Tender For Repair And Replacement Of Old Unsv Defected Lt Panels, Ug Cables, Lt Switch Gear Items In Central Ac Plants Under Ge (I) Gos.
Tender Overview
Project Description
Tender for Repair And Replacement Of Old Unsv Defected Lt Panels, Ug Cables, Lt Switch Gear Items In Central Ac Plants Under Ge (I) Gos.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 30-Jul-2026 | corrigendum1 | Other | 10-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Taking down old unsv/burnt LT panels/Feede pillar of any capacity and supply, install, testing and commissinoning of LT panel board indoor type of size 2250 mm long X1800 mm width X 400 mm thickness(depth) (length and width and thickness of LT panel sizes if required for heigher & lower size as required and decided by Engr-in-charge) with single door type suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz, ,cubicle and shall have air ventilation arrangement,IP-54 Protection, floor mounted, free standing, dust and vermin proof, with see through glass as per requirement made out of 2 to 2.15mm thick at outer sheet and 1.60 mm thick at internal compartments CRCA sheet and necessary angle/flat irons duly powder coated, hinged doors with rubber gasket, handles.Panel shall have front and rear opening,locking arrangement,cable alleys,cable entry holes for incoming and out going cables,busbar chamber and switch gear compartment,see through glass for indicator lamps, control copper wiring & safety fuses,earthing terminals,affix danger notice plate,aluminium busbar fixed on DMC/SMC insulators and all incoming and outgoing internal connection should be connected suitable rating aluminium bus bars only with RYB color code sleeves/taps, and the panel will be mounted on 50mmX50mmX6 mm GI angle iron base frame of height 45 CM above GL as per site requirement and below GL 45 CM and including connecting up of existing incoming and out going cables by using new aluminium lugs and cable gland and connecting of earth strip and providing civil work/PCC foundation (1:2:4) type B1 with studs,bolts,nuts & washers as per site requirement. And complete all as specified and directed and including comprising of following:- |
| 2 | Note:- (i) LT panel board manufactured by any manufacturer should be followed by CPRI norms/certified and also zonal approved maufacturers only. (ii)The contractor shall be arranged General (SLD), circuit lay out drawings & Switch gear items makes/brands submitted for prior approval by the Accepting Officer/Engineer -in-charge before procurement/ordering.(i) Incoming:- MCCB,4 pole,400 Amps,415 Volts, 35/36 KA,50Hzs Manual drawout type with THERMAL MAGNETIC based release system incl factory fabricated steel spreader links & steel nuts,bolts and washers of suitable amps rating in RYB &N.-01 Nos (ii) Outgoing :- ON-Load change over switch with front operated handle 315Amps,415Volts 4 Pole incl steel coated factory fabricated spreader links & steel nuts,bolts and washers of suitable amps rating in RYB &N-01 Nos. |
| 3 | (iv) MCCB,4 pole,125 Amps,415 Volts, 25 KA,50Hzs Manual drawout type with thermal magnetic based release system incl factory fabricated steel spreader links & steel nuts,bolts and washers of suitable amps rating in RYB (v) MCCB,4 pole,100 Amps,415 Volts, 25 KA,50Hzs Manual drawout type with thermal magnetic based release system incl factory fabricated steel spreader links & steel nuts,bolts and washers of suitable amps rating in RYB (vi) MCCB,4 pole,63 Amps,415 Volts, 16/18 to 25 KA,50Hzs Manual drawout type with thermal magnetic based release system incl factory fabricated steel spreader links & steel nuts,bolts and washers of suitable amps rating in RYB (viii) R,Y,B Phase indicating lamp -01 Set Make:- Jigo/L&T/C&S(ix) Digital Ammeter (0 amps to 500 Amps) with ASS (Ammeter selector switches) -01 No.(x) 400/5A current transformer -03 No's (xi) Digital Voltmeter( 0Volts to 500Volts)-01 No with VSS,(xii) Protection fuses& controll wiring -03 Nos (xiii) Main bus bar & distribution out going distribution busbar size and amps rating x1.5 times rating of controlling MCCBs capacity TPN bus bar 400 amps rating -01 Set |
| 4 | Taking out old unsv existing on load change over with wall mouted sheet steel enclosure any type/rating and incl providing supply and fix on load change over switch 415V in wall mounted sheet metal enclosure/open excution type/side handle type as per site requiremet 4 pole of capacity 400 amps and including providing incoming and outgoing cables features and necessary hole fasters, lugs,nuts,bolts and washers etc and including providing necessary alterations,welding works in existing panels/on wall mounting fitting complete all as specified and directed. |
| 5 | Taking out old unsv existing on load change over with wall mouted sheet steel enclosure any type/rating and incl providing supply and fix on load change over switch 415V in wall mounted sheet metal enclosure/open excution type/side handle type as per site requiremet 4 pole of capacity 250 amps and including providing incoming and outgoing cables features and necessary hole fasters, lugs,nuts,bolts and washers etc and including providing necessary alterations,welding works in existing panels/on wall mounting fitting complete all as specified and directed. |
| 6 | Taking down old unsv busbar from existing location and incl providing supply and fix supply and fix compact air insulated rising main busbar made in 2 mm sheet steel metal enclosure with ETP grade copper bus bar,4 pole, 315/320A,4 way amps,busbar breaking capacity of 35 KA and IP 54 protection suitable for wall mounted concealed in wall surface level and including providing incoming and outgoing features and necessary conneceted accessopries complete all as specified and directed . |
| 7 | Taking down old rusted unsv cable tray from existing location and supply and fixing new pre galvanized pertorated cable tray 100mm x 100 mmx1.60mm suitable for fixing on wall/roof hanging/ floor mounted as per site requirement and including providing GI hanging rod,nuts,bolts and washers complete all as specified and directed. |
| 8 | Taking down old rusted unsv cable tray from existing location and supply and fixing new pre galvanized pertorated cable tray 100mm x 50 mmx1.60 mm suitable for fixing on wall/roof hanging/ floor mounted as per site requirement and including providing GI hanging rod,nuts,bolts and washers complete all as specified and directed. |
| 9 | Taking down old unsv busbar from existing location and incl providing supply and fix supply and fix compact air insulated rising main busbar made in 2 mm sheet steel metal enclosure with ETP grade copper bus bar,4 pole, 250A,4 way amps,busbar breaking capacity of 35 KA and IP 54 protection suitable for wall mounted concealed in wall surface level and including providing incoming and outgoing features and necessary conneceted accessopries complete all as specified and directed . |
| 10 | Material and labour for earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 32 X 6 mm from earth electrode to test point or up to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate no 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including char coal, salt packed all around the earth electrode plate in layers,PCC earth pit chamber 1:3:6 type C1,RCC cover 1:2:4 type B1, including excavation,earth work in any strata and returning filling, removal of surplus soil and testing for required value complete all as specified and directed. |
| 11 | M&L for PVC insulated sheathed single core 70 sqmm unarmed LT copper conductor cable as earth continuity conductor with galvanized shaddle with screws for two number in each running metre complete all as specified and directed. |
| 12 | M&L for PVC insulated sheathed single core 16 sqmm unarmed LT copper conductor cable FRLS type complete all as specified and directed. |
| 13 | M&L for PVC insulated sheathed single core 25 sqmm unarmed LT copper conductor cable FRLS type complete all as specified and directed. |
| 14 | M& L for in repair earthing continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn inconduit pipe or fixed to poles or any other indicated situation for loop earthing etc as required galvanised iron steel earth strip of size 25x4 mm size for earthing connectivity conductor incl providing suitable heavy duty insulators,nuts,bolts and screws etc with insulators for three number in each running metre complete all as specified and directed. |
| 15 | Cutting of bituminous top road,PCC surface/floor by using mechanical method incl road boaring/cutting any type carefully without damagig to surrounding area complete all as spfd and directed. |
| 16 | Material and labour for PCC 1:2:4 type B1 using 20 mm grade aggregate as in pre cast cover slabs including form work and set in cement motor 1:6 complete all as spfd and directed. |
| 17 | Supply and fixing galvanised steel cable tray of size 250mm X100 mmx 5 mm tray fixing on wall with proper nuts,bolts ,GI clamps and washers etc fixing at ay height on wall surface and necessary anchoring arrangements,cuttings,jointings,weldigs,fabrication as per site reqt suitable for UG cable laying complete all as specified and directed. |
| 18 | Material & labour for GI pipe 80 mm \\" light grade'' laid in trenches floors/on,pole/road for cable protection with all fittings complete all as specified and directed. |
| 19 | Boaring holes horizontally under road without damaging the surface of road (minimum 1.0 Mtr bellow the road surface) with the help of GI tubing of any dia not exc 80mm dia for passing of UG cable all as specified and as directed. |
| 20 | Supply and filling in and spreading unwashed river sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. |
| 21 | Excavation in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr depth for laying of cables, pipe lines, protection pipes and foundations etc and getting out in soft loose soil complete all as specified and directed. |
| 22 | Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed |
| 23 | Removing excavated soil not exc 50 mtr ant depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed |
| 24 | M & L for brick sub class 'B' 250mm x 115mm x 0.75mm and laid in trenches as in protection of UG cable complete all as specified and directed. |
| 25 | Material & labour for GI pipe 50 mm \\"light grade\\" laid in trenches floors/on , pole/road for cable protection with all fittings complete all as specified and directed. |
| 26 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 16 sqmm,3.5 core complete all as specified and directed. |
| 27 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 25 sqmm,3.5 core complete all as specified and directed. |
| 28 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 35 sqmm,3.5 core complete all as specified and directed. |
| 29 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 50 sqmm,3.5 core complete all as specified and directed. |
| 30 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 70 sqmm,3.5 core complete all as specified and directed. |
| 31 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 95 sqmm,3.5 core complete all as specified and directed. |
| 32 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 120 sqmm,3.5 core complete all as specified and directed. |
| 33 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 150 sqmm,3.5 core complete all as specified and directed. |
| 34 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 185 sqmm,3.5 core complete all as specified and directed. |
| 35 | Taking up/down old unsv underground cable from existing locations and supply, laying and testing cable XLPE insulated,screened,PVC bedded,galvanized steel strip or wire armoured,electric power cables 1100 volts grade with stranded aluminium conductor of size 240 sqmm,3.5 core complete all as specified and directed. |
| 36 | Supply, installation,testing and commissioning of 8.5 TR (Tons of Refrigeration) AC compressor heavy-duty commercial unit scroll compressor designed for ductable ACs, package units, and chillers, operate on 3-phase power (380–420V), cooling capacity 102,000 BTU/h (8.5 tons) motor power 10HP to 11HP, primerilly Refrigerant R410A, R407C, or R22 (depending on the system age) all as specified and directed by Eng-in-Charge. |
| 37 | M&L for replacement of cast iron sluice valve with stainless steel spindles with flanged ends duly ISI marked confirming to IS 780 part1, PN 1 type complete suitable as per exiting AC plant for the 100 MM bore sizes complete all as specified and directed. |
| 38 | All as per item No 37 above but 80 MM bore |
| 39 | All as per item No 37 above but 65 MM bore |
| 40 | Taking down old unsv butterfly valve from existing location and supply and fixing new butterfly valve of size 100 mm dia and including necessary pipe fittings nuts,bolts,washers and rubber washers etc complete all as specified and directed |
| 41 | All as per item No.40 above but size 80 mm dia. |
| 42 | All as per item No.40 above but size 65 mm dia. |
| 43 | All as per item No.40 above but size 50 mm dia. |
| 44 | Taking down old unsv Non return valve from existing location and supply and fixing new non return valve of size 100 mm dia and including necessary pipe fittings, nuts,bolts,washers and rubber washers etc complete all as specified and directed |
| 45 | All as per item No.44 above but size 80 mm dia. |
| 46 | All as per item No.44 above but size 65 mm dia. |
| 47 | All as per item No.44 above but size 50 mm dia. |
| 48 | Taking down old unsv Non return butterfly valve from existing location and supply and fixing new non return butterfly valve valve of size 100 mm dia and including necessary pipe fittings, nuts,bolts,washers and rubber washers etc complete all as specified and directed |
| 49 | All as per item No.48 above but size 80 mm dia. |
| 50 | All as per item No.48 above but size 65 mm dia. |
| 51 | All as per item No.48 above but size 50 mm dia. |
| 52 | Taking down old unsv pipe line from existing loaction and supply and fixing new MS ERW heavy duty pipe of size 100 mm dia with fittinmgs and including providing necessary fabrication,welding work and accessories nuts,bolts and washers complete all as specified and directed. |
| 53 | All as per item No.52 above but size 80 mm dia. |
| 54 | All as per item No.52 above but size 65 mm dia. |
| 55 | All as per item No.52 above but size 50 mm dia. |
| 56 | Taking down old unsv pipe line from existing loaction and supply and fixing new GI heavy duty pipe of size 100 mm dia with fittings and including providing necessary fabrication,welding work and accessories nuts,bolts and washers complete all as specified and directed. |
| 57 | All as per item No.56 above but size 80 mm dia. |
| 58 | All as per item No.56 above but size 65 mm dia. |
| 59 | All as per item No.56 above but size 50 mm dia. |
| 60 | All as per item No.56 above but size 40 mm dia. |
| 61 | All as per item No.56 above but size 32 mm dia. |
| 62 | All as per item No.56 above but size 25 mm dia. |
| 63 | Taking down old unsv gate valves from existing loaction and supply and fixing new gate valve of size 100 mm dia with necessary accessories nuts,bolts and washers complete all as specified and directed. |
| 64 | All as per item No.63 above but size 80 mm dia. |
| 65 | All as per item No.63 above but size 65 mm dia. |
| 66 | All as per item No.63 above but size 50 mm dia. |
| 67 | All as per item No.63 above but size 25 mm dia. |
| 68 | Taking down old unsv strainer for suction from existing loaction and supply and fixing new strainer of size 150 mm dia with necessary accessories nuts,bolts and washers complete all as specified and directed. |
| 69 | All as per item No.68 above but size 100mm dia. |
| 70 | Supply and install,testing and commissioning of monoblock pumpsets suitable for 415 volts 3 phase, 50Hzs,rpm 2880-3000 capacity of 10 HP including necessary suitable fittings such has flanges,reduced sokets, nipple, suitable water pressure guage 7 Kg or 10 kg X100 mm dia and replace old CI foot valve with GM working parts( IS-4037) 100/150mm dia, bend,Tee , nuts, bolts required at site and necessary threading,welding and drilling etc complete all as specified and directed by Engr-in -Charge. |
| 71 | Supply,install, Commissioning and testing of capacity of cooling tower 100 TR, one no twin cell type corrosion resistant,fire retardant,FRP induced draft,rectangular/square type counter flow cooling tower of capacity 120% of plant running capacity with maximium allowable temperature 50 degree centigrade,drift loss 0.005% of water circulation,such as 80TR,water flow rate USGPM-1500,Inlet temp-97.5F,outlet temp-90F,wet bulb temp-83F,FRP materials,suitable mechanical eqpt-hot dip galvanized UV stabilized,PVC piping work,incl aluminium fan hub and blades-06 Nos,suitable size blades,fan motor 5 HP,960 rpm, dry weight 500 kgs,operating weight approx 1750 kgs, size suitable for as existing,incl sprinklers and functioning required connected items and including removing old unserviceable complete all as specified and directed. |
| 72 | Supply and fix MCCB, 200 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed. |
| 73 | Supply and fix MCCB, 250 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed. |
| 74 | Supply and fix MCCB, 315 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed. |
| 75 | Supply and fix MCCB, 400 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed. |
| 76 | Supply and fix MCCB, 630 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 9 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender