Defence Statutory Bodies & Commissions/Committees Closing in 9 days TDR #56572413

Tender For special Repair Lt Cable In Dstv Md Accn Area In Hisar Mil Stn Under Ge Hisar

Issued by Statutory Bodies & Commissions/Committees · Hisar, Haryana
Tender Value
38.82 Lakhs
Estimated cost
Bid Submission
10 Aug 2026
9 days left
EMD
77640
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Hisar → Haryana
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for special Repair Lt Cable In Dstv Md Accn Area In Hisar Mil Stn Under Ge Hisar

BOQ

Name of Work:- SPL REPAIR LT CABLE IN DSTV MD ACCN AREA IN HISAR MIL STN UNDER GE HISAR
Sl. No. Item Description
1Supply, laying, jointing, testing and commissioning in replacement of LT cable of size 25 Sqmm 4 core LT underground cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified and directed.Note : (i) All incoming and outgoing cable shall be connected by suitable size of thimbles/lugs.
2All as per item No 1.00 (here-in-before) but 35 Sqmm 3.5 core.
3All as per item No 1.00 (here-in-before) but 50 Sqmm 3.5 core.
4All as per item No 1.00 (here-in-before) but 70 Sqmm 3.5 core.
5All as per item No 1.00 (here-in-before) but 95 Sqmm 3.5 core.
6All as per item No 1.00 (here-in-before) but 120 Sqmm 3.5 core.
7All as per item No 1.00 (here-in-before) but 185 Sqmm 3.5 core.
8All as per item No 1.00 (here-in-before) but 240 Sqmm 3.5 core.
9All as per item No 1.00 (here-in-before) but 300 Sqmm 3.5 core.
10All as per item No 1.00 (here-in-before) but 400 Sqmm 3.5 core.
11Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed. Notes : 1. The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing condition and making good entirely to satisfaction of EIC.2. The PCC work shall be measured & paid for separately uner respective item of Sch 'A' / BOQ.
12M&L for sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed.Note :- For the purpose of payment only punned thickness shall be measured and paid.
13Taking up bricks laid as cable covers and stacking serviceable brick for reuse at site etc complete all as specified and directed.
14Laying only old bricks retrieved from item No. 13.00 (here-in-before) as cable covers in trenches etc complete all as specified and directed.
15M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed.
16Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed.
17Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed.
18M&L for boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 100 mm bore and making good both ends all specified and directed.
19Supply and fixing in replacement 40 mm bore GI Pipe of light grade with all fittings fixed to walls / floors / poles or under road etc complete all as specified and directed.
20Supply and fixing in replacement 80 mm bore GI Pipe of light grade with all fittings fixed to walls / floors / poles or under road etc complete all as specified and directed.
21M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth streep 25x4 mm by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 15 mm bore for watering and 40mm bore upto 7.50 metre long GI pipe light grade for earth strip protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete all as specified and directed.
22Supply, installation, commissioning and testing in replacement of LT Panel, LT(415 Volts, 50 Hz, 3-phase, 4 wire supply size of LT panel not less than 1.5 m high x 2.0 m width x 0.8 m depth CPRI approved/tested, factory assembled, out door type, weather and vermin proof (Protection Class IP-54) made out of 3.15 mm (for external) and 2.00 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged, double door opening for external, rubber lining, locking arrangement, painted internally and externally with powder coating of grey shade (RAL-7032) complete mounted on angle iron 65mm x 65mm x 6 mm legs 45 cm high above GL and 15 cm embedded in ground with and including blocks of PCC 1:2:4 type C1 of block size 30x30x30 cm comprising of the following:- (a) Bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer ACB, bus bar must be colour coded heat shrinkable as well as outgoings shall have aluminium four pole (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs. (b) INCOMING :- (i) ACB 4 pole, LT 415 Volts, 50 Hz AC grade of 800 Amps rating 50 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 Nos. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 Nos (iii) Ammeter 0-800 Amp digital type with 3 way rotary selector switch - 01 Nos (iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (c) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting -8 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 27 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 1 No. Notes : (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links.
23All as per item No 22 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.7 m depth but incommer & outgoing as per the following :- (a) INCOMING :- (i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade of 400 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No (iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36 KA -1 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 100 Amps 25 KA - 8 Nos.
24All as per item No 22 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.7 m depth but incommer & outgoing as per the following:- (a) INCOMING :- (i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade of 400 Amps rating 36 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 Nos. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No (iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps - 10 Nos.
25Demolition of path /concrete in ground floors and pavings (below or above ground level) not exceeding 15cm thickness complete all as specified and as directed. Note : The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing condition and making good entirely to satisfaction of EIC.
26M&L for cement concrete type B-2, 1:2:4 (40mm graded aggregate) as in foundation filling/ sub bases complete all as specified and as directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56572413
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 38.82 Lakhs
LAST DATE 10-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for special Repair Lt Cable In Dstv Md Accn Area In Hisar Mil Stn Under Ge Hisar
Basic Detail
Tender No GE(H)-15/2026-27
Bidding Type Tender
Location
City Hisar
State Haryana
Key Dates
Publish Date 20 Jul 2026
Submission Date 10 Aug 2026
Open Date 12 Aug 2026
Finance
Tender Value 38.82 Lakhs
Tender Fee 500
EMD 77640
Exemption Available
Document List
9409e842-fffe-41b7-97ed-0f2356f61750.html
BOQ_873356.xls
TENDERGE15.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 20, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 10, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 9 days
Aug 12, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 11 days

Tender Documents

Download All (ZIP) ↓
html

9409e842-fffe-41b7-97ed-0f2356f61750.html

xls

BOQ_873356.xls

pdf

TENDERGE15.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders