Tender For Electrical Work At Ghss Ratnipora Under Pmkkky
Tender Value
5 Lakhs
Estimated cost
Bid Submission
05 Aug 2026
5 days left
EMD
10002
Bank guarantee accepted
Document Fee
200
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pulwama → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Electrical Work At Ghss Ratnipora Under Pmkkky
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havell lifeguard/Polycab green/ Finolex/ Apar/ RR/eq. standard make as desired by engineer incharge ) single core cable in surface / recessed medium class PVC conduit, with modular switch ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.), modular plate,suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor ( Havell/ Apar/ Polycab/SSK/ Anchor/equivalent as directed by engineer incharge.) single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm + 1X 4 sq. mm earth wire , FRLS PVC insulated copper conductor ( Havell lifeguard/Polycab green/ Finolex/ RR/ Apar/ eq. standard make as desired by engineer incharge ) single core cable in surface/recessed medium class PVC conduit. |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,modular plate, suitable GI box , connections etc. as required. Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Leiva /ABB Tvisha make make.) |
| 5 | Wiring for lighting circuits/ 6- 10 amp power plugwith 2X2.5 sq. mm FRLS PVC insulated copper conductor( Havell lifeguard/Polycab green/ Finolex/ Apar/ RR/eq. standard make as desired by engineer incharge ) single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.) |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor ( Havell lifeguard/Polycab green/ Apar/ Finolex/ RR/eq. standard make as desired by engineer incharge ), single core cable in surface/ recessed medium class PVC conduit as required. |
| 8 | ( b )2 X 16 sq. mm + 1 X 6 sq. mm earth wire |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, with cement plaster, wall putty , paint, complete |
| 10 | Providing and fixing of 6-16mm Cu thimbles duly cramped at cable ends. |
| 11 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 12 | Supply installation testing and commissioning of Indicator of Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /Crabtree athena make.) |
| 13 | Sub Head-2 - Fixtures and Fittings |
| 14 | Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Housing and Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Helonix/Havell/ Wipro make / sample to be approved before installation.. |
| 15 | S/F testing and comm. Of 20 W + 4 ft. wall mounted LED batten with powdered coated aluminum housing & integrated electronic driver with minimum system lumen efficacy of 100 lm/W with THD<10%.( commercial series) CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips/ Trulux /Wipro make / sample to be approved before installation.. |
| 16 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 No. Aluminium blades, 30 cm long down rod, 2nos. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, and including iron hook complete . USHA /orient/Crompton make (Project series, sample to be approved before installation) |
| 17 | Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate Anchor roma plus/Legrand Mylinc /ABB Tivsha/schneider Livia /Havell Coral make. |
| 18 | Supply installation testing and comm. Of 200-250mm sweep exhaust fan Shutter type of havell /Bajaj/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections. |
| 19 | Supplying and fixing following way, Triple pole and neutral, sheet steel, MCB distribution board,( Havell/ legrand/ Shinider/SSK make) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) |
| 20 | 6 way, Double door |
| 21 | S/F testing and comm. Of MCB's 10 K of the below mentioned capacities in sub main controls legrand C curve/ Schinider/ ABB ./equivalent make as directed by engineer incharge. |
| 22 | a) 6-32 Amp SP MCB |
| 23 | b) 40-63amp DP MCB |
| 24 | Providing of Chemical earthing as per IS standards by way of digging 10' deep pit then embedding 3 meter G.I Earthing electrode , 80mm dia. connecting the plate with main control board by8- 10 SWG G.I wire with 1/2\\" dia. Full thread brass nut and bolt and washers. Refilling of pit with chemical compound. |
| 25 | S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size. |
| 26 | c)35 sq.mm 2 core |
| 27 | Supply installation testing and comm. of flood light 50 W ( warm, white ), Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ Havell ( JETA QUANTO PLUS MONO 50 W) /Wipro/Crompton make. the job also includes the angle iron stand of suitable size to be grouted in cement concrete with hold fasteners complete job. |
| 28 | Design, Fabrication, Supplying, Installation, Testing and Commissioning of following panel, duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required.( As per approved design,size may vary as per site requirement) |
| 29 | Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required. |
| 30 | Normal INCOMING: |
| 31 | a)125A 2P MCCB 25 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make. |
| 32 | b) 2 No. of Aluminium Bus Bar of 200 Amp. |
| 33 | c)Digital meters and phase indicators -1 set. |
| 34 | OUTGOING: |
| 35 | c) 40-63amp DP MCB |
| 36 | c) space for 12 way MCB's Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 21, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysAug 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender