Tender For Augmentation Of Water Supply Scheme Buh, Block Dhilwan, District Kapurthala. (Under Head 15Th Fc)
Tender Overview
Project Description
Tender for Augmentation Of Water Supply Scheme Buh, Block Dhilwan, District Kapurthala. (Under Head 15Th Fc)
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 28-Jul-2026 | Date extended upto 05.08.2026 | Date | 05-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Development of tubewell |
| 2 | Development and Stabilizing of the tubwell with air compressor of required capacity as directed by the engineer-in- charge including cost of tools, appliances & consumable to the satisfaction of Engineer-in-charge. |
| 3 | Capacity of Air compressor 300 cfm at 250 PSI |
| 4 | Collection of water sample from different strata and testing of sample from approved laboratory (Phisical & chemical Analysis) |
| 5 | Testing of water sample for Heavy metal from approved laboratory (Toxic material such as Arsenic, lead, mercury, pesticide etc.) |
| 6 | Construction One No. 50KL (50,000 Itrs) capacity having height 20.00 mtr of up to FSL & 17.00 mtr sill level from Ground level complete with external RCC stair case with landing slabs at each staging RCC roof, ventilator single main hole cover lightening conductor etc. complete as described in schedule No.3. Providing and fixing D.I. K-9 D/F expansion joints latest bell mouth and D/F puddle collars as per DWSS design on basis of enclosed drawing. Duck foot bends, Conforming to ISI - 9523 and C.I/D.I. D/F sluice Valve duly ISI marked (IS-14846-2000 or latest) one each with inlet, outlet and scour pipes, including providing and installing inlet, outlet scour pipe and overflow DI double flanged pressure pipes DI K-9 horizontally as per IS 8329-2000 and latest Amendments duly ISI marked from bottom dome to duck foot bend and further up to 2.75 mtr as per detail specification. TMT steel Providing & applying integral crystalline slurry hydrophilic in nature for water freezing management for vertical & horizontal service and swell able type water stop tape & painting of all complete shall be included in cost & P/F aluminum ladder inside the OHSR complete in all respect as per specifications. (The specifications & drawing are based on safe bearing capacity of soil not less than 8.75 tone per sqm. In case the safe bearing capacity of soil is less than 8.75 tone per Sqm. then the contractor shall submit his own design for foundation portion based on actual safe bearing capacity as per DWSS specifications. The difference in quantities from the standard drawing based on 8.75 tone per sqm safe bearing capacity will be paid as per CSR+ Prevailing Ceiling Premium including providing and fixing automatic Electronic Water Level control Device and Construction of Plinth protection around OHSR with masonry toe wall with 40 mm thick CC 1:2:4 on top over 100 mm thick CC 1:8:16 including overflow scour haudi complete in all respects. Note 1) Providing and applying integral crystalline slurry of hydrophilic in nature for water proofing management etc. (For vertical and horizontal surface) 2) Providing and applying of swellable type water stop tape etc |
| 7 | Rising main |
| 8 | Providing, Laying, fixing & jointing of P.V.C. Pipes Type-A as per ISI-4985-2021 (ISI marked with the prior approval of Engineer-in-charge) along the Trenches and laying the same in Trenhes to correct alignment and gradients, cutting, jointing and testing complete as per specifications.For more than 3 mtr street width with Mechanically Excavation including specials |
| 9 | 110mm o/d pipe of 10 kgf. / sqcm |
| 10 | Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze(gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing , testing & cost of Nut ,Bolt & insertion sheet, all carriage complete (with the approval of Engineer in- charge). |
| 11 | Class PN-1 as per ISI |
| 12 | 100mm i/d Sluice Valves flanged |
| 13 | Construction of masonary Sluice Valve Chamber excluding Sluice valve cover as per standard design & drawings of public health department |
| 14 | Size 0.6 m. x 0.6 m. |
| 15 | Distribution network |
| 16 | Providing, Laying, fixing & jointing of P.V.C. Pipes Type-A as per ISI-4985-2021 (ISI marked with the prior approval of Engineer-in-charge) along the Trenches and laying the same in Trenhes to correct alignment and gradients, cutting, jointing and testing complete as per specifications.For more than 3 mtr street width with Mechanically Excavation including specials |
| 17 | 63mm o/d pipe of 6 kgf. / sqcm |
| 18 | 75mm o/d pipe of 6 kgf. / sqcm |
| 19 | 90mm o/d pipe of 6 kgf. / sqcm |
| 20 | 110mm o/d pipe of 6 kgf. / sqcm |
| 21 | 160mm o/d pipe of 6 kgf. / sqcm |
| 22 | Providing, Laying, fixing & jointing of P.V.C. Pipes Type-A as per ISI-4985-2021 (ISI marked with the prior approval of Engineer-in-charge) along the Trenches and laying the same in Trenhes to correct alignment and gradients, cutting, jointing and testing complete as per specifications.For Less than 3 mtr street width Manual Excavation including specials |
| 23 | 63mm o/d pipe of 6 kgf. / sqcm |
| 24 | 90mm o/d pipe of 6 kgf. / sqcm |
| 25 | Dismantling brick or flagged stone flooring without concrete base and relaying of dry brick on edge paving with a dismantled bricks including sand grouting and including restoration of roads to orginal Position |
| 26 | 63mm o/d pipe of 6 kgf. / sqcm |
| 27 | 75mm o/d pipe of 6 kgf. / sqcm |
| 28 | 90mm o/d pipe of 6 kgf. / sqcm |
| 29 | 110mm o/d pipe of 6 kgf. / sqcm |
| 30 | Dismantling of interlock tile 80mm thick cement concrete interlocking paver block including Refixing of interlock tile 80mm thick cement concrete interlocking paver block of M-40 grade machine made rubber moulded smooth finish by strong vibratory process or with vibro-hydraulic compaction machine and of approved size and design/ shape laid in ordinary grey color and pattern over including 40mm thick |
| 31 | 63mm o/d pipe of 6 kgf. / sqcm |
| 32 | 75mm o/d pipe of 6 kgf. / sqcm |
| 33 | 90mm o/d pipe of 6 kgf. / sqcm |
| 34 | Dismantling of cement concrete road and restoration in original condition |
| 35 | Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze(gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing , testing & cost of Nut ,Bolt & insertion sheet, all carriage complete (with the approval of Engineer in- charge). |
| 36 | Class PN-1 as per ISI |
| 37 | 80mm i/d Sluice Valves flanged |
| 38 | 100mm i/d Sluice Valves flanged |
| 39 | 150mm i/d Sluice Valves flanged |
| 40 | Construction of masonary Sluice Valve Chamber excluding Sluice valve cover as per standard design & drawings of public health department |
| 41 | Size 0.6 m. x 0.6 m. |
| 42 | Size 0.9 m. x 0.9 m. |
| 43 | Hand boring Horizontly for crossing of pipe under road or any other obstacle by using Auger/Bocki method.Including excavation, stringing and jointing of pipe upto 160mm complete |
| 44 | Excavation manually in trenches for pipe lines with straight or open cutting in streets and lanes in builtup area where width of street / Lane from wall to wall is less than 3 meter including trimming and dressing sides levelling of beds of trenches to correct grade, cutting joint holes, refilling consolidation, watering , including the cost of dewatering of rain water, diversion for traffic, night signals. Providing & fixing caution boards, watching, fencing, etc. and removal of surplus soil from the site upto 15 meter distance complete in all respects. |
| 45 | Earth work upto 1.5 m. Depth |
| 46 | All classes of soil except rocky |
| 47 | Supplying and fixing of ISI Marked CI D-joint (complete with nut, bolts & rubber ring) as per IS:8794 for repair of pipe line including cutting, jointing and testing etc. but excluding cost of excavation complete. |
| 48 | 80 mm |
| 49 | 100 mm |
| 50 | Bailing out water from the trenches for making new connections in existing pipe lines including cleaning trimming and dressing the trenches to correct alignment and grade as required by the Engineer-in-charge. |
| 51 | Connection with pipe line Upto 300mm i/d |
| 52 | Connection with existing PVC pipe including cost of tee earth work in excavation and back filling complete in all respect |
| 53 | Pumping machinery |
| 54 | Providing & installing, testing & commisioning of 1 no electrically driven Submersible Pump set capable of delivering 321 LPM against a head of 63 mtr along with electric panel board consisting of electrical appliances such as automatic Star Delta Push Button or oil imeersed starter, Main Switch, VM, AMpere Meter, ELCB, Shunt capacitor. Single phase, preventer, Indicating lamps, Kit-Kat etc., including submersible cable 95 mtr length and 4.00mm2 size as per IS694-1990 reaffirmed 2000 complete in all respects. |
| 55 | (Motor with Pump) 321LPM, 63mtr Head |
| 56 | Panel Board |
| 57 | Supply and erection of PVC insulated PVC sheathed (3 core) round flexible wire with copper conductor (FR) cable (ISI marked) confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 58 | Overall size 4.0sq.mm (84/0.3mm), 3Core |
| 59 | Repair of Pump Chamber size 3.70 x 4.30 |
| 60 | Dismantling concrete |
| 61 | Cement concrete plain 1:2:4 mix |
| 62 | Scraping |
| 63 | Cement Plaster |
| 64 | Conglomerate floor 40mm thick cement concrete rete 1:2:4 on 100mm thick cement concrete 1:8:16 with stone aggregate 40mm gauge and 100mm fine sand filling using mechanical mixer for mixing of material |
| 65 | Conglomerate floor 50mm thick cement concrete rete 1:2:4 on 100mm thick cement concrete 1:8:16 with stone aggregate 40mm gauge and 100mm fine sand filling using mechanical mixer for mixing of material |
| 66 | 12.5 mm thick cement plaster 1:4 |
| 67 | Preparation of plastered surfaces for distempering including surface, applying filling with approved quality filler consisting of plaster of paris and chalk mitti including finishing the surface to the required finish complete |
| 68 | Finishing walls with cement based water soluble paint such as snowcem, robbiacem etc. two or more coats to give an even shade |
| 69 | Applying pink primer or aluminum priming coat on wood work including preparation of surface knotting and stopping etc. |
| 70 | Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade. |
| 71 | Applying priming coat with metal primer on new steel or iron work including preparation of surface. |
| 72 | Supplying and fixing glass panes with glazing clips and special metal sash putty of approved make. |
| 73 | Glass panes 3mm or 8.44 kg per sqm upto 0.4 sqm area |
| 74 | Hollock wood doors shutter windows shutter including hinges, screws, chocks, cheats, stops cords etc. complete fixed in position. |
| 75 | panelled, glazed or glazed and panelled. |
| 76 | 40 mm thick |
| 77 | RECESSED HGW CONDUIT PIPE WIRING SYSTEM WITH FLUSH PIANO TYPE SWITCHES: |
| 78 | Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge welded conduit pipe 20mm/ 25mm dia (1.6mm thick) ISI Marked recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for having (Flush/ Piano type accessories) Step type electronic fan regulators 100watts (socket size), bell push, 5Pin 6Amp. sockets (4Module Box), 16Amp. universal sockets (6Module Box), 6/16/20Amp. Switches etc. and covered with brown bakelite white glazed translucent backside painted sheet 3mm thick etc., PVC connector (For Fan Box and Call Bell), PVC Bush, Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), CI Circular junction Boxes (Four way 1½\\" deep for walls and 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 79 | Wiring fan point (With fan box) |
| 80 | Wiring light point |
| 81 | Wiring 6Amp. Plug control comprising wall socket point |
| 82 | Wiring 16/20Amp. power plug control point |
| 83 | Household water connection on PVC Pipe line |
| 84 | Providing proposed water connection to household up to wall with providing, laying, jointing, testing GI pipe lines 15mm i/d B-Class, (Above GL), Prov. & fixing MDPE pipe 15mm i/d with speicals (Below GL), including cost of specials such as tees, bends, sockets, elbow etc. cutting, threading and testing in trenches in ground and ISI marked 15mm i/d GM furrule as per IS:2692 and 3\\" i/d clamp with C.I. bib cock 15mm i/d as per IS:210 with stainless steel spindle of approved make complete in all respects. |
| 85 | Disinfection Unit |
| 86 | Disinfection Unit Providing Installing, testing & commissioning one no. Electronically actuated, Diaphragm operated, Metering System, Chemical Dosing, Chlorinator, Suitable for delivering 0.5 to 6 Litres fo Bleaching Powder solution/ Sodium Hypo solution per hour under maximum delivery pressure upto 7 Kg. cm2 and suction lift not less than 1.5 m, as per DWSS standard specifications |
| 87 | Development of water works |
| 88 | Construction of Cement Concrete Foot Path with masonry toe wall & earth filling inside water works as per standard Drawing |
| 89 | Painting of MS Sign board as per standard size of DWSS as per standard Drawing |
| 90 | Credit of Old Pumping machinery |
| 91 | Old electrically driven submersible pump set 10.00 BHP Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 7 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender