Tender For Development Of Sports Complex At Sector 23 Dwarka.Sub Head: Supply Installation Testing and Commissioning of Internal Electrical Installation In Fire Plant Room,Stp, Light Around Admin Building, Spectator Stand Etc. At Sector-23, Dwarka.
Tender Overview
Project Description
Tender for Development Of Sports Complex At Sector 23 Dwarka.Sub Head: Supply Installation Testing and Commissioning of Internal Electrical Installation In Fire Plant Room,Stp, Light Around Admin Building, Spectator Stand Etc. At Sector-23, Dwarka.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group C |
| 2 | Wiring for light/ power plug with 2X4 sq.mm FRLS/HFFR PVC insulated copper conductor singlecore cable in surface/ recessed steel conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for light/ power plug with 4X4 sq. mm FRLS/HFFR PVC insulated copper conductor singlecore cable in surface/ recessed steel conduit along with 2 Nos. 4 sq.mm FRLS/HFFR PVC insulatedcopper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 8 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 9 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 10 | 1 or 2 Module (75mmX75mm) |
| 11 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plateswitch box including connections but excluding modular plate etc. as required. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connectionsetc. as required. |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,connections etc. as required. |
| 14 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block includingconnections etc. as required. |
| 15 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator). |
| 16 | 4 way (4 + 12), Double door |
| 17 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 18 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 19 | 100 A, 16 KA,TPMCCB |
| 20 | Supplying and fixing 40 A rating, 240/415 V. 10 kA. \\"C\\" curve, double pole miniature circuit breaker suitable for inductive load in the existing DB complete with connections, testing and commissioning etc. as required. |
| 21 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 22 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable etc as required. |
| 24 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following bodymaterial and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range-5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electricalcircuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required withMinimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)18- 22 Watt |
| 25 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 45 watt |
| 26 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver asper the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to200 watt as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not morethan the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shallbe as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 27 | 150 watt |
| 28 | 200 watt |
| 29 | Supply of following size XLPE insulated and PVC sheathed aluminium power cable of 1.1 KV grade connection, testing etc. complete as required.4x25 sq mm |
| 30 | Supply of Power cable of following sizes XLPE insulated copper armoured conductor cable. The cost shall include all necessary supports clamps etc as necessary as required.4C x 16 sq mm |
| 31 | Supply of XLPE power cable of 1.1 kV grade aluminium conductor armoured cable of the followng sizes complete as required.3.5 x 300 Sq. mm |
| 32 | Supply and fixing of 250 mm exhaust fan etc complete as required. |
| 33 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 34 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 35 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 36 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 37 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 38 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 39 | 4 X 16 sq. mm (28mm) |
| 40 | 4 X 25 sq. mm (28mm) |
| 41 | 3½ X 300 sq. mm (70mm) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender