Tender For Upgradation Of Firefighting System At Bdc & Testing Centre As Per Latest Nbc Guideline Including Comprehensive Operation & Maintenance For A Period Of Three (3) Years After The Expiry Of Guarantee Period Of One Year
Tender Overview
Project Description
Tender for Upgradation Of Firefighting System At Bdc & Testing Centre As Per Latest Nbc Guideline Including Comprehensive Operation & Maintenance For A Period Of Three (3) Years After The Expiry Of Guarantee Period Of One Year
BOQ
| Sl. No. | Item Description |
| 1 | SITC of Fire Double Hydrant 4\\" 150# Flanged |
| 2 | SITC of Two-Way Inlet Breeching 6\\" 150# Flanged Type |
| 3 | SITC of Four-Way Inlet Breeching 6\\" 150# Flanged Type |
| 4 | SITC of Fire RRL Hose Pipe 2 x 15 MTR (White) with connector |
| 5 | SITC of Automatic Fire Hose Reel with Retractable Drum, 20 mm Connection |
| 6 | SITC of Butter fly Valve - 6\\" wafer type |
| 7 | SITC of Butter fly Valve - 4\\" wafer type |
| 8 | SITC of Butter fly Valve - 2\\" wafer type |
| 9 | SITC of Non-Return Valve - 6\\" x 150# |
| 10 | SITC of Ball valve 1/2\\" Female connection (PG) |
| 11 | SITC of Ball valve 1\\" Female connection (Air vent) |
| 12 | SITC of 20mm Ball valve Female connections (Hose reel) |
| 13 | SITC of Control Valve with Indicator 4” |
| 14 | SITC of Test valve 1” |
| 15 | SITC of strainer 6\\" 150# flanged connections |
| 16 | SITC of Fire Extinguisher (6Kg ABC Type) |
| 17 | SITC of Fire Extinguisher (6Kg CO2 Type) |
| 18 | SITC of smoke detector |
| 19 | SITC of Manual call point with hooter |
| 20 | SITC of Sprinkler |
| 21 | SITC of Heat detector |
| 22 | SITC of Fire Strobe |
| 23 | SITC of Fire Buckets |
| 24 | SITC of 6\\" SCH 40 Pipe-MS |
| 25 | SITC of 4\\" SCH STD Pipe |
| 26 | SITC of 2\\" SCH 80 Pipe |
| 27 | SITC of 1\\" SCH STD Pipe |
| 28 | SITC of Booster Pump |
| 29 | SITC of Pressure Switches |
| 30 | SITC of SS Pressure gauge 1/2\\" Male along with matching coupling |
| 31 | SITC of Air Vent 1\\" Male |
| 32 | SITC of Doors assembly for staircase hydrant |
| 33 | SITC of Control panel box for Terrace Pump with cables and cable trays |
| 34 | SITC of Level Gauges for Tanks |
| 35 | SITC of Ladders for tanks |
| 36 | SITC of FCC and other wings |
| 37 | SITC of Air vessel for Booster Pump |
| 38 | SITC of 2C X 1.5 Sq mm FRLS Armoured Cable |
| 39 | SITC of Flexible Hose fixing accessories for protection of cables |
| 40 | SITC of Rossete Plate:suitable for sprinkler/drop pipe penetrations, sized to suit pipe diameter, providing a neat finished appearance at ceiling/wall openings, complete with fixing accessories, conforming to NBC 2016 Part 4 |
| 41 | SITC of MS Hose Box |
| 42 | SITC of Four-Way Inlet Breeching 6\\" 150# Flanged Type |
| 43 | SITC of Four-Way outlet Breeching 6\\" 150# Flanged Type |
| 44 | SITC of Gate valve 4\\" x 150#: Suitable for Fire water applications |
| 45 | SITC of Gate valve 8\\" x 150# Suitable for Fire water applications |
| 46 | SITC of Non return valve 8\\" x 150# Suitable for Fire water applications |
| 47 | SITC of Non-Return Valve - 6\\" x 150# Suitable for Fire water applications |
| 48 | SITC of 3/4\\" 800# Ball valve THREADED (PG & PT): Suitable for Fire water applications |
| 49 | SITC of strainer 4\\" 150# flanged connections]: Suitable for Fire water applications |
| 50 | SITC of strainer 8\\" 150# flanged connections: Suitable for Fire water applications |
| 51 | SITC of Fire Extinguisher (6Kg CO2 Type) |
| 52 | SITC of 2\\" SCH 80 MS Pipe |
| 53 | SITC of 4\\" SCH STD MS Pipe |
| 54 | SITC of 6\\" SCH STD MS Pipe |
| 55 | SITC of 8\\" SCH STD MS Pipe |
| 56 | SITC of 3/4\\" SCH 80 MS Pipe |
| 57 | Design, supply, erection testing and commissioning of Electric Motor Driven Jockey pump of Capacity 180 LPM, Vertical multistage type, Head approximately 60 m, Automatic pressure maintenance, Complete with pressure switch and accessories |
| 58 | Design, supply, erection and testing of main Electric motor driven Fire Pump of 2280 LPM Capacity of Horizontal centrifugal split case/end suction type, Duty as per hydraulic calculation, Head approximately 60 m, Continuous duty, Mechanical seal, dynamically balanced impeller and complete in all respects |
| 59 | Design, supply, erection and testing of main Electric motor driven Fire Pump of 1620 LPM Capacity of Horizontal centrifugal split case/end suction type, Duty as per hydraulic calculation, Head approximately 40 m, Continuous duty, Mechanical seal, dynamically balanced impeller and complete in all respects |
| 60 | Design, supply, erection and testing of Diesel Engine driven pump of 2280 LPM Capacity, Horizontal centrifugal, Head approximately 60 m , Automatic starting, diesel tank with supporting, flexible coupling, safety guard flanges and control panels, battery & battery banks chargers, cables, fittings, etc. external cooling arrangements, and complete in all respects. |
| 61 | Design, supply, erection and testing of Diesel Engine driven pump of 1620 LPM Capacity, Horizontal centrifugal, Head approximately 40 m, Automatic starting, diesel tank with supporting, flexible coupling, safety guard flanges and control panels, battery & battery banks chargers, cables, fittings, etc. external cooling arrangements, and complete in all respects. |
| 62 | SITC of PG for Pump LineType: Bourdon Tube Pressure Gauge Connection Size: 1/2\\" Male (Bottom Entry) Connection Type: BSP or NPT (to match existing system) Case Material: SS 304, Wetted Parts: SS 316 Dial Size: 100 mm (4\\") minimum Pressure Range: 0–16 Bar (or as required by the system) Accuracy: ±1.6% F.S. or better Filling: Glycerine Filled, Window: Toughened Glass / Polycarbonate Protection: IP65 minimum, Operating Temperature: -20°C to +60°C Mounting: Direct Bottom MountWith all accessories |
| 63 | SITC of Main Incomer Panel from Main Grid to Pump Station200A MCCB with individual outgoing MCCB for protection + PT/DPT Cables, cable trays etcAdd 2 x 200A MCCB for 2 Outgoing cables with RYB Indicators, Voltmeter, VMR, EtcWith all accessories |
| 64 | SITC of EarthingCu-Bonded Earthing 1.5m LG x 14mm – 3 No.s. With Chemical Filling & Installation at MangaloreWith all accessories |
| 65 | SITC of Main Incomer Panel (With Busbar & 2 x MCCB) Main Incomer Panel Modification at Site Add 2 x 200A MCCB for 2 Outgoing cables with RYB Indicators, Voltmeter, VMR, EtcWith all accessories |
| 66 | SITC of 150sqmm2 Aluminium 3.5C XLPE Insulated Cable from Main Incomer to BDC & TC Pumpstations(250Mtr)Polycab 150 Sq.mm 3.5 Core Aluminium Conductor Armoured LT Refer Terms -- Site 1-175m; Site 2-75m.With all accessories |
| 67 | Earth Work excavation for foundation up to a depth of 1.5 metres with initial lift and lead of excavated soil to a distance less than 50 feet |
| 68 | Providing Mixing & laying P.C.C.bed in C.C.1:4:8 mix using approved quality of 40mm (1.5\\") & downgraded stone ballast (jelly)sand and cement including required centring frame work, with lift and lead charges consolidation and curing to the required period etc. |
| 69 | Providing & Laying R.C.C works using approved quality of 20mm & downgraded stone ballast (jelly) sand and cement required cantering, form work, scaffolding, Bartending, lead & lift charges consolidation and curing to the required period etc. complete. i. R.C.C M25 Grade Concrete-Footing: |
| 70 | ii. R.C.C M25 Grade Concrete Pedestal Column |
| 71 | iii. R.C.C M25 Grade Concrete Plinth Beam |
| 72 | Providing, cutting, bending and placing TMT reinforcement steel bars of approved make and grade, for foundation works including footings, pedestals and grade beams, as per structural drawings and bar bending schedule (BBS). |
| 73 | Providing & Constructing laterite stone masonry in C.M.1:6 Mix with approved quality of laterite stones to the required sizes, including necessary scaffolding, lead & lift charges, curing to the required period etc. complete. |
| 74 | Earth Filling with available (excavated) soil from within 50 feet for basement, including watering, mixing consolidation, levelling etc. complete. |
| 75 | Providing & Constructing laterite stone masonry in C.M.1:6 Mix with approved quality of laterite stones to the required sizes, including necessary scaffolding, lead & lift charges, curing to the required period etc. complete. |
| 76 | Providing & Constructing Hollow/Solid block masonry in C.M.1:6 Mix with approved quality of concrete blocks to the required sizes including scaffolding lead & lift charges curing to the required period etc. complete. |
| 77 | Providing & Laying R.C.C works using approved quality of 20mm & downgraded stone ballast (jelly) sand and cement required centering, form work, scaffolding, Bartending, lead & lift charges consolidation and curing to the required period etc. complete. R.C.C M25 Grade Concrete Column |
| 78 | R.C.C M25 Grade Concrete Lintel |
| 79 | R.C.C M25 Grade Concrete Beams |
| 80 | R.C.C M25 Pump Foundation: |
| 81 | R.C.C M25 Grade Concrete Shade Rack |
| 82 | R.C.C M25 Grade Concrete 5\\" Thick Slab: |
| 83 | Providing, cutting, bending and placing TMT reinforcement steel bars of approved make and grade, for foundation works including footings, pedestals and grade beams, as per structural drawings and bar bending schedule (BBS). |
| 84 | Providing & Fixing Windows as per client requirement with complete |
| 85 | Providing & Fixing Doors as per client requirement with complete |
| 86 | Providing & Making wall and ceiling plastering with C.M.1:4 mix to a thickness of ½\\" to ¾\\" to get perfect plumb finish with necessary scaffoldings, curing to the required period etc. complete |
| 87 | Providing and laying Cement concrete flooring 40 mm thick with 20 mm nominal size stone aggregate using 1:2:4(1 cement: 2 coarse sands :4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry complete. |
| 88 | Providing and carrying out painting works including surface preparation, cleaning, putty, primer and minimum two coats of approved paint for walls, steel and other surfaces complete with all labour, materials, scaffolding, tools and finishing. Also providing complete electrification works including supply and laying of wiring in PVC conduit, switch boxes, modular switches, light and power points, distribution board, MCBs, earthing, cable termination, testing and commissioning, including all materials, labour and accessories required for complete installation. |
| 89 | Providing complete electrification works including supply and laying of FRLS copper wiring in PVC conduit, installation of modular switches, switch boxes, light points, fan points, power sockets, distribution board with MCB/RCCB, earthing, cable laying, termination, testing and commissioning, including all materials, labour, tools and accessories required for complete and proper functioning of the electrical system. |
| 90 | Earth Work excavation for foundation up to a depth of 1.5 metres with initial lift and lead of excavated soil to a distance less than 50 feet. |
| 91 | Providing Mixing & laying P.C.C.bed in C.C.1:4:8 mix using approved quality of 40mm (1.5\\") & downgraded stone ballast (jelly)sand and cement including required centring frame work, with lift and lead charges consolidation and curing to the required period etc. |
| 92 | Providing & Laying R.C.C works using approved quality of 20mm & downgraded stone ballast (jelly) sand and cement required centering, form work, scaffolding, Bartending, lead & lift charges consolidation and curing to the required period etc. complete.i. R.C.C 1:2:4 Footing |
| 93 | ii. R.C.C 1:2:4 Pedestal Column |
| 94 | iii. R.C.C 1:2:4 Plinth Beam |
| 95 | Providing, cutting, bending and placing TMT reinforcement steel bars of approved make and grade, for foundation works including footings, pedestals and grade beams, as per structural drawings and bar bending schedule (BBS). |
| 96 | Providing & Constructing laterite stone masonry in C.M.1:6 Mix with approved quality of laterite stones to the required sizes, including necessary scaffolding, lead & lift charges, curing to the required period etc. complete. |
| 97 | Earth Filling with available (excavated) soil from within 50 feet for basement, including watering, mixing consolidation, levelling etc. complete. |
| 98 | Providing & Constructing laterite stone masonry in C.M.1:6 Mix with approved quality of laterite stones to the required sizes, including necessary scaffolding, lead & lift charges, curing to the required period etc. complete. |
| 99 | Providing & Consturcting Hollow/Solid block masonry in C.M.1:6 Mix with approved quality of concrete blocks to the required sizes inculding scaffolding lead & lift charges curing to the required period etc. complete. |
| 100 | Providing & Laying R.C.C works using approved quality of 20mm & down graded stone ballast (jelly) sand and cement required centering, form work, scaffolding , Bardending,lead & lift chargesconsolidation and curing to the required period etc. complete.i. R.C.C 1:2:4 Column |
| 101 | ii. R.C.C 1:2:4 Lintel |
| 102 | iii. R.C.C 1:2:4 Beams |
| 103 | iv. R.C.C M20 Pump Foundation: |
| 104 | R.C.C 1:2:4 Shade Rack |
| 105 | R.C.C 1:2:4 5\\" Thick Slab |
| 106 | Providing, cutting, bending and placing TMT reinforcement steel bars of approved make and grade, for foundation works including footings, pedestals and grade beams, as per structural drawings and bar bending schedule (BBS). |
| 107 | Providing & Fixing Windows as per client requirement with complete |
| 108 | Providing & Fixing Doors as per client requirement with complete |
| 109 | Providing & Making wall and ceiling plastering with C.M.1:4 mix to a thickness of ½\\" to ¾\\" to get perfect plumb finish with necessary scaffoldings, curing to the required period etc. complete |
| 110 | Providing and laying Cement concrete flooring 40 mm thick with 20 mm nominal size stone aggregate using 1:2:4(1 cement: 2 coarse sand :4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry complete. |
| 111 | Providing and carrying out painting works including surface preparation, cleaning, putty, primer and minimum two coats of approved paint for walls, steel and other surfaces complete with all labour, materials, scaffolding, tools and finishing. Also providing complete electrification works including supply and laying of wiring in PVC conduit, switch boxes, modular switches, light and power points, distribution board, MCBs, earthing, cable termination, testing and commissioning, including all materials, labour and accessories required for complete installation. |
| 112 | Providing complete electrification works including supply and laying of FRLS copper wiring in PVC conduit, installation of modular switches, switch boxes, light points, fan points, power sockets, distribution board with MCB/RCCB, earthing, cable laying, termination, testing and commissioning, including all materials, labour, tools and accessories required for complete and proper functioning of the electrical system. |
| 113 | Monthly Charges towards Comprehensive Operation & Maintenance after the expiry of guarantee period of one year. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender