryllic exterior paint of approved brand and manufacture (Such as Dulex/ Asian Paints/ Sherwin Willians) including applying one coat of cement primer and one coat of surface treatment etc. complete. |
| 38 | Painting two or more coats (excluding priming coat) with superior quality ready mixed paint for steel work of approved brand & manufacture in all shades on new work to give an even shade. |
| 39 | Supplying and fixing of Precast RCC slabs(factory madethe factory should be ISO certified and registered under Dirctorate of Industries Govt. of India) at site in concrete Grade of M-25 with 20 mm nominal size Granitic or basaltic aggregate consolidated by means of mechanical platform vibration etc. with lifting hooks of M.s. 10mm bars and PVC cups including cost of reincforcement Certificate from manufacturer shall be produced indicating grade of concret and minimum content of steel in the product along with 5 year free replacement warranty in case of breakage complete and as directed by Engineer -in -charge. b) Size 900 x 400 x 100 mm with steel reinforcement not less than 5.0 kgs per unit -12 T capacity |
| 40 | Steel work welded in built up section and framed work including cutting hoisting fixing in position for steel grating of size2.00 m x 0.90 m with R.S. joists Tees angles flats and channels of TATA/ SAIL/ VIZAG make only with structural steel not less than 163.6 kg. per unit including applying priming coat of red lead paint and two or more coats with superior quality ready mixed paint for steel work of approved brand and Manufacture in all shades on new work to give an even shade as per the approved drawing and direction of the Engineer in-charge. |
| 41 | Providing & fixing colour coated Alluminium (PUF) sandwich panel roofing systems of approved make adhering to Aluminium 3105 grade for top & bottom sheet of thickness 0.40 & 0.35 respectively including PUF insulation betewwn the top & bottom sheet of Denslity 40 (+/-2) Kg/m3 inclusive of S.S. 304 grade self tapping fastneres complete as directed by Enigneer incharge (frame work for roof roof accesorries to be paid seperately) for tile Design PUF roof panel Gutter width should be atleast 25% more than the Crest width. Minimum height at heighest point of Crest should be minimum 65mm. Minimum thickness at anygiven point should not be below 30mm. a) PUF Insulated tile roof 30mm thick of trapezoidal design |
| 42 | Providing & Fixing Alluminium Ridge of approved make adhering to Alluminium 3105 grade of 0.71mm thickness & 60 cm wide inclusive of SS304 grade self tapping fastners to match the Alluminium roofing system & as directed by Engineer in charge complete |
| 43 | Providing & Fixing Alluminium 50mm Trapezhoidal End Cap for PUF Roofing of approved make of Alluminium AA 3105 grade matching with 50mm PUF panel profile including the required fastners etc. Complete for Alluminium PUF Roofing System & as directed by Engineer in charge. |
| 44 | Providing and fixing Prince or equivalent make PVC SWR half round eaves gutter with bolts nuts and flat iron brackets 40 x 3 mm size complete. b)180 mm nominal size |
| 45 | Extra for providing and fixing prince or equivalent make PVC SWR short stop ends for socketed half round eaves gutters. b)180 mm nominal size |
| 46 | Extra for providing and fixing prince or equivalent make PVC SWR stop end outlet with one clamp for socketed half round eaves gutters. b) 180 mm nominal size |
| 47 | Providing and fixing PVC SWR pipes confirming to IS 13592 type A including jointing with seal ring confirming to IS 5382 leaving 10 mm gap for thermal expansi on. a) Single socketed pipe 75 mm dia |
| 48 | Providing and and laying vitrified floor tiles in different sizes of Johnson Somany Kajaria (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622 of approved make in colours and shades as specified laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including grouting the joints with white cement and matching pigment etc. complete; b) 600 x 600 mm light Shades |
| 49 | Providing and fixing vitrified antiskid tiles (320x320) and 10mm thick tiles in floor treads of steps landing on 25mm thick bed of cement mortar 1:3 and jointed with cement slurry complete. |
| 50 | Providing woodwork in frames of doors windows clerestory windows trusses & other frames wrought framed and fixed in positon. b) Second class Indian teak wood |
| 51 | Providing and fixing flush doors shutters commercial type core of block board construction with frame of first class hard wood and well matched commercial ply veneering and vertical grains or cross bands and face veneers on the both faces of shutters. b)35mm thick including anodized aluminium butt hinges with necessary screws: |
| 52 | Providing and fixing bright finished brass door latch with necessary screws etc complete a) 300x 16 x 5 mm |
| 53 | Providing and fixing chromium plated brass sliding door bolt with bolts nuts and screws etc. complete. b)250 x 16 mm |
| 54 | Providing & fixing chromium plated brass tower bolts (barrel type) with necessary screws complete.b)200 x 10 mm |
| 55 | Providing and fixing chromium plated brass handle with necessary screws etc. complete a)125 mm |
| 56 | Applying priming coat with ready mixed primer of approved brand and manufacture on wood work complete. |
| 57 | Painting two or more coats (excluding priming coat) with superior quality ready mixed paint for wood work of approved brand & manufacture in all shades on new work to give an even shade. |
| 58 | TWO TRACK SLIDING WINDOW (Heavy):-;Provi ding & fixing Two Track sliding window Yashashri make or equivalent in heavy sections made out of 104mm x 51 mm x 2.5 mm Upvc multi cavity track section & shutter made out of 45mm x54mm x 2.5mm Upvc multi cavity section welded in corners with Glass beading & EPDM Gasket & 4mm clear glass with lock & rollers. The average weight of Two Track Sliding window (Heavy) is 16.75 kg per sq mtr. These Upvc sections are tested by using BS 2782 & DIN 53459 test methods. |
| 59 | Providing and fixing M.S. grill of required pattern in wooden frames of Windows etc. with M.S. flats square or round bars with round headed bolts and nuts or by by screws. a)Plain grill |
| 60 | Providing and laying non- pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand ) including testing of joints etc. complete. 250 mm dia RCC pipe |
| 61 | Providing and laying non- pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand ) including testing of joints etc. complete.;a) 100 mm dia RCC pipe |
| 62 | Supplying and fixing rolling shutters of approved make made of 80 x 1.25 mm M.S. laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5cm long wire springs grade No.2 and M.S. top cover of 1.25 mm thick for folling shutterstop cover and spring. |
| 63 | Waterproofing of sunken slabs toilet blocks terraces on slabs under brickbats roofs watertanks. Cleaning the surface and filling cracks (if any) applying EPCO ACR wherever necessary Providing and Moistening the surface with water to render it saturated. Mix Cement and Monobond WF in the ratio of 1.25 kg to 1 by weight and stir continuously.Apply minimum 2 coats with an interval of 12 hours minimum between the coats. Fix fiber mesh while the first coat is still tacky. Cure with sprinkling of water 3-4 times a day. incl. cost of scaffolding transport etc. as per dir of EIC. All the chemicals will be of Krishna Conchem Products Pvt. Ltd. or Equivalent |
| 64 | Providing and fixing ASTM UPVC pipe conforming to ASTM 2467 with ISO 14001 including all UPVC plain & brass threaded fittings including jointing of pipes & fittings with one step UPVC solvent cement trenching refilling & testing of joints complete as per direction of Engineer. External work.;I) SCH-80(blue)/(w hite) b)25mm outer dia. |
| 65 | Providing & laying of shot Blasted Paving Tiles Basant or Equivalent make manufactured by tile making machine complying with IS:1237: ref: 2005 and manufactured by ISO certified plant. Size: 250mm x 250mm x 28mm (Types: Plain tiles Transverse pattern tiles) b) Other colours |
| 66 | Turfing Lawns with Fine Grassing including Ploughing Dressing (Turfing lawns with fine grassing including ploughing dressing including breaking of clods removal of rubbish dressing and supplying doobs grass roots at 10 cm apart including supplying and spreading of farm yard manure at rate of0.6 cum per 100 sqm) |
| 67 | Planting Flowering Plants and Shrubs in Central Verge |
| 68 | Supplying & spreading of aggregate in HT yard substation using aggregate of size 40mm nominal, leveling etc. as directed by Engineer in charge. |
| 69 | Providing and fixing anodized aluminium FIXED MESH in Fixed windows/ ventilators with Aluminium mesh (1X1) of square shape & Rectangular aluminium sections of 2.5X1.5 inch, including, transportation, scaffolding and handling etc. complete as per direction of the Engineer-in-charge: |
| 70 | Providing, fabricating, finishing, transporting, and installing a life-size Gaur (Indian Bison) sculpture made of Fiber Reinforced Plastic (FRP), including internal structural framework, surface finishing, realistic detailing, painting, and complete installation at site as per approved design and as per direction of the Engineer in charge of aproximate size 8-10ft L x 7- 8ft ht |
| 71 | Designing, modelling, moulding, fabricating, finishing, painting, transporting, and installing a life-size Baby Gaur (Calf) sculpture made of Fiber Reinforced Plastic (FRP), complete with internal structural framework and proper anchoring system, as per approved design and direction of the Engineer in charge ..Aprox size 3.5 -4.5 ft x 2.5 to 3ft ht |
| 72 | Designing, modelling, fabricating, finishing, transporting, and installing Artificial Rocks made of Fiber Reinforced Plastic (FRP) including internal structural framework, surface texturing, natural rock finishing, painting, and complete installation at site as per approved design and drawings. The work includes all materials, labour, tools, scaffolding, transportation, installation, and finishing complete in all respects\\" |
| 73 | Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 400 kVA, Mineral oil immersed and naturally cooled outdoor type,Copperwound, without gas cushioning, hermetically Sealed transformer, de lta/starconnected with additional neutral brought out on load side, temperature riseshould not exceed 45 by thermometer in oil and 50 by the resistancemethod in winding at full load rating, using type A winding insulation (kraft paper) , with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories completewith test certificate with below 1225 Watts at 50%load, 3450 Watts at 100% load as per IS:1180 (part 1): 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. |
| 74 | Supplying, erecting, testing & commissioning 11 kV, 630A, 21kA/3sec, 3 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 2nos. feeder with 2 LBS and 1 no. feeder with 1 VCB. compliant to IEC 62271-100, 200 and 102 as per specification no. SW- HTS/RMU SCADA. |
| 75 | Supplying, installing, testing and commissioning 11 kV 630A, vacuum circuit breaker with internal arc compliance complete erected on provided CC foundation/MS channels/trench, etc. as per specification no SW-HTS/VCB. |
| 76 | Supplying, erecting, testing and commissioning 11KV HT metering cubicle (compact/vertical type) approved by licensee fabricated with 2 mm (14 SWG)M.S. sheets with supporting angle, painted with powder coating / epoxy paint of required shade, copper bus bar size 25 x 6 mm, heavy duty mechanical lock, with counter meter for measuring no of times the opening of meter door, top side cover (CT, PT cover) interlock with meter door, epoxy casted 3 nos CT having required ratio between 10/5A to 50/5A, VA10 or 15, Class 0.5S, epoxy casted 3 nos PT having ratio 11000 /V3/110/V3 VA 50, Class 0.5 suitable for provided trivector meter, and provision for incoming and outgoing cables complete duly tested by licensee with necessary test certificates and erected on provided plinth/cc foundation as per specification no. CP-HT. |
| 77 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with CI/RCC cover having locking/Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil.c)Watering GI pipe 20mm Class B with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs (min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value.Aluminium tag with embossed earthing value to be attached to the pipe.g) watering arrangement(pl umbing will be paid seperately) (a) In soily strata |
| 78 | Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosure with CI/RCC cover having locking/lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil.c)Watering GI pipe 20 mm Class B with funnel as per specs. d) Charcoal/ salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs (min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. g) watering arrangement (plumbing will be paid seperately).;(a) In soily strata |
| 79 | Extra for using salt and charcoal for GI or copper plate earth electrode as required( 96 Kgs of Charcoal and 5 Kgs of Salt) |
| 80 | Supplying and laying 25 mm x 5 mm GI strip at 0.5 m below ground as strip earth electrode including soldering etc. as required |
| 81 | Supply of following size of 3 core HV 11 KV grade ISI mark XLPE cable with stranded compact circular aluminium conductor conductor screened with extruded semiconducting compound XLPE insulated insulation screned with extruded semiconducting compound in combination with copper tape(0.3 KA for 1Sec.) cores laid offinner sheath of PVC tapegalvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS:7098 (Part II) with latest amendments.;3 Core 95 sq. mm |
| 82 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of grade exceeding 1.1 KV but not exceeding 11 KV grade of size not exceeding 120 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Inchargesand cushioning with screened sand bed of 20mm thick protective covering with bricks placed lenghtwise on top of cable all over the run and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) Soily strata |
| 83 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of grade exceeding 1.1 KV but not exceeding 11 KV grade of size not exceeding 400 sq.mm direct in the existing masonry open duct. complete as required |
| 84 | Supply of cable route marker 20 cms diameter of GI plate 6mm thick with inscription theron bolted or welded to 25mm x 25mmx 5mm angle iron 60 cms long and fixing the same in ground with PCC etc complete as required. For HT cable. |
| 85 | Supply of 3 1/2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(Part I) with latest amendments of following size.;3 1/2 Core 95 sq.mm |
| 86 | Supply of 3 1/2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(Part I) with latest amendments of following size.;3 1/2 Core 120 sq.mm |
| 87 | Supply of 3 1/2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(Part I) with latest amendments of following size.;31/2 Core 185 sq.mm |
| 88 | Supply of 3 1/2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(Part I) with latest amendments of following size.;3 1/2 Core 240 sq.mm |
| 89 | Supply of 4 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554 (Part I) IS:7098(Part I) with latest amendments of following size.;4 Core 10 sq.mm |
| 90 | Supply of 4 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554 (Part I) IS:7098(Part I) with latest amendments of following size.;4 Core 35 sq.mm |
| 91 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq. mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 92 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq. mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 93 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 120 sq.mm but not exceeding 400 sq. mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable)and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 94 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 400 sq. mm in the existing RC C/HUME/STONEWARE Metal pipe etc. complete as required |
| 95 | Supply and fixing of cable route marker 15 cms diameter of GI plate 6mm thick with inscription theron bolted or welded to 25mm x 25mmx 5mm angle iron 60 cms long and fixing the same in ground with PCC etc complete as required. |
| 96 | Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. |
| 97 | Supplying, erecting, testing & commisioning LT current transformer with barprimary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with testcertificat es. |
| 98 | Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB |
| 99 | Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected toCTs. |
| 100 | Supplying & erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc |
| 101 | Supplying & erecting LED type indicating pilot lamp with LED colour blue, 230/ 250 V on provided box / panel with necessary material, wiring & connections etc. |
| 102 | Supplying, installing, testing and commissioning air circuit breaker manual fixed type, non -drawout type, 650V, 630A, rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s), with s tandardaccessories with ready to close, individual fault trip, alarm and trip indications,mechanical and electrical anti pumping, soft/hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and t emperature rise protection & with 4 C/O contacts for On-Off- Trip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification no. SW-ACB |
| 103 | Supplying and erecting ON LOAD automatic transfer switch 4 pole, 415V, 400A, 50 Hz with enclosure, flexibility of neutral connection, line and load r eversibility,changeover with phase barriers, source separator, terminal covers along with staggered termination for cable connection and ATS controller with provision of time delay protection of OV, UV, phase sequence changing, single phasing and event logging, connected with provided leads complete complying to IS/IEC 60947-3 Part-1/6 as per specification no. SW-SWR/ATS. |
| 104 | Supplying, erecting & marking of surge arrestor/ surge protection device at thesub main distribution board after the incoming breaker of type 2 tested for Imax40 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD |
| 105 | Providing & erecting 3 Pole MCCB 415V, 630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no.SW-MCCB |
| 106 | Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36\ kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV /trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no.SW-MCCB NOTE: 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB- (TO NEW PANEL.) |
| 107 | Providing & erecting 3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV /trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no.SW-MCCB NOTE: 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB- TO EXISTING BLOCK DISTRIBUTION PANEL. |
| 108 | Providing & erecting 3 Pole MCCB, 415V, up to 100A, rated short-circuit b reaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW- MCCB. NOTE: 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB- TO EXISTING BLOCK DISTRIBUTION PANEL. |
| 109 | Supplying, erecting & marking FP MCB 40A to 63A, with rated short - circuitbreaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB |
| 110 | Supplying and erecting GI sheet 1.6 mm (16 SWG) having zinc coating of 350 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. |
| 111 | Supplying and erecting acrylic sheet 2 mm thick for covering wall entries including cutting, drilling and fixing with nut bolts / screws etc. complete |
| 112 | Supplying and erecting self-locking arrangement with keys in duplicate, made of brass of grade 1 compliance to IS 729-1979 duly erected, flush with surface of panel / cupboard |
| 113 | Supplying and erecting expanded metal jali enclosure made from GI square mesh 15 SWG having 20/25 mm squares, properly fixed/welded and duly painted with one coat of red oxide and two coats of silver/enamel paint complete. (size of jali or enclosure to be specified in the estimate.) |
| 114 | Supplying and erecting slotted angles, frames etc. for panel board or any other purposes complete with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority |
| 115 | Supplying, erecting, testing & commisioning bus bar chamber triple pole with neutral with four aluminium bars, 500V 800A having 100mm ( width) x 5 mm(thickness), with 99.9 % aluminium purity as per E91E grade & current density 0.8 A per sq mm compliance to IS 5082 and enclosure fabricated with 16SWG CRCA sheet and epoxy paint, with suitable number of ways and with SMC/DMC insulators and accessories of suitable rating and two nos of separateearthing terminals complete as per specification no. CP- BB |
| 116 | Supplying and erecting panel mounting type digital ammeter having three and half digit LED display, external CT operated, calibrated for suitable to operate on 500V, 0 to 1000A having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. |
| 117 | Supplying and erecting panel mounting type digital voltmeter having three and half digit LED display, calibrated for 0 to 750V AC suitable to operate on 500V having accuracy class of 0.5 ,AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer |
| 118 | Supplying and erecting selector switch suitable for voltmeter/ammeter for 3 phase AC supply 500V, 50Hz, on provided box / panel and duly connecting with necessary PVC wire leads and lugs. |
| 119 | Supplying and erecting 525 V 3 phase, 50 Hz., MPP type capacitor having minimum overcurrent capacity of 1.8 In, peak inrush current capacity 300 In and minimum life 150000 hours kVAr bank of metalised polypropylene condensers (MPP) with the standard capacities of 2, 3, 5, 7, 10, 12.5 and 15 kVArunits of P.F. correction for operation on 3 phase 50 Hz. with externally discharging resistances, earthing terminals and built on angle iron or channel iron frame work and provided with terminal cover box complete erected on provided iron bracket or on floor duly tested by licensee |
| 120 | Supplying, erecting, testing & commisioning 150kVAr, 440 V, 3 phase, 50 Hz.,APFC Panel with contactor logic with intelligent microprocessor relay, consisting of 2,3,5,5,10,10,15,20,30,50 or suitable steps of APP/MPP type capacitor units withdetuned (harmonic filter) reactors of suitable rating, APFCpanel shall be compliance to IEC 61439 and power quality IEC 61921 standard as per specification no. CP- ED/APFC. |
| 121 | Supplying and erecting switch disconnector fuse (SDF) switch 4 pole, 415V, 300-320A, open execution, AC23 A rated with terminal shrouds on both sides and phase barriers along with telescopic shaft for depth adjustments and door interlock and padlock complying to IS/IEC 60947-3 Part-1/3HRC - DIN type fuse, insulation voltage 1000 V for enclosing in panel with rotary handle for ON / OFF operation (without HRC fuse) as per specification no. SW-SWR/SDF. |
| 122 | Supplying and erecting switch disconnector fuse (SDF) switch 4 pole, 415V, 100A, open execution, AC23 A rated with terminal shrouds on both sides and phase barriersalong with telescopic shaft for depth adjustments and door interlock and padlock complying to IS/IEC 60947-3 Part-1/3 HRC-DIN type fuse, insulation voltage 1000 Vfor enclosing in panel with rotary handle for ON / OFF operation (without HRC fuse) as per specification no. SW-SWR/SDF. |
| 123 | Supplying and erecting switch disconnector fuse (SDF) switch 4 pole, 415V, 63A,open execution, AC23 A rated with terminal shrouds on both sides and phase barriersalong with telescopic shaft for depth adjustments and door interlock and padlock complying to IS/IEC 60947-3 Part-1/3 HRC-DIN type fuse, insulation voltage 1000Vfor enclosing in panel with rotary handle for ON/OFF operation (without HRC fuse) as per specification no. SW- SWR/SDF. |
| 124 | Supplying, erecting, testing & commisioning bus bar chamber triple pole with neutral with four aluminium bars, 500V, 100A having 15mm (width) X 3 mm (thickness), with 99.9 % aluminium purity as per E91E grade & current density 0.8 A per sq mm compliance to IS 5082 and enclosure fabricated with 16 SWG CRCA sheet and epoxy paint, with suitable number of ways and with SMC/DMC insulators and accessories of suitable rating and two nos of separate earthing terminals complete as per specification no. CP- BB |
| 125 | Supplying, erecting, testing & commisioning LT current transformer with barprimary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with testcertificat es. |
| 126 | Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB |
| 127 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB - TO CANTEEN BLOCK |
| 128 | Supplying and erecting GI sheet 1.6 mm (16 SWG) having zinc coating of 350 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. |
| 129 | Supplying and erecting acrylic sheet 2 mm thick for covering wall entries including cutting, drilling and fixing with nut bolts / screws etc. complete |
| 130 | Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. |
| 131 | Supplying and erecting self-locking arrangement with keys in duplicate, made of brass of grade 1 compliance to IS 729-1979 duly erected, flush with surface of panel / cupboard |
| 132 | Supplying and erecting slotted angles, frames etc. for panel board or any other purposes complete with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority |
| 133 | Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs. |
| 134 | Supplying and erecting selector switch suitable for voltmeter/ammeter for 3 phase AC supply 500V, 50Hz, on provided box / panel and duly connecting with necessary PVC wire leads and lugs. |
| 135 | Supplying & erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc |
| 136 | Supplying & erecting LED type indicating pilot lamp with LED colour blue, 230/ 250 V on provided box / panel with necessary material, wiring & connections etc. |
| 137 | Supplying, erecting & marking DP MCB 6 A to 32 A, B-series with rated short -circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 138 | Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 139 | Supplying, erecting & marking TP MCB 6A to 32A, with rated short - c ircuitbreaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB |
| 140 | Supplying and erecting four pole power contactor 430V, 40A for time switch complete erected on provided wooden block/ box, with necessary materials.Supplying and erecting four pole power contactor 430V, 40A for time switch complete erected on provided wooden block/ box, with necessary materials. |
| 141 | Supplying and erecting programmable digital almanac timer microcont rollerbased with real time clock to operate on derived switching “ON” and switching“OFF” street light as per daily sunset and sunrise respectively au tomaticallyhaving 4 digit LED continuous time display, relay output 230V / 10A with 10hrs. battery backup and manual over drive facility capable to drive differentcapacity contactors timer erected in provided M.S. box. |
| 142 | Supplying, erecting, testing and commissioning of diesel generating set with alternator of 250 kVA output continuous rating, 3 phase, 415 V, 50 Hz, 0.8 p.f., A.C. supply, a totally enclosed air cooled / liquid cooled multi-cylinderdiesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2/G3 and maximum fuel consumption 42.30 ltr /hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads, with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA sheet, sound absorbing material to restrict sound level... The extended description pertaining to this item is enclosed in Ann exure_RA-172797. |
| 143 | Supply, laying and termination of 7C X 2.5 SQMM CABLE FOR MAINS SUPPLY COMMAND in DG Set |
| 144 | Making M-20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq. m at 1.5m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m higho ctagonal/conica l GI pole). |
| 145 | Providing & erecting 6 m high (clear height) galvanised octagonal pole withfoundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provi dedfoundation as per specification no. OH-PL/OPL |
| 146 | Providing and erecting galvanised 1000mm single arm sword type bracket withFRP dome and ball as per specification no. OH-PL/BKT |
| 147 | Providing and erecting galvanised 1000mm double arm sword type bracketwith FRP dome and ball as per specification no. OH- PL/BKT |
| 148 | Supplying and erecting integrated LED street light fitting 70-75W IP65 & IK08class having single piece pressure die-cast aluminium housing, having systemlumens output of Min. 7700 Lumens, min. efficacy of 110 lumen/W, CRI>70,CCT upto 6500K,THD& lt;10%, p.f. >0.95, operating range of 140- 270V, inbuiltsurge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL. |
| 149 | Supply of 3 core armoured PVC/XLPE insulated PVC sheathed copper conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(PartI) with latest amendments of following size.;3 Core 4 sq.mm |
| 150 | Supply of 3 core unarmoured PVC/XLPE insulated PVC sheathed copper conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(Part I) with latest amendments of following size.;3 Core1.5 sq.mm |
| 151 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq. mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 152 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq. mm in the existing RCC /HUME/ STONEWARE Metalpipe etc. complete as required |
| 153 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with CI /RCC cover having locking/Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0mtrs(min) and disposal of excavated soil. c)Watering GI pipe 20mm Class B with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs (min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value.Aluminium tag with embossed earthing value to be attached to the pipe.g) watering arrangement(plumbing will be paid seperately). (a) In soily strata |
| 154 | Extra for using salt and charcoal for GI or copper plate earth electrode as required( 96 Kgs of Charcoal and 5 Kgs of Salt) |
| 155 | Providing and fixing 6 SWG dia GI wire on surface or in recess for loop arthing . as required |
| 156 | Supplying and making cable end terminations with brass compression gland and copper lugs for folowing sizes of 3 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(2) 3 x 4 Sq. mm. |
| 157 | Supplying and laying (including excavation of suitable width & depth up to 90cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPEfor enclosing cable below ground/road surface, complete. |
| 158 | Supply, installation, testing and commissioning of main fire pump (MFP / EP) suitable for water discharge of 2280 LPM at 70 meter head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply, 50-60 HP or of suitable HP capacity for ma nual/automatic operation and consisting of following: (a)Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plas...The extended description pertaining to this item is enclosed in Ann exure_MR-171100 |
| 159 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 LPM at 70 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply, 5- 8 HP or of suitable HP capacity for manual/automatic operation and consisting of following: (a) Horizontal/vert ical type, multi stage,centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic...The extended description pertaining to this item is enclosed in Ann exure_MR-171102. |
| 160 | Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 LPM at 70 m head driven by 50-60 HP or suitable HP capacity diesel engine at required working speed suitable for manual/automatic operation and consisting of following:(a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal to ensure a minimum pressure of 3.5 kg/sq. cm at highest and farthest outlet at specified flow of 2280 LPM at 70 m head conforming to IS 1520.(b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150 ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine, exhaust pipe exte...The extended description pertaining to this item is enclosed in Ann exure_MR-171103 |
| 161 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalized with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pre ssurization) pumps & Diesel pump with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac... The extended description pertaining to this item is enclosed in Ann exure_MR-171104 |
| 162 | Supply, Installation Testing Commissioning of Air Vessel of 300 mm Ø1.5m in height M.S. tank installed inside pump house |
| 163 | Supplying and fixing priming tank HDPE 1000 litres capacity along with required piping and valves |
| 164 | Supply, Installation Testing and Commissioning of pressure gauge of 100 mm Ø., 0- 300 PSI or 0-14 kg per cm square fitted with 12/15 mm Ø. pad cock valve, andG.I. pipe, elbow etc. |
| 165 | Supply,Installation Testing Commissioning of pressure switch with 12/15 mm Ø isolation valve, G.I. nipple, elbow etc. |
| 166 | Supply, Installation, Testing and commissioning of gun- metal ball valve 25 mm dia |
| 167 | Supply, Installation, Testing and commissioning of gun- metal Air release valve 25 mm dia |
| 168 | Supply, Installation, Testing and Commissioning of C.I foot valve, flanged end including rubber gasket, nuts bolts and washers. 150 mm |
| 169 | Supply, Installation, Testing and Commissioning of C.I foot valve, flanged end including rubber gasket, nuts bolts and washers. 80 mm |
| 170 | Supply, Installation Testing and Commissioning of following size cast iron double flange Butterfly Valve with matching flange, nut bolts & gasket. 150 mm |
| 171 | Supply, Installation Testing and Commissioning of following size cast iron double flange Butterfly Valve with matching flange, nut bolts & gasket. 100 mm |
| 172 | Supply, Installation Testing and Commissioning of following size cast iron double flange Butterfly Valve with matching flange, nut bolts & gasket. 80 mm |
| 173 | Supply, Installation Testing and Commissioning of following size cast iron double flange Non Return Valve with matching flange, nut bolts & gasket. 150 mm |
| 174 | Supply, Installation Testing and Commissioning of following size cast iron double flange Non Return Valve with matching flange, nut bolts & gasket. 100 mm |
| 175 | Supply, Installation, Testing and commissioning of gun- metal fire brigade connection (suction collecting head / Four Way) consisting of 4 Nos. 63 mm dia instntaneous type male couplings with built-in check valves, and 150 mm dia. |
| 176 | Supply and Installation Testing Commissioning of gun metal / Stainless Steel Single outlet hydrant valve fitted matching flange, nut bolts & gasket |
| 177 | Supply, Installation of Hose box made of 18 gauge MS sheet 800mm x 600mm x 250mm with double door with 4mm thick glasses and housing for hose pipe, and branch pipe. and having front doors with viewing glass (8'x6'') and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour. and Rates include for suitable size iro brackets and anchor bolts.' |
| 178 | Supply and Installation, Testing and Commissioing of Gun Metal Short Branch Pipe with 20 mm dia nozzle. |
| 179 | Supply, Installation, Testing and Commissioning of 63 mm dia RRL Hose 15 mtr length with ISI marked brass male & female coupling (IS:903) bound & rivetted to hose pipe with copper rivets complete |
| 180 | Supply, Installation & Testing of First aid Hose reel conforming to IS 884 completes with 19 mm dia bore reinforced braided rubber hose of 30 mtrs length fitted with 6.35mm dia shut off Nozzle, 25 mm dia ball valve etc. The hose reel shall be manual 180 deg. swining type with reel drum hose shall be provided with coupling. |
| 181 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 200 mm |
| 182 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 150 mm |
| 183 | Supply, fabrication, erection, testing, and commissioning of 150 mm diameter size of GI ERW C class pipe (conforming to IS-1239) laying under ground (including pipe trench excavation and refilling) with all fittings (Standard MS fittings with welded joint shall be used on the pipes) including Tees, elbows, reducers, unions, flanges, rubber gaskets, GI nut s/bolts/washers/tie-bolt supports, and clamps with coating of bitumen paint and 4 mm thick wrapping as per specification no. FF-PP. |
| 184 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 100 mm |
| 185 | Supply, fabrication, erection, testing, and commissioning of 100 mm diameter size of GI ERW C class pipe (conforming to IS-1239) laying under ground (including pipe trench excavation and refilling) with all fittings (Standard MS fittings with welded joint shall be used on the pipes) including Tees, elbows, reducers, unions, flanges, rubber gaskets, GI nut s/bolts/washers/tie-bolt supports, and clamps with coating of bitumen paint and 4 mm thick wrapping as per specification no. FF-PP. |
| 186 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 80 mm |
| 187 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 50 mm |
| 188 | Supply, Fabrication, Erection, Testing and commissioning of following sizes of G.I. ERW C class pipes (conforming to IS -1239), Erection on Above Ground (including proper iron supports and anchor fastners) and Laying with all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts . Washer, tie bolt supports and clamps etc with one coat of redoxide primer and one coats of synthetic enamel paint. 25 mm |
| 189 | Supply, Installation, Testing & Commissioning of 2 Zone Micro processer based Fire Alarm Control panel with battery charger, 48 hours battery back-up and related accessories |
| 190 | Supply, Installation, Testing & Commissioning of 4 Zone Micro processer based Fire Alarm Control panel with battery charger, 48 hours battery back-up and related accessories |
| 191 | Supplying, installing, testing and commissioning of Conventional Smoke detector with base |
| 192 | Supply, installation, Testing and commissioning of conventional Multi-sensor fire detector (combining smoke & heat sensing) with base along with necessary accessories complete. |
| 193 | Supplying, installing, testing and commissioning of Conventional Manual Call Point with back box. |
| 194 | Supplying, installing, testing and commissioning of Conventional Sounder with strobe light |
| 195 | Supply of 2 core armoured PVC/XLPE insulated PVC sheathed copper conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(PartI) with latest amendments of following size.;2 Core1.5 sq.mm |
| 196 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq. mm on surface etc. complete as required |
| 197 | Supplying and erecting ABC powder fire extinguisher as per IS : 13849 of 4 kg capacity with necessary clamp for erection on wall. |
| 198 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg.Capacity, conforming to IS 2878 Complete with, necessary clamp made front 50mm x 6mm. M.S. flat with nut & bolts grouted in wall complete |
| 199 | Supplying and erecting Clean Agent (HFC236FA TYPE) gas fire extinguisher of 4 kg capacity conforming to IS standards complete with necessary clamps for erection on wall. Fire extinguisher made up of Mild Steel & duly hot phosphate & powder coated external as Well as Internal the fire Extinguishers is hydrotested at 30kg/cm^2. |
| 200 | Supply and erection of K- Type kitchen fire extinguisher of 4 Kg capacity with necessary clamps for erection on wall. Conforming to IS 15683:2006. |
| 201 | Supplying and erecting Clean Agent 5Kg capacity Modular Type fire extinguisher as per IS : 15683 with necessary clamp for erection on wall. |
| 202 | Supply installation, testing & commissioning of Tubing Based Suppression System, Cylinder as per IS: 15683 With DLP Valve, Pressure Gauge, filled with 4 Kg of Clean Agent with End Fittings, Low pressure Switch & Cylinder Bracket. The system should have Linear fire Detection Tube, 6 mm OD, 4mm ID, 20mt long, along with System Pressure Health Monitoring Panel, 1 Zone indication with Hooter |
| 203 | Supplying , installation, Testing and commissioning of the 4 manifold LPG bank with all accessories Manifold with stand for 4 Cyilinder. Qty. 2 Nos Rubber hose pipe steel wire brided Standerd IS 9573 Qty. 8 Nos.Standerd LPG regulator with fittings Qty. 4 nos. LPG Pressure Regulator Qty. 1 Nos LPG Pressure gauge Qty. 2 Nos 15 mm GI/MS C class pipe Heavy with fittings, supports and clamp including painting Qty. 36 mtr |
| 204 | Supply, Installation, testing and Commissioning of Gas Detection System.1. FGGAS-GDS-000010 - GDS-24-2 Gas Detection System ( 1 Panel)2. FGGAS -CLR-000016 - TS21I-CLR-EX: Commercial LPG/PNG Gas Detector without PPMwith explosion proof housing, PESO Certified.(2 Gas Detector)3. T1IMTROTHR000005 - FireSounderwith Strobe Light - 24V/105 db 4. 2 c x 1.5 Sqmm and 4c x 1.25 Sqmm cable |
| 205 | Construction of LPG Bank room Size: 3M Length X 3M Width X 3 M Height With Roof Sheet.Including Excavation, Rubble packing , PCC, Concerete, Refilling (3Mx3Mx100 mm)RCC Fondation 300x300x300mm Qty. 5 nosIron structure vertical. 50x50x3.2 mm Squre tube. 36mtr. Horizontal 25x25x2mm Squre tube 48 mtr Basplate 300x300x10mm. Qty 5 Nos. Roofing Sheet, 16Sqmtr. Door. 2mtr Heightx1 mtr Width. Qty. 1 Nos. G I Mesh 3mm thick 25x25 mm spacing, Qty. 36 Sqmtr |
| 206 | Core Cutting For Pipe fixing 100 mm dia |
| 207 | Filling core cut gap with Concrete sealant. |
| 208 | Supply and Installation of Emergency Exit Light Wall Mounted with Rechargeable Battery Backup- Size :100X300 mm |
| 209 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. FIRE EXTINGUISHER (Size- 200 x 250 mm). |
| 210 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. HOSE REEL HOSE (Size- 200 x 250 mm). |
| 211 | Supply & installing of Photo luminescent, nontoxic, non-r adioactive,maintenance free, self-glowing \\"Emergency Exit Signages\\" job complete with required coatin gs/accessories for installation on walls. ASSEMBLY POINT(Size- 600 x 600 mm) |
| 212 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005.FIRE ALARM (Size- 200x 250 mm). |
| 213 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. STAIRCASE IDENTIFICATION (Size- 100 x 300 mm). |
| 214 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Signages will be Blue with Graphic symbol in WHITE colour as per IS 9457:2005. Lift (Size- 200 x 200 mm). |
| 215 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Signages will be Blue with Graphic symbol in WHITE colour as per IS 9457:2005. Ramp (Size- 200 x 200 mm). |
| 216 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Signages will be Blue with Graphic symbol in WHITE colour as per IS 9457:2005.Parking (Size- 200 x 200 mm) |
| 217 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. UP & DOWN ARROWS (Size- 100 x 300 mm). |
| 218 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005 FIRE PANEL (Size- 100 x 300 mm). |
| 219 | Photo luminescent non toxic, non radioactive, maintenance free self glowing signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminescent aluminum sheet 1.0 mm thick containing luminescent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects. i) PERSON WITH DISABILITY |
| 220 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. EXIT (Size- 100 x 300mm). |
| 221 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005. NO SMOKING (Size- 100 x 300 mm). |
| 222 | Photo luminescent non toxic, non radioactive, maintenance free self glowing exit signs comprising zinc sulphide chargeable crystals which can glow in dark; printed on U-1000 photo luminiscent aluminium sheet 1.0 mm thick containing luminiscent 111 as base chemical cover with UV stabilized coating job complete with SS screws for wall mounting or to be hanged on rust proof chain for ceiling mounting complete in all respects, plate size 12\\" X 18\\" (general size, may increase or decrease depending on site requirements). The colour of the Directional and Fire Safety signages shall be RED with Graphic symbol in White colour and the colour of the Emergency escape signages shall be Green with Graphic symbol in WHITE colour as per IS 9457:2005.DANGER (Size- 200 x 250mm). |
| 223 | Supply and fixing of Photo luminescent Emergency escape plan (Size A3) of each building and floor signages with necessary accessories complete as per IS 9457:2005. Rates should be including marking of all the points of Arrows and signages on the plan by using AutoCAD, complete. |
| 224 | Supply of 3 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554 (Part I) IS:7098(Part I) with latest amendments of following size.;3 Core 16 sq.mm |
| 225 | 12 core x1.5 sqmm Copper cable for Diesel Engine pump |
| 226 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(5) 3 x 16 Sq. mm. |
| 227 | Supply of 3 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554 (Part I) IS:7098(Part I) with latest amendments of following size.;3 Core 70 sq.mm |
| 228 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(9) 3 x 70 Sq. mm. |
| 229 | Supply of 3 1/2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554(Part I) IS:7098(PartI) with latest amendments of following size.;3 1/2 Core 120 sq.mm |
| 230 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(6) 3 1/2 x 120 Sq. mm. |
| 231 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq. mm in the existing masonry open duct etc. complete as required |
| 232 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq. mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharges and cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 233 | Supplying installation testing and commissioning of surface/ recess mounting vertical type 415 V TPN double door MCB DB of sheet steel dust protected duly phosphatised and powder painted inclusive of 200 A tinned copper busbar common neutral link earth bar din bar for mounting MCBs detachable gland knock out plate and with 100 A 10 KA MCCB as incomer interconnection between incomer MCCB and busbars of following ways (but without MCCB/MCBs as required);(a) 6 way with 100A MCCB as Incomer double door Cat B |
| 234 | Providing and fixing following rating and breaking capacity adjustible 4 pole MCCB inside the existing cubicle panel board including drilling holes in cubicle panel making connections etc as required;(d) 200 A Adjustable 35/40 KA CAT B |
| 235 | Supplying and Installing following size perforated type 16 SWG M.S.cable tray of GI pregalvan ised/hot dip galvanised/ powder coated finish in convenient sections joined with connectors suspended from the ceiling with suitable MS suspenders including bolts and nuts painting suspenders etc complete as required.; 150mm width x 50mm depth |
| 236 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with CI/RCC cover having locking /Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil.c)Watering GI pipe 20mm Class B with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs (min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe.g) watering arrangement(pl umbing will be paid seperately).;(a) In soily strata |
| 237 | Supplying and laying 25 mm x 5 mm GI strip at 0.5 m below ground as strip earth electrode including soldering etc. as required |
| 238 | Extra for using salt and charcoal for GI or copper plate earth electrode as required( 96 Kgs of Charcoal and 5 Kgs of Salt) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender