Tender For Provision Of Af Share Of Works For Certain Infrastructure At Af Stn Wadsar Under Ge (Af) Chiloda (File No. 89396/E8)
Tender Overview
Project Description
Tender For Provision Of Af Share Of Works For Certain Infrastructure At Af Stn Wadsar Under Ge (Af) Chiloda (File No. 89396/E8)
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-Aug-2026 | 1st date amendment | Date | 29-Aug-2026 |
| 2 | 21-Aug-2026 | 2nd amendment in dates | Date | 03-Sep-2026 |
| 3 | 27-Aug-2026 | 3rd Amendment in tender dates | Date | 08-Sep-2026 |
| 4 | 21-Aug-2026 | 2nd amendment in dates | Date | 03-Sep-2026 |
| 5 | 01-Sep-2026 | Amendments to tender documents | Other | 10-Sep-2026 |
| 6 | 01-Sep-2026 | Revised BOQ 2 | BOQ | 10-Sep-2026 |
| 7 | 28-Aug-2026 | Revised BOQ | BOQ | 10-Sep-2026 |
| 8 | 28-Aug-2026 | Amendment in tender document | Other | 10-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | NOTE: Schedule ‘A’ Part I to XII under Ser No. 1.00 to 12.00 are prepriced by MES. Bidders shall insert their lumpsum amount in the green coloured field under Col-6 only. |
| 2 | Lump sum price worked out for BUILDINGS/ STRUCTURES as listed in Sch 'A' Part I. |
| 3 | Lump sum price worked out for DEMOLITION/ DISMANTLING as listed in Sch 'A' Part II |
| 4 | Lump sum price worked out for EXCAVATION, EARTH WORK AND SITE CLEARANCE as listed in Sch 'A' Part III |
| 5 | Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch 'A' Part IV |
| 6 | Lump sum price worked out for INTERNAL WATER SUPPLY as listed in Sch 'A' Part V |
| 7 | Lump sum price worked out for ROAD/ PATH/ HARDSTANDING as listed in Sch 'A' Part VI |
| 8 | Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch 'A' Part VII |
| 9 | Lump sum price worked out for AREA DRAINAGE as listed in Sch 'A' Part VIII |
| 10 | Lump sum price worked out for EXTERNAL ELECTRIFICATION as listed in Sch 'A' Part IX |
| 11 | Lump sum price worked out for EXTERNAL WATER SUPPLY as listed in Sch 'A' Part X |
| 12 | Lump sum price worked out for FENCING & GATE as listed in Sch 'A' Part XI |
| 13 | Lump sum price worked out for LIGHTENING PROTECTION as listed in Sch 'A' Part XII |
| 14 | SCHEDULE 'A' PART - XIII MISCELLANEOUS ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signifies this fact only. Bidder shall insert their rates in Green filed under Col-6. |
| 15 | DEMOLITION AND DISMANTLING |
| 16 | Excavation over areas of any type of soil/strata upto 9 mtr height on existing earthen traverse walls complete all as specified and directed. |
| 17 | SEWAGE DISPOSAL |
| 18 | S&F on site LLDP sub ground structure septic tank of capacity 5000 Litres in one single unit, anaerobic type of domestic/semi commercial unit of dia 1440mm, height1550mm with BOD reduction upto approx 70% of the incoming sewage rotationally moulded with moulded in lifting eyes for handling & installation with provisions of manholes covers flexible in and outlet pipe designed to carry sewage & sludge water, excavation in any type of soil, PCC 1:4:8 below foundation, vent shift, connection etc with up flow filter including media complete all as specified and directed as per manufactures the following features shall be follows:-a. Durableb. 100% eco friendlyc. Light weightd. Rust proof/leak proof/corrosion proof/ not prone to crackinge. Completely water & air tight. |
| 19 | Provision of Soakage well including Excavation in any type of soil foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M-25 concrete including interrupting chamber and screen chamber made of brick masonry in CM, RCC cover slab in M-25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 3.0 mtr dia and 3.0 mtr effective depth complete all as specified & as directed. |
| 20 | FENCING & GATE |
| 21 | Supply of Glued PVC Coated Chain Link Fence System with following specification:-Fabric – 3.0 mtr height, 15 mtr lengthMesh size – 75x75mmLine wire dia – 3.0/4.0 mmTie & Stirup wire dia – 2.0/3.0 Strain Post – 60 mm OD, 3 mm thick, 4000mm (3000 + 1000MM grouted)Diagonal Support – 48 mm OD, 2 mm thick, 3800mmMOC – GalvanizedFinish – Polyester power Coated to 60-80 micron in green colour, RAL 6005Accessories : brace band, double clap, tension Band, rail End Cap, M8x35 SS304 mushroom Head bolt with security nut and washer, M10X250 GI Anchor Rod. |
| 22 | Installation of Fence System : Refer Note for technical Specifications Note :-Heavy Galvanized Glued PVC Chain Link Fabric The chain link fabric shall have a precise mesh size to ensure structural integrity and security as follows:Mesh Size 75x75 mm (Tolerance +/- 4.0 mm as per IS 2721)Fabric Length : 15 mtrFabric Height : 3 mtr Mesh Wire Galvanized GI wire as per IS280 (Soft)Mesh coated Wire Dia : 3.00 mm(ID)/4.00 mm (OD) (+/=0.1)Grade of Wire : 1 to 4 as per IS 7887Galvanizing of wire : Min 90 GSMTensile Strength of wire 350-550 N/sq mm as per IS 280 and tested as per IS 1608, Wire shall be Glue + PVC Coated as per ASTM F668 class 2 End Salvaedge of fabric : Knucking both side (KK) – Standard for general use as per IS 2721Certificate & Compliance : Wire supplier shall be from BIS- certified and have certification for wire manufacturing.Manufacturer shall hold a BIS license for IS 2721, ensuring national compliance and ISO 9001: 2015-certifed.Quality Management System to guarantee traceability and consistent product performance. |
| 23 | M&L for Construction of steel gate with RCC pillar (Size 5.5 m wide x 3m height ) including angle iron frame, guide rail, steel painting, plastering to pillars, excavation and earth work complete all as specified and shown on drawing (Drg No. CEAA/TD/70 Sheet ½) and as directed. |
| 24 | EXTERNAL WATER SUPPLY |
| 25 | M&L for Brick masonry valve pit of size 450 mm x 450 mm x 700 mm (internal) with neceaasry excavation and earth work, PCC 1:3:6 in foundation brick work in CM 1:6, 15 mm thick rendering in CM 1:4 (internally ) , 5 mm thick M/S plate cover incl M.S angle iron frame including material & labour for preparation of new iron surface & applying two coat of synthetic enamel paint over a coat of red oxide primer with and including locking arrangement complete all as specified and directed. |
| 26 | LIGHTENING PROTECTION |
| 27 | M & L for maintenance free Chemical earthing of technology with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed.Note:- (i) Earthing is to be done in front of the Engr-in-Charge.(ii) Test Results of earthing to be submitted by the contractor for all earthings.(iii) The Contractor shall have to give written guarantee for maintenance earth resistance of less than 1.0 Ohm for the period of 10 (ten) years after certified date of completion and shall be deposited 2000/- per earthing as security deposit for a period of Ten (10) Years.(iv) Failing to maintain resistance of earthing less than 01.0 ohm, new earthing to be provided by the contractor without any extra cost.(v) Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surrounding area complete. |
| 28 | EXTERNAL ELECTRIFICATION |
| 29 | Supply and lay for double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to ISI 14930 (Part I and II) for protection of underground cables of following size nominal outer dia & nominal inner dia with all fittings laid in trenches / road/ nallah or fixed along wall for cable protection complete all as specified and as directed. |
| 30 | (a) Nominal outer dia 63 mm & nominal inner dia 50 mm dia. |
| 31 | (b) Nominal outer dia 90 mm & nominal inner dia 76 mm dia. |
| 32 | (c) Nominal outer dia 120 mm & nominal inner dia 103.5 mm dia. |
| 33 | (d) Nominal outer dia 160 mm & nominal inner dia 136 mm dia. |
| 34 | S & F for Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 ( 20 mm graded aggregrate ) of size 900 x 300x 100 mm thick with DANGER/ 11 KV CABLE /MES embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work ( as required / ordered at site) complete all as specified and as directed. |
| 35 | S & F for Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with \\"DANGER/ LT 433 VOLTS CABLE /MES or DANGER/ MES\\" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed. |
| 36 | Supply, installation, Testing and commissioning of Outdoor type (IP 54), 05 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP54 SF6 insulated, One side Extensible, consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Four Nos (04) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration V+VVVV+M) inside robotically welded stainless steel 304 (Non Ferrite non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manager voltage surges and Air Insulated Metering Module of Class-0.5. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions & complete with all accessories. The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must RMU manufacturer's own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protectioncomplete all as specified and as directed. The unit shall include the following with all necessary standard fitting as required at site.- (At Main tapping point ) |
| 37 | Make of RMU shall be limited to : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE (Channel partner/ System Integrator/ Authourized Partner/ License partner make RMU shall not be accepted.) (a) Vacuum Circuit Breaker consist of following accessories :- (i) Microprocessor based Numerical Protection Relay for Circuit Breakers - REF615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 32, 27, 59, 25, 81U, 81O, 95 Measurement for 3I,I0,3U,U0,Kw,KVA,PF,Hz,Kwh, 16 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Graphical LCD Display (ii) Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. (iii) SF6 Gas pressure indicator on the gas tank. (iv) Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10,000 mechanical operation. (v) CT shall be minimum 50-100/1A ,2.5VA , 5P10 - 3 Nos. for protection (vi) CT shall be minimum 50-100/1A ,2.5VA , Class 0.5 - 3 Nos. for metering (vii) Right angle boot to be provided in each module (viii) 2 x12 Volts, 26 AH Battary with Charger - 1 Set (ix) Bus VT shall be 11KV/V3/110V/V3 ,20VA , Class 0.5 - 3 Nos. for metering (x) Auxiliary VT shall be 11KV/230 ,500VA for AC supply input to Battary Charger. (xi) Capacitive voltage indication fixed type system as per IE (xii) Interlocked Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (IP3X). Safety interlocked to prevent access to cable termination in live-condition. (xiii) Right angle boots (push on type) (xiv) Cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB. (xv) Necessay interclocking arrangement for safety and operations (xvi) One No. Operationg Handle for Manual Operation and one no. manometer (xvii) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (xviii) Above switchgear shall confirm to all relevant IEC/IS Standards. |
| 38 | Supply, installation, Testing and commissioning of indoor type (IP 3X), 06 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of Two Nos (02) motorised vacuum circuit breaker (Incomer) and four Nos (04) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIC (Configuration VVVVV+M) inside robotically welded stainless steel 304 (Non Ferrite non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manager voltage surges and Air Insulated Metering Module of Class-1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions & complete with all accessories. The complete RMU must be type tested for Internal arc 25KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must RMU manufacturer's own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protectioncomplete all as specified and as directed. The unit shall include the following with all necessary standard fitting as required at site..- (for Sub Station). Make of RMU shall be limited to : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE (Channel partner/ System Integrator/ Authourized Partner/ License partner make RMU shall not be accepted.) |
| 39 | (a) Vacuum Circuit Breaker consist of following accessories :- (i) Microprocessor based Numerical Protection Relay for Circuit Breakers - REF615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 32, 27, 59, 25, 81U, 81O, 95 Measurement for 3I,I0,3U,U0,Kw,KVA,PF,Hz,Kwh, 16 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Graphical LCD Display (ii) Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. (iii) SF6 Gas pressure indicator on the gas tank. (iv) Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10,000 mechanical operation. (v) CT shall be minimum 50-100/1A ,2.5VA , 5P10 - 3 Nos. for protection (vi) CT shall be minimum 50-100/1A ,2.5VA , Class 0.5 - 3 Nos. for metering (vii) Right angle boot to be provided in each module (viii) 2 x12 Volts, 26 AH Battary with Charger - 1 Set (ix) Bus VT shall be 11KV/V3/110V/V3 ,20VA , Class 0.5 - 3 Nos. for metering (x) Auxiliary VT shall be 11KV/230 ,500VA for AC supply input to Battary Charger. (xi) Capacitive voltage indication fixed type system as per IE (xii) Interlocked Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (IP3X). Safety interlocked to prevent access to cable termination in live-condition. (xiii) Right angle boots (push on type) (xiv) Cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB. (xv) Necessay interclocking arrangement for safety and operations (xvi) One No. Operationg Handle for Manual Operation and one no. manometer (xvii) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (xviii) Above switchgear shall confirm to all relevant IEC/IS Standards. |
| 40 | Supply, Installation, Commissioning and testing of Transformer11 KV/ 415 Volts, confirming to IS 1180 (Part-1)- 2014 with latest amendment No. 4, BEE 3 star rated, EEL 2, step down Out door type of capacity 2500 KVA complete with standard fittings, HT 33 KV 3 phase, LT 415 volts, 3 phase, 4 wire 09 position On Load tap changer of rating + 10% to -10% in steps @ 1.25 % each by means On load tap changing gear (OLTC)+ Remote Tap Cubical Changer (RTCC) Panel+ Automatic Voltage Regulator transformer copper wound, double wound, oil immersed naturally cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dyn -11 (vector group with neutral brought on secondary side (LV side) and the maximum temperature rises should not exceed 40 degree centigrade in oil and 45 degree centigrade in HV/LV winding ring measured by resistance after continuous full load run in ambient temp as per IS -2026 per transformer, IS-3639 for fitting & accessories, IS-2099 for high voltage porcelain bushings and the transformer shall be comprised with the following standard fitting with on load tappings on HT side to vary secondary voltage within limit all as per IS -1180 complete all as specified and as directed wit latest policy. |
| 41 | Supply, Installation, Commissioning and testing of Transformer 11 KV/ 415 Volts, confirming to IS 1180 (Part-1)- 2014 with latest amendment No. 4, BEE 3 star rated, EEL 3, step down Out door type of capacity 250 KVA complete with standard fittings, HT 33 KV 3 phase, LT 415 volts, 3 phase, 4 wire 09 position On Load tap changer of rating + 10% to -10% in steps @ 1.25 % each by means On load tap changing gear (OLTC)+ Remote Tap Cubical Changer (RTCC) Panel+ Automatic Voltage Regulator transformer copper wound, double wound, oil immersed naturally cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dyn -11 (vector group with neutral brought on secondary side (LV side) and the maximum temperature rises should not exceed 40 degree centigrade in oil and 45 degree centigrade in HV/LV winding ring measured by resistance after continuous full load run in ambient temp as per IS -2026 per transformer, IS-3639 for fitting & accessories, IS-2099 for high voltage porcelain bushings and the transformer shall be comprised with the following standard fitting with on load tappings on HT side to vary secondary voltage within limit all as per IS -1180 complete all as specified and as directed wit latest policy. |
| 42 | Note for item No 26 &27:- (i) Three Nos porcelain bushing suitable for 11 KV on HV side, complete with copper rods, nuts and washers with cable end box. (ii) Four Nos porcelain bushing suitable for 415 Volts on LV side, complete with copper rods, nuts and washers with cable end box. (iii) Monogram plate. (iv) Oil conservator with filter and drain plug. (v) Prismatic/transparent oil gauge.(vi) De-hydrating breather with first fill of dehydrating agent (silica gel). (vii) Thermometer pocket.(viii) Air release plug.(ix) Inspection cover (x) Lifting lugs for complete transformer (xi) Top cover lifting lugs (xii) Jacking lugs (xiii) Top filter valve (xiv) Instruction plate (xv) Drain cum bottom filter valves (xvi) Earthing terminal and stud (xvii) On load tap changer with RTCC & AVR (xviii) Rating and Diagram plate (xix) Buchholz relay with alarm & trip contacts. (xx) Bi directional roller wheel -04 Nos. (xxi) Marshalling box for termination of all alarm & trip controls of the transformer. (xxii) WTI (Winding temperature indicator) with alarm & trip contact (xxiii) Oil surge relay. (xxiv) Shut off valve for buchholz relay. (xxv) OTI (Oil temperature indicator) dial type of 150 mm with alarm and trip contact capillary type. (xxvi) Two earthing terminals on tank cover to facilitate fixing of 50x6 mm galvanised iron earth strip for earthing of body. (xxvii) Necessary PCC foundation/ block masonry platform as directed by OEM. (xxviii) First filling of new and unused transformer oil, IS-335 marked (Make Savita/ Apar/ Power Link Note :- (a) The rates include for supplying transformers with standard fittings and installing complete including all jointing materials, connecting with electrical system, earthing, testing and commissioning. (b) The transformer will have its initial oil filling to appropriate level (cost of oil including testing with desired dielectric strength included in supplied and installed rates, cost of PCC foundation shall be included as per manufacturer drawing) |
| 43 | Supply, install test & commissioning of Sandwich Type copper Bus Duct (from Transformer to ACB & Voltage Stabilizer) suitable for 1000 Volts, 4000 Amps, 150 KA for 1 Sec copper sandwich type construction, 3 Pole, 4 Wire, 100% N Body enclosure as Integral earth, Insulation voltage 1000 Volts having impulse withstand voltage of 12 kV, electrolytic copper conductor, insulated with class F Insulation material and factory fitted Joint block in one side of the each trunking components. The enclosure shall provide a protection IP- 55 as per IEC-60529 for indoor application and IP- 65 + canopy for outdoor application. The busbar trunking shall comply with standard IEC 61439-6. The Bus duct enclosure consists of four C-ribbed section bars, bordered and riveted, with excellent mechanical, electric and heat loss efficiency and painted with RAL- 7035 resins with high resistance to chemical agents.The enclosure shall provide a protection of IK 10 against mechanical impact.The whole busbar is Halogen Free and “fire“ complete all as specified and directed |
| 44 | Supply, install test & commissioning of Sandwich Type copper Bus Duct (from Voltage Stabilizer to Main LT Panel) suitable for 1000 Volts, 4000 Amps, 150 KA for 1 Sec copper sandwich type construction 3 Pole, 4 wire, 100% N Body enclosure as integral earth, insulation Voltage 1000 Volts having impulse withstand voltage of 12 kV, electrolytic copper conductor, insulated with class F Insulation material and factory fitted Joint block in one side of the each trunking components. The enclosure shall provide a protection IP- 55 as per IEC-60529 for indoor application and IP- 65 + Canopy for outdoor application. The busbar Trunking shall comply with standard IEC 61439-6. The Bus duct enclosure consists of four C-ribbed section bars, bordered and riveted, with excellent mechanical,electric and heat loss efficiency and painted with RAL7035 resinswith high resistance to chemical agents.The enclosure shall provide a protection of IK 10 against m echanical impact.The whole busbar is Halogen Free and and “fire“ complete all as specified and directed |
| 45 | Supply, install test & commissioning of Sandwich Type copper Bus Duct (from Main LT Panel to APFC Panel) suitable for 1000 Volts, 1600 Amps, 85 KA for 1 Sec copper sandwich type construction 3 Pole, 4 wire, 100% N Body enclosure as integral earth, insulation Voltage 1000 Volts having impulse withstand voltage of 12 kV, electrolytic copper conductor, insulated with class F Insulation material and factory fitted Joint block in one side of the each trunking components. The enclosure shall provide a protection IP- 55 as per IEC-60529 for indoor application and IP- 65 + Canopy for outdoor application. The busbar Trunking shall comply with standard IEC 61439-6. The Bus duct enclosure consists of four C-ribbed section bars, bordered and riveted, with excellent mechanical, electric and heat loss efficiency and painted with RAL7035 resins with high resistance to chemical agents.The enclosure shall provide a protection of IK 10 against mechanical impact.The whole busbar is Halogen Free and “fire retardant” in compliance with standard EN 60332-3. |
| 46 | Supply, installation, testing and commissioning of servo controlled voltage stabilizer confirming as per IS : 9815 Part-I: 1994 reaffirmed 2019, of capacity 2500 KVA, 415 Volts, 3 phase, 4 wire, 50 Hz, naturally oil cooled, indoor, balanced type, copper wound, digital display type, relay free smooth and silent operation with first filling of transformer oil (IS 335 :2018) complete all as specified and as directed. |
| 47 | (a) 2500 KVA |
| 48 | (b) 250 KVA |
| 49 | Note:- Servo controlled voltage stabilizer shall have following specifications:- (i) Input voltage 360 Volts- 480 Volts (ii) output voltage 415V+/- 1% (Adjustable) (iii) rated frequency 50 Hz (iv) No distortion in wave fom (v) response time not to exceed 10 mille seconds (vi) Sensitivity (+1) 1% (vii) Rate of correction more than 6 volt/second for per phase (viii) class of insulation -A (ix) No load losses less than 0.5% (x) Full load losses less than 2.5% (xi) duty cycle -continuous 24x7 (xii) efficiency more than 95% (xiii) Type of load : 3 phase, unbalanced type (xiv) Digital display voltmeter /ammeter (xv) Over load/short circuit protection (xvi) High/low voltage cut off (xvii) By pass arrangement in case of emergency (xviii) Single phase sequence change protection |
| 50 | Supply ,fabrication, installation and testing of LT isolator Panel factory made, Type Test Assemble (TTA) Panel, indoor type for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 2.0 mm thick CRCA sheet of suiitable size accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP- 54 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate). Note:- All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:- |
| 51 | INCOMER:- (a) Copper strip busbar of 6000 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos (b) ACB 4 Pole 4000 Amps, Draw- out type circuit breaker with Microprocessor based ET6L Trip Unit with thermal memory, Fully rated neutral with in built protection, ET6L provides Over load, Shortcircuit, Instantaneous & Earth-fault protections, Short circuit breaking capacity 65 KA @ 440 volts AC, Conforms to IS/ IEC60947-2&3 and Incomer & Outgoing connectionSandwich Duct from TOP side)- 01 No. (c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) (d) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 01 set. |
| 52 | OUTGOING: (a) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity (O/C, S/C & E/F) Protection including all fixing accessories with both ends spreader link- 01 No (for fixed type capacitor panel 100 KVAR) (b) MCCB 80 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos (for fixed type capacitor panel 50 KVAR) (c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -03 set (set of three) (d) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 03 set. (e) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 53 | S & F for LED Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 protection security light fitting luminaire of capacity 70 watts with high power LEDs as light source and electronic driver, 4kV inbuilt and 10 kV external surge protecton with Top opening driver cover for easy maintenance with warranty option of 5 years from date of installation with pre wired and necessary mounting arrangements and provision of 4 sq mm three core copper conductor cable multi stranded from fitting terminal to street junction box complete all as directed. |
| 54 | Supply ,fabrication, installation and testing of LT Panel factory made, Type Test Assemble (TTA) Panel, indoor type for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 2.0 mm thick CRCA sheet of suiitable size accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP- 54 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate).(for Transformer 2500 KVA Panel). Note:- All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:- |
| 55 | INCOMMING:- (a) Copper strip busbar of 6000 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos (b) ACB 4 Pole 4000 Amps, Draw- out type circuit breaker with Microprocessor based ET6L Trip Unit with thermal memory, Fully rated neutral with in built protection, ET6L provides Over load, Shortcircuit, Instantaneous & Earth-fault protections, Short circuit breaking capacity 65 KA @ 440 volts AC, Conforms to IS/ IEC60947-2&3- 01 No (c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) (d) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 01 set. |
| 56 | OUT GOING:- (a) ACB 4 Pole 3200 Amps, Draw- out type circuit breaker with Microprocessor based ET6L Trip Unit with thermal memory, Fully rated neutral with in built protection, ET6L provides Over load, Shortcircuit, Instantaneous & Earth-fault protections, Short circuit breaking capacity 65 KA @ 440 volts AC, Conforms to IS/ IEC60947-2&3- 01 No (b) ACB 4 Pole 1600 Amps, Draw- out type circuit breaker with Microprocessor based ET6L Trip Unit with thermal memory, Fully rated neutral with in built protection, ET6L provides Over load, Shortcircuit, Instantaneous & Earth-fault protections, Short circuit breaking capacity 65 KA @ 440 volts AC, Conforms to IS/ IEC60947-2&3- 01 No. (forAPFC panel 900 KVAR) (c) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (d) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (e) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -02 set (set of three) (f) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 02 set. (g) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 57 | Supply ,fabrication, installation and testing of LT Panel factory made, Type Test Assemble (TTA) Panel, indoor type for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 2.0 mm thick CRCA sheet of suiitable size accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP- 54 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate). (for Transformer 250 KVA Panel). Note:- All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:- |
| 58 | INCOMER:- (a) Copper strip busbar of 600 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos (b) MCCB 400 Amps with rotary handle with built-in Microprocessor Based Release, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity (O/C, S/C & E/F) Protection including all fixing accessories with both ends spreader link- 01 No. (c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) (d) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 01 set. |
| 59 | OUTGOING: (a) MCCB 400 Amps with rotary handle, with built-in Microprocessor Based Release, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity (O/C, S/C & E/F) Protection including all fixing accessories with both ends spreader link- 01 No. (HPR feeder No 2) (b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity (O/C, S/C & E/F) Protection including all fixing accessories with both ends spreader link- 02 Nos. (forAPFC panel 90 KVAR)+ spare0 (d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -03 set (set of three) (e) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 03 set. (f) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 60 | Supply ,fabrication, installation and testing of LT Panel factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 2.0 mm thick CRCA sheet of suiitable size accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP- 54 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate). All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:- |
| 61 | INCOMER:- (a) Copper strip busbar of 120 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos (b) MCCB 63 Amps with rotary handle with built-in Microprocessor Based Release, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity (O/C, S/C & E/F) Protection including all fixing accessories with both ends spreader link- 01 No (c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) (d) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 01 set. |
| 62 | OUTGOING:(a) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 No. (for SS load , Street lights load) (b) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -04 set (set of three) (e) Digital Multifunction Meter with RS-485 communication port, Accuracy Cl.-1.0 with suitable CT’s of ratio and selector switch – 04 set. (f) Multifunctional Digial type Astronomical function Time switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase - 01 No (g) Power contractor 2 Pole, 32 Amps, 250 Volts, 50 Hz - 01 No (h) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 63 | Supply, installing, testing and commissioning of factory made Type Test Assemble (TTA) APFC Panel wihth MPP-H capacitor and suitable capacity ACB as incommer, indoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 54 class protection and made of 2.0 mm CRCA MS sheet and 50 x 50 x 5mm thick MS angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement having copper bus bar size four strips 2400 Amps 415 Volts consisting of 900 KVAR with 16 steps (4x 100 KVAR+ 8x 50 KVAR+ 4x 25 KVAR) including necessary Protection with suitable Amps ratingMCCB 4 pole of each capacitor bank complete all as specified and as directed. |
| 64 | Supply, installing, testing and commissioning of factory made Type Test Assemble (TTA) APFC Panel wihth MPP-H capacitor and suitable capacity MCCB as incommer, indoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 2.0 mm CRCA MS sheet and 50 x 50 x 5mm thick MS angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement having copper bus bar size four strips 150 Amps 415 Volts consisting of 90 KVAR with 04 steps (1x 50 KVAR+ 1x 20 KVAR+ 1x 15 KVAR + 1x 5 KVAR) including necessary Protection with suitable Amps ratingMCCB 4 pole of each capacitor bank complete all as specified and as directed. |
| 65 | Supplying and laying synthetic Rubber insulated mats suitable for voltage upto 33 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of size 2.0 Mtr x 1.0 Mtr x 20 mm tihck complete all as specified as diredcted. |
| 66 | M & L for maintenance free Chemical earthing of technology with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 67 | Note:- (i) Earthing is to be done infront of the Engr-in-Charge. (ii) Test Results of earthing to be submitted by the contractor for all earthings. (iii) The Contractor shall have to give written guarantee for maintenance earth resistance of less than 1.0 Ohm for the period of 10 (Ten) Years after certified date of completion and shall bdeposited 2000/- per earthing as security deposit for a period of Ten (10) Years. (iv) Failing to maintain resistance of earthing less than 01.0 ohm , new earthing to be provided by the contractor with out any extra cost. (v) Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surronding area complete. |
| 68 | S & F for Security light junction box of size 205 x 255 x 112 mm for luminaries, weather proof made out of polycorbonate housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole/ wall mounting type comprising of MCB SP 10 Amps, fixed on pole with bracket and screws complete all as specified and as directed. |
| 69 | NOTE : Amount of credit of Rs. 872823.01 for retrieved materials is mentioned in schedule of credit on Srl Page No. 54 of tender documents in pdf form which will be deducted offline while acceptance of tender. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 6 daysCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayCorrigendum-5 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysCorrigendum-6 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysCorrigendum-7 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysCorrigendum-8 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender