Housing Urban and Rular Development Government Departments Closing in 1 days TDR #56523990

Tender For Construction Of Post-Operative Ward & Ot Block Of Khowai District Hospital Building At Khowai, Tripura/Sh:- Providing Internal Electrification Works Along With Fire Detection System Thereof.

Issued by Government Departments · Khowai, Tripura
Tender Value
14.26 Lakhs
Estimated cost
Bid Submission
29 Jul 2026
1 days left
EMD
28530
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Khowai → Tripura
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Construction Of Post-Operative Ward & Ot Block Of Khowai District Hospital Building At Khowai, Tripura/Sh:- Providing Internal Electrification Works Along With Fire Detection System Thereof.

BOQ

Name of Work:- Construction of Post-Operative Ward & OT Block of Khowai District Hospital Building at Khowai, Tripura/SH:- Providing Internal Electrification works along with fire detection system thereof.
Sl. No. Item Description
1Wiring for light/ fan/ exhaust fan/ call bell point with 2x1.5 sq. mm PVC insulated copper conductor cable (FR) in PVC conduit (medium gauge) recessed in slab/ wall complete with 6/10 amps modular type switch, cover plate, GI box including necessary connection etc. as required.(As per TSR-2021, Sl. No-401)
2Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2 x 1.5 sq. mm PVC insulated Copper conductor cable (FR) on modular concealed switch board with cover plate earthing the 3rd pin etc. as required. (As per TSR-2021 Sl. No.403)
3Providing and fixing of 3/6 pin 16 / 20 amps plug point with modular type 16/20 amps switch and socket including connection with 2 x 2.5 sq. mm PVC insulated Copper conductor cable (FR) on modular concealed switch board with cover plate earthing the 3rd pin etc. as required:- (As per TSR-2021 Sl. No.404)
4Wiring for Circuit/Sub-main with the following sizes PVC insulated Copper conductor cable (FR) in PVC conduit (medium gauge) recessed in slab/ wall etc. as required:- (As per TSR-2021, Sl. No.405)
52 X 2.5 + 1 X 1.5 sq mm
62 X 4 + 1 X 1.5 sq mm
72 X 10 + 1 X 4 sq mm
84 X 10 + 2 X 4 sq mm
94 X 16 + 2 X 6 sq mm
10Supplying and fixing of the following PVC conduit (medium gauge) with all accessories on slab/recessed on wall etc as required.:-(As per TSR-2021, Sl. No.603)
1119/20 mm dia
1225 mm dia
13Supplying & installation of metalic fan clamp box of standard size with 3mm thick bakelite/plastic cover as required:-(As per TSR-2021, Sl. No.823)
14Supplying and fixing of following surface/recess mounted LED luminaries in powder coated die cast housing complete with high efficiency polycarbonate diffuser and necessary connection etc. as required (with 50000 burning hours and minimum lumen output of 100 lm/watt):-(As per TSR-2021 Sl. No.1101)
15Surface mounted round/Square shaped 18/20 watt LED downlight with integral driver and high quality polycarbonate diffuser:-
16Surface mounted box type batten suitable for single 18/20 watt integrated LED tube lamp (without lamp):-
17Supplying and fixing of following LED Tubes, retrofit bulbs/lamps for LED luminaries including necessary connection etc. as required:-(As per TSR-2021 Sl. No.1103)
1818/20 watt LED tube with integral driver and polycarbonate diffuser (50000 burning hours and minimum lumen output of 100lm/watt):-
1920 watt LED retrofit lamp with polycarbonate body and aluminium heatsink :-
20Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resistant tempered glass/diffuser including necessary connection etc. as required (50000 burning hours and minimum lumen output of 100 lm/watt):-(As per TSR-2021 Sl. No.1102)
2145 watt LED street light fixture with integral driver and secondary lens (IP 66):-
22Supplying & fixing of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated Copper conductor cable(FR) (ISI marked, BEE 1 star/minimum service value 4.0 m3/min/W) : -(As per TSR-2017 Sl. No.802)
23Supplying & installation of 225/230 mm sweep metalic body exhaust fan including connection etc as required:-(As per TSR-2021 Sl. No.816)
24Supplying & installation of shutter for 225/230/300 mm sweep metalic body exhaust fan in the existing hole as required:-(As per TSR-2021 Sl. No.821)
25Making different sizes of hole in the wall for fixing of exhaust fan including finishing the same with cement plastering and painting etc as required:-(As per TSR-2021 Sl. No.831)
26Supplying and fixing of the following electrical accessories including necessary connection etc. as required.(As per TSR-2021, Sl. No.604)
273mm thick bakelite sheet
28Supplying and installation of powder coated steel sheet enclosure (MCB DB) suitable for 240/415 volts MCB/Isolator/RCCB (SP / SPN / DP / TP / TPN / FP)complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required.(As per TSR-2021 Sl. No.1208):-
292 way SPN MCB DB (single door):-
30(2+10) / 12 way SPN MCB DB (double door):-
316 way horizontal TPN MCB DB (Double door):-
326 way vertical TPN MCB DB suitable for FP MCCB incomer upto 125 amps (Double door):-
33Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required:-(As per TSR-2021 Sl.No.1215)
346 to 32 amps SP MCB:-
356 to 32 amps DP MCB:-
3640 amps DP MCB:-
3740/50/63 amps TPN MCB:-
38Supplying & installation of isolators of following ratings in the existing MCB DB including connection etc as required:-(As per TSR-2021 Sl.No.1217)
3940 amps DP isolator:-
40Supplying & installation of TP/FP MCCB of following ratings in the existing MCCB enclosure/ panel board including connection etc as required (Ics=100% of Icu with adjustable settings):-(As per TSR-2021 Sl.No.1219)
41125 amps FP MCCB, Breaking capacity 25KA (Thermal Magnetic) :-
42Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required:- (As per TSR-2021 Sl.No.1201)
4363 amps 415 volts four strip Copper busbar chamber 4 ways of size (330mmx280mmx100mm):-
44Supplying & installation of Surge Protection Device (SPD) of following ratings in the existing Panels/MCB DBs including necessay connections etc as required:- (As per TSR-2021 Sl.No.1216)
45Surge Protection Device (SPD, withdrawable) (Type-2) with Imax 70 KA (3P+N) :-
46Catridge for Surge Protection Device (SPD) (Type-2) with Imax 70 KA (1P+N/3P+N) :-
47Supplying and fixing of the following modular accessories including necessary connection etc. as required. (As per TSR-2021 Sl.No.609)
4820/25 amps single phase motor starter switch (2M):-
495 step fan regulator (2M):-
506/10 amps one way SP switch (1M) :-
51Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\\"x 12\\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:-(As per TSR-2021, Sl. No.703)
52Extra for using salt (12 kg) and charcoal (96kg) for plate earth electrode as required.(As per TSR-2021,Sl. No.705)
53Supply and fixing of 25 x 3mm copper strip on wall/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals:-(As per TSR-2021 Sl. No.714)
54Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement- 1:2:4 ( 1 Cement: 2 fine sand : 4 graded well burnt brick aggregate 20 mm nominal size):-(As per TSR-2021 Sl. No.1509)
556 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete. In cement mortar 1 : 4 ( 1 cement : 4 fine sand ):-(As per TSR-2021 Sl. No.1521)
56Neat cement punning:-(As per TSR-2021 Sl. No.1522)
57Supplying and fixing of MS frame made of (25mm x 25mm x 5mm) MS angle with necessary support by (40mm x 6mm) MS flat and 12 mm thick marine plywood on top, grouted on wall with 4 nos legs (25mmx25mmx5mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required:-(As per TSR-2021 Sl. No.1502)
58Supplying and laying of following sizes XLPE insulated PVC sheathed Aluminium conductor Un-armoured cable including necessary connection etc as required.(As per TSR-2021 Sl. No.1302)
593 core 4 Sq mm
60Drawing of armoured/un-armoured cable with proper saddling etc as required:-(As per TSR-2021 Sl. No.1511)
61Supplying & fixing of G.I. pipe (medium gauge) bracket fabricated at suitable angle for fixing of outdoor light on wall/ RCC base with necessary MS clamp, nut, bolt etc as required:-(As per TSR-2021 Sl. No.1501)
6225 mm dia
63Supplying, installation, testing and commissioning of following ratings true online double conversion UPS with IGBT based rectifier and inbuilt isolation transformer, 50/60Hz (Auto sensing) frequency, unity P.F, voltage regulation +/-1%, Pure sine wave form, total harmonic distortion < 5% with full load, Noise level 50db at 1m, LED indication for Normal mode/Load on battery/Load on bypass/System fault, Audible alarm for Mains failure, low battery, Overload, fault and Bypass mode complete with necessary battery bank, M.S Rack for mounting battery bank, Battery inter link cables and all other necessary accessories including connections etc. as required:- (Ref. Agreement No: 92/EE/IED/AMB/2025-26)
645kVA/5KW, 240 VDC 1Ph input/1Ph output Online UPS with 20 nos of 12V, 65Ah SMF VRLA Battery bank with (for 2hrs Backup) etc.as required:-
65Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- (As per TSR-2021, Sl. No.503)
662 X 1.5 sq mm
67Supplying, installation, testing & commissioning sector panelsuitable for following zones, complete with visual indications forshort circuit fault, open circuit fault, fire condition and allotherstandard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections,interconnections as required.(As per TSR-2021 Sl. No.1709)
684 Zone
69Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with allconnections etc. as required. (As per TSR-2021 Sl. No.1702)
70Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required (As per TSR-2021 Sl. No.1703)
71Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S.box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. (As per TSR-2021 Sl. No.1706)
72Supplying and installation of secure zone 4 kg ABC powder fire Extinguisher gross weight 6.38 kg, empty weight 2.38 kg, can height 372 mm, diameter 150 mm, discharge time minimum 13 seconds , discharge mechanism - squeeze grip type range minimum 2 meters applicable on class A,B,C and electrically started fire, A rating- 2A, raring-55B, can contrast- mig welded,valve construction- forging & machining, external coating of can..epoxy polyester powder coating, sheet metal thickness. 1.60mm, conforms to BIS standards, 5 years warranty(make. ceasefire/secure/fireshield) (Ref. Agreement no: 92/EE/IED/AMB/2025-26):-
73Supplying and fixing of thermoplastic cable junction box with connectors suitable for following sizes cable : -(As Per TSR 2021, S.L No.1405)
741.5 sqmm - 4 sqmm Cable:-
75Supplying and fixing of Copper terminal ends (LUGS) - long barrel of following sizes: -(As Per TSR 2021, S.L No.1402)
762.5 sq mm:-
774 sq mm:-
7810 sq mm:-
7916 sq mm:- Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56523990
AUTHORITY Government Departments
TENDER VALUE 14.26 Lakhs
LAST DATE 29-07-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction Of Post-Operative Ward & Ot Block Of Khowai District Hospital Building At Khowai, Tripura/Sh:- Providing Internal Electrification Works Along With Fire Detection System Thereof.
Basic Detail
Tender No 25/EE-IED/AMB/2026-27
Bidding Type Tender
Location
City Khowai
State Tripura
Key Dates
Publish Date 17 Jul 2026
Submission Date 29 Jul 2026
Open Date 30 Jul 2026
Finance
Tender Value 14.26 Lakhs
Tender Fee 1000
EMD 28530
Exemption Available
Document List
6088fd1e-e6ed-4ed5-baad-bbee8bb5a9be.html
BOQ_76129.xls
DNIeT25.pdf
Tendernotice_1 (17).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 29, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Jul 30, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 2 days

Tender Documents

Download All (ZIP) ↓
html

6088fd1e-e6ed-4ed5-baad-bbee8bb5a9be.html

xls

BOQ_76129.xls

pdf

DNIeT25.pdf

pdf

Tendernotice_1 (17).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender