Tender For Provn Of Deficient Living Accn For Officers And Airmen At 47 Su (Spl Work) Under Ge (Af) Chiloda
Tender Overview
Project Description
Tender for Provn Of Deficient Living Accn For Officers And Airmen At 47 Su (Spl Work) Under Ge (Af) Chiloda
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-Jul-2026 | Corrigendum1 | Date | 18-Aug-2026 |
| 2 | 08-Aug-2026 | Corrigendum2 | Date | 27-Aug-2026 |
| 3 | 27-Aug-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 03-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | BOQ 82324/CHL/E8 BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CWE (AF) CHILODA Name of Work: PROVN OF DEFICIENT LIVING ACCN FOR OFFICERS AND AIRMEN AT 47 SU (SPL WORK) UNDER GE (AF) CHILODA CA No : CWE (AF) CHILODA /CHL / OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | NOTE: Schedule ‘A’ Part I to X under Ser No. 1 to 10 here in after are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 3 | Lump sum price worked out for BUILDING/ STRUCTURE as listed in Sch 'A’ Part I. |
| 4 | Lump sum price worked out for EXCAVATION & EARTH WORK as listed in Sch 'A’ Part II. |
| 5 | Lump sum price worked out for INTERNAL WATER SUPPLY as listed in Sch 'A’ Part III. |
| 6 | Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch 'A’ Part IV. |
| 7 | Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch 'A’ Part V. |
| 8 | Lump sum price worked out for AREA DRAINAGE as listed in Sch 'A’ Part VI |
| 9 | Lump sum price worked out for ROAD/ PATH / HARDSTANDING as listed in Sch 'A’ Part VII. |
| 10 | Lump sum price worked out for EXTERNAL WATER SUPPLY as listed in Sch 'A’ Part VIII |
| 11 | Lump sum price worked out for EXTERNAL ELECT SUPPLY as listed in Sch 'A’ Part IX |
| 12 | Lump sum price worked out for DEMOLITION AND DISMANTLING as listed in Sch 'A’ Part X |
| 13 | Lump sum price worked out for COMPOUND WALL as listed in Sch 'A’ Part XI |
| 14 | Lump sum price worked out for HOT WATER SUPPLY AND SOLAR HOT WATER as listed in Sch 'A’ Part XII |
| 15 | SCHEDULE `A' PART-XIV (MISCELLANEOUS ITEMS)(Note for following items- The contractor shall quote his rate for each of these items separately. The estimated rate is left blank since the same is not prepriced by MES) |
| 16 | SEWAGE DISPOSAL |
| 17 | S&F DWCPE (SN8) 200 (OD)/175(ID) mm diameter pipes laid on 150 mm thick PCC bed 1:4:8 with excavation in any type of soil at depth 0.7 m - 1.65 m deep , incl manholes/drop manholes of standard size made of Brick masonry/RCC with SFRC ventilating cover and frame includes all items and activities to execute and make sewer line functional complete all as specified and as directed. |
| 18 | EXTERNAL WATER SUPPLY |
| 19 | M&L for Brick masonry valve pit of size 600x600x700mm with necessary excavation and earth work, PCC 1:3:6 type C2 in foundation, brick work with old size brick in CM 1:6, 15 mm thick rendering in CM 1:4 (internally), 5mm thick MS plate cover including M.S angle iron 50x50x5 frame including material & labour for preparation of new iron surface & applying two coats of synthetic enamel paint over a coat of red oxide primer with and including locking arrangement complete all as specified and all as directed by Engr-in-Charge |
| 20 | EXTERNAL ELECTRIFICATION |
| 21 | Supply ,fabrication, installation and testing of LT Panel factory made, TypeTest Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, out door type, weather proof, water proof, dust proof, vermin proof, shock proof IP 65 protection made out CRCA seet 3.15 mm thickness of suiitable size accommodate accessories with front and back double door opening/ lockable by the key from both side and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC /Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) . All extension link/ inter connection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories. Note: - Cost of earthwork and PCC work etc are deemed to be included in quoted rate of this item. |
| 22 | IN COMING: -(a) Copper strip busbar of 500 amps rated capacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrographic insulators with nuts & both at both ends = 04 Nos(b)4 pole MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links-01No.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, Ac -01 set (set of three) (d) Digital Ammeter of range (0-250) Amps, flush mounting type with CT’s of ratio 250/5 and selector switch -01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch -01 No. |
| 23 | OUT GOING: -(a) 4 pole MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links -02 Nos(b) 4 pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links -02 Nos(c) MCB TPN 32 Amps with breaking capacity 10KA-02Nos(d) Multifunctional digial type timer Switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase -01 No.(e) Power contractor 4 Pole, 32 Amps, 415 Volts, 50 HZ -01 No(f) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200mm x 150mm, white with letters figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/shutter of LT panel-01 No |
| 24 | Supply ,fabrication, installation and testing of LT Panel factory made, TypeTest Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, out door type, weather proof, water proof, dust proof, vermin proof, shock proof IP 65 protection made out CRCA seet 3.15 mm thickness of suiitable size accommodate accessories with front and back double door opening/ lockable by the key from both side and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC /Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) . All extension link/ inter connection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories .Note: - Cost of earthwork and PCC work etc are deemed to be included in quoted rate of this item. |
| 25 | IN COMING: -(a) Copper strip busbar of 500 amps rated capacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrographic insulators with nuts & both at both ends = 04 Nos(b)4 pole MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links-01No.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, Ac -01 set (set of three) (d) Digital Ammeter of range (0-250) Amps, flush mounting type with CT’s of ratio 250/5 and selector switch -01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch -01 No. |
| 26 | OUT GOING: -(a) 4 pole MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links -02 Nos(b) 4 pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics=100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links -02 Nos(c) MCB TPN 32 Amps with breaking capacity 10KA-02Nos(d) Multifunctional digial type timer Switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase -01 No.(e) Power contractor 4 Pole, 32 Amps, 415 Volts, 50 HZ -01 No(f) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200mm x 150mm, white with letters figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/shutter of LT panel-01 No |
| 27 | S & F Security light junction box of size 200 x 140 x 95 mm for luminaries, weather proof made out of polycorbonate housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole/ wall mounting type comprising of MCB SP 10 Amps, fixed on PCC foundation with screws complete all as specified and as directed. |
| 28 | M&L for Boring of holes under road not less then 0.6mtr depth and 90mm dia hole by trenchless mannual boring by using augar and laying of necessary GI pipe of suitable dia including jointing and cable pulling all as specified. |
| 29 | M & L for maintenance free technology Chemical earthing with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 30 | Note:- (i) Earthing is to be done infront of the Engr-in-Charge. (ii) Test Results of earthing to be submitted by the contractor for all earthings.(iii) The Contractor shall have to give written guarantee for maintenance earth resistance of less than 1.0 Ohm for the period of 10 (ten) years after certified date of completion and shall be deposited 2000/- per earthing as security deposit for a period of Ten (10) Years.(iv) Failing to maintain resistance of earthing less than 01.0 ohm , new earthing to be provided by the contractor with out any extra cost to Govt.(v) Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surrounding area shall be deemed to be included in quoted rate complete. |
| 31 | FIRE FIGHTING |
| 32 | S & F 3 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the Engineer-in-Charge. |
| 33 | S & F 5 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the Engineer-in-Charge. |
| 34 | S & F 9 litre capacity mechanical foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete (In Parking Area) all as specified and directed by the Engineer-in-Charge. |
| 35 | S & F 9 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete (1 No. at entry/exit )all as specified and directed by the Engineer-in-Charge. |
| 36 | S & F Galvanized mild steel Fire bucket of size as directed by Engr-in-Charge (Filled with dry sand & water) conforming to IS 2546: 1974 round bottom type enamel painted, white inside & Red out side and Letter \\"FIRE\\" in black out side and handle with mounting bracket complete as specified and directed by the Engineer-in-Charge. |
| 37 | S & F Galvanized mild steel Fire hook bracket with 3 mtr bamboo handle painted with red colour complete as specified and directed by the Engineer-in-Charge. |
| 38 | S & F Galvanized mild steel Fire breather bracket with 3 mtr bamboo handle painted with red colour complete as specified and directed by the Engineer-in-Charge. |
| 39 | M & L for Fire point constructed with angle iron frame mounted on PCC platform with PCC 1:3:6 type C1 and covered with GI Sheet of size/ thickness as directed by Engr-in-Charge and painted with red colour and letter \\"FIRE\\" in top of shed complete as specified and directed by the Engineer-in-Charge. |
| 40 | INTERNAL ELECTRIFICATION |
| 41 | M&L for testing and commissioning (SITC) of Modular Type Air Conditioner Control Box consisting of FR-grade modular enclosure, 20A/25A Double pole (DP) Isolator, 20A/25A DP MCB (C Curve) 10 KA Breaking Capacity, LED Power indication lamp, suitable busbar, terminals, internal wiring earthing arrangement, gland and all necessary accessories, complete as required for operation of split air conditioner units up to 2.0 TR capacity. |
| 42 | M&L for installation, testing and commissioning of Vertical TPN Distribution Board (Double Door DB) suitable for 415V,3 phase, 4 wire, 50Hz AC supply system fabricated from CRCA Sheet steel,powder coated , wall mounted/floor mounted as required , complete with busbars , neutral link, earth bar, gland plate, wiring and all accessories complete all as specified and directed. |
| 43 | S & F LED batten fitting alongwith removable LED Tube 20W, 230 Volt, wall /ceiling mounted ,LED batten fixed by means of bolts,ABS rotor suitable for single side connections. LED rod having glass material complete haivng lumen efficacy minimum 100 lm/w,CCT 6500 K, CRI>80 ,burning hour minimum 25000,PF - 0.9 powered by integral constant current driver suitable for 230 V AC with all accessories internallly prewired including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 44 | Supply & fix LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type100 lm/w,CCT 6500 K, CRI>80 ,burning hour minimum 25000, PF - 0.9, with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. |
| 45 | Supply and fixing (BLDC) ceiling fans complete with blades down rods remote control unit with battery 02 Nos and accessories 230 Volt 1200 mm sweep min air delivery 240 cu m/min with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) all as specified and directed. |
| 46 | M&L for PVC box flush mounted 100mm x 100 mm x 100mm having holes for 20mm conduit entry including 2 pin TV socket outlet flush type duly marked with symbol of TV and 3 mm thick plastic laminated sheet cover complete for telephone connection all as specified |
| 47 | Supplying, installing, testing and commissioning in replacement of indoor type totally enclosed weather ,dust & vermin proof CPRI approved factory made LT wall mounted meter panel board 415 volt, 3 phase, 4 wires,AC,50 Hz fabricated from 2.00 mm thick CRCA sheet steel and epoxy powder coating in RAL 7032 shade with seven tank treatment process, front opening hinged door with a fully transparent cover made of polycarbonate/high grade engineering plastic to permit clear view of display, locking arrangement, Aluminum busbar 250 amp ,20 mm x 5 mm insulated with heat shrinkable sleeves, appropriate space for fixing single phase energy meter 05 Nos, hold fast/fastener/bolts/copper lugs/spacers/terminal blocks, rubber gasket, locking knobs, phenolic laminated sheets for live isolation ,heat shrinkable sleeves, nuts, bolts, washers, connections from MCCB to busbar, busbar to meter & meter to MCB with single core copper cable of size 6.0 sqmm connection , R- Y-B LED indications to show 3 phase availability at incomer including the following :- |
| 48 | (a) 01 Nos (in coming) MCCB 63 Amps , 415 volts,4 pole, 16 KA, thermally adjustable between 70 to 100 % all as per legrand cat Ref no-4200 03 /CG/ L&T/Standard(b) Temper proof electric meters single phase -02 Nos only alongwith sealing, making sticker of Qtr No in suitable size for identification etc all as directed by engr -in charge)(c) 2 numbers MCB DP 40 Amp,10 KA, 'C' series as approved ( one number in each outgoing side of meter) Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
TodayBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender