Power Government Departments Closing in 7 days TDR #56520610

Tender For Construction Of New 33/11 Kv Sub- Station Fauladpur & 33 Kv Line And 11 Kv Inter Connection Under Aen(Htm), Jpd, Behror In The Jurisdiction Of Kotputli Circle Of Jaipur Discom.

Issued by Government Departments · Jaipur, Rajasthan
Tender Value
12.54 Lakhs
Estimated cost
Bid Submission
30 Jul 2026
7 days left
EMD
25088
Bank guarantee accepted
Document Fee
2950
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of New 33/11 Kv Sub- Station Fauladpur & 33 Kv Line And 11 Kv Inter Connection Under Aen(Htm), Jpd, Behror In The Jurisdiction Of Kotputli Circle Of Jaipur Discom.

BOQ

Name of Work:- Construction of New 33/11 KV Sub- Station Fauladpur & 33 KV Line and 11 KV Inter Connection under AEN(HTM), JPD, Behror in the jurisdiction of Kotputli circle of Jaipur Discom.
Sl. No. Item Description
133/11 KV S/S
2Grass cutting and surface dressing including removal of unwanted/rubbish plants with roots from open ground /yard and other Nigam premises with stacking of grass/plants at desired place near the ground.
3Levelling of ground
4Levelling of ground above 30 cm.to 90 CM.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting)
5Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13).
6(A) Height of poles/R.S.Joist/M.S. Rail Size of pit
79 Mtr/ 1.2mx0.6mx1.50 m deep
8Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms .Liftup to 1.5 Meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 Meter.
9Hard soil mixed with boulders
10Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate mix.
11The rates are all lead of cement,lime,ballast, sand,surkhi and grit etc.at site of work.
12For all concrete work coarse sand shall be used no extra will be paid .
13Concrete mix prepared by power driven mechanical mixer shall be used .
14Under exceptional coditions, where mechanical mixer and vibrator are not used(with the approval of Engineer Incharge reduced by 3% for mechanical mixer and 2% for Vibrator
15Thickness of the cement concrete should not exceeed 100 mm.
16Plaster on new surface on walls in cement ,sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick.
17The rates for complete work including racking of joints,curing,grinding,mixing and finishing T&P and scaffolding material and cost of material with all lead and lift.
18The rates cover protection of all place and things,requiring protection and cleaing such places and thing of all droppings and splashes of mortar etc.
19Masonry for foundation and plinth
20Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges.
21Safe carriage of PCC poles including loading / un-loading
22a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole
23Within 10 Kms.
24Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 4.75*10
25Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site
26Within 10 Kms.
27Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 4.61*10
28Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc.
29Within 10 Kms.
30Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 5.57*10
31Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading from store to site (these Charges will be 1.5 times for both sides)
32a) 10 & 16 KVA
33Above 10 Kms. & upto 30 Kms Add for each Km.or part [email protected]*10
34b) 25 & 40 KVA
35Within 10 Kms.
36Safe Carriage of 33/11 KV Power Transformer
37a) Upto 1.6 MVA
38Within 10 Kms
39Above 10 Kms & upto 30 Kms . Add for each Km or part thereof
40Above 30 Kms & upto 50 Kms . Add for each Km or part thereof
41Above 50 Kms . Add for each Km or part thereof
42Safe loading of power/ distribution transformer.
43(A) 33/11 KV power transformer.
445 MVA
45Safe unloading of steel fabricated/ unfabricated conductor drum & other line material.
46a) 33/11 KV power transformer.
47Above 3.15 MVA
48Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base.
49Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station.
50Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1 Nos. disc & 1 set of H/W ) on terminal point including fixing of hardware and strips.
51Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 Nos. disc.& 1set of H/W) on terminal point including fixing of hardware and strips.
52Fixing of 33kv pin insulator with pins.
53Fixing of 11 KV pin insulator with pins.
54Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.
5533kv G.O.switch
5611kv G.O.switch
57Assembly and installation of Horn Gap fuse set (set of 3nos)on erected structure as per design, complete in all respectwith post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.
5833kv Horn Gap fuse set.
5911kv Horn Gap fuse set.
60Installation testing as per Nigams norm & commissioning of 11/0.4KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates,
6125 and 40 KVA
62Fixing of PG clamp of Dog /Racoon Conductor
63Installation of lightening arrestors on erected structure /support (1 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates,
64(A)sub-station type
6533 KV L.A. each
66Assembly,installation & commisioning of 11 KV Roaster switchs on erected structures with stting for accurate operation including fixing of allied accessories completed in all respect with post insulators and jumpering on both ends for connection with systm.The nuts & bolts will be supplied by contractor for which payment will be made as per prevailing Dicom store issue rates.
67Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.
68(A) IN URBAN AREA
69ACSR DOG
703 Nos. of earthing of 11/0.4 KV distribution transformer /sub-station with 3 pieces of M.S.Rod 20mm dia each 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16\\" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm (having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence.
71Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder:
72Excavation of trench of 0.65 Mtrs.depth and 0.5 Mtr.width
73Ordinary rock ( where blasting is not required.)
74Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust.
75Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust.
76Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil:
77Where drilling is required
78Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates.
79(B) IN RURAL AREA
80PCC Poles 9 Mtr. Long
81Laying / stringing of bus bar with ACSR Dog & jumper connection using tie rod ,33KV /11KV insulator strings,required hardware,P.G.clamps/T clamps etc.as per requirement including Y-connections at bus bar jumpering point as per the direction of engineer in-charge.
82ACSR DOG/RABBIT
83Installation of metering points on 11 KV Out going feeder at 33/11 KV S/S.
84The installation work to be carried out as per drawing/design, under the supervision of concerned Assistant Engineer
85Mounting structure
86The requisite steel members will be supplied by contractor including the hardware. Contractor shall joint/weld the members to form the mounting structure as per drawing. Necessary tools, welding, machines, lifting devices etc. shall be arranged by contractor.
87Civil works
88Erection of lattices in alignment including excavation and concreting of structure foundation including cement, sand and grit 20 mm size (crusher broken) having ratio 1:3:6 and grit 40 mm size for ratio 1:5:10 and curing for period as required (21 days). Area of concreting will be as per the drawing.
89Metering Equipments:
90The requisite metering equipments (CTPT set, meter,meter box & suitable conductors for jumpers), will be provided by the concerned Assistant Engineer in healthy condition at site. The cables from CTPT set to meter box laid down in 50 mm GI pipe with suitable bends & nipples, shall be provided by contractor alongwith the consumable items such as PVC tapes, petroleum jelly etc. The cable should be PVC multi strand copper 4 core 2.5/4 Sq. mm ISI marked and firm & tight connections shall be made by suitable connector e.g. at CTPT sets by using clamps and at meter/TTB by suitable lugs etc. The CTPT sets so installed shall be earthed by means of the MS Flat (size 50x6 mm) by joining it with the nearest earthing available at the sub-station. Requisite earthing material shall be made available by the contractor.
91Meter:
92Meters should be fixed firmly inside the tamper proof box, as per drawing. All the meter fixture will be provided by contractor including all consumables.
93Meter Box
94The meter box shall be provided by the concerned Assistant Engineer. However, hardware or any other items required to fix the meter inside the meter box will be provided by contractor. The meter box will be fixed firmly with sufficient strength at a place as per drawing. The test terminal block(TTB) link type shall be provided by contractor in the meter box.
95Painting:
96All surfaces interior and exterior of lattice structure shall be white aluminum painted.
97Commissioning of Metering Equipments:
98Installed meters inside the box and metering equipments duly mounted on the mounting structure will be powered up by connecting load in the presence of the concerned Assistant Engineer who will arrange the necessary shut down. The completion certificate shall be furnised by contractor.be filled accordingly. Since the work involves higher A.C. voltage level, the contractor shall take full care regarding safety norms, so as to avoid any accidental hazards.
99Laying, testing termination of control cable 1100 volts PVC insulated including supply and installation of ferrules to designate various cores of control cables by terminal Nos. of identification including utilization of cable gland. The control cable should be clearly arranged in trenches avoiding crossings including clamping of control cable at regular interval and providing identify tags.
1002x2.5 Sq.mm.
1014x2.5 Sq.mm.
10212x2.5 Sq.mm.
1034x4 Sq.mm.
104Fabrication of steel structures of M.S angle, M.S.channel & M.S.Flat including cutting, drilling as per design and drawing.
10533/11 KV Rural Sub-Station Structure (4086.879 Kg)
106Drilling of holes in MS Channel / Angle /Flat
10711/16\\" dia holes(17.46 mm dia.)
10833KV LINE
109Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13).
110(B) Lattice Tower /Size of pit
11112.8/12.6 Mtr/ 1.5mx1.5m x2.10 m deep
112(C)Stay set/Depth of pit
1138'x 3/4\\" -0.75x0.5x1.6 m
114Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site
115Within 10 Kms.
116Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 4.61*10
117Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc.
118Within 10 Kms.
119Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ (5.57*10)
120Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site.
121Within 10 Kms.
122Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 4.61*10
123Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. The cost muffing and grouting will be paid extra.
124Lattice Structure
125Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire
1268\\"x3/4\\" with 7/8 SWG stay wire
127Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base.
128Supplying and laying of randum rubble stone boulder having weight not less than 20 kgs.
129Fixing of PG clamp of Dog /Racoon Conductor
130Fixing and assembly of disc.point channel pair with pilot plates top hampers & clamps on erected single pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates,
13133 KV line
132Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 Nos. disc.& 1set of H/W) on terminal point including fixing of hardware and strips.
133Fixing of 33kv pin insulator with pins.
134Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.
135(A) IN URBAN AREA
136ACSR DOG
137Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.
138(B) IN RURAL AREA
139G.I.Earth wire 6 SWG
140Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom)
141Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil:
142Where drilling is required
143Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide)
144On new surface
145Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint)
146On new works with two coats.
14711KV INTERCONNECTION
148Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line.
149Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13).
150(A) Height of poles/R.S.Joist/M.S. Rail Size of pit
1519 Mtr/ 1.2mx0.6mx1.50 m deep
152(C)Stay set/Depth of pit
1536'x 5/8\\" -0.75x0.5x1.35 m
154Safe carriage of PCC poles including loading / un-loading
155c) 9 Mtr.long 200 Kg. PCC pole
156within 10 Kms.-
157Above 10 Km. & upto 30 Km. add for each Km. or part thereof @ 4.75*10
158Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site
159Within 10 Kms.
160Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ 4.61*10
161Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc.
162Within 10 Kms.
163Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof. @5.57*10
164Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates.
165(B) IN RURAL AREA
166PCC Poles 9 Mtr. Long (400 Kg)
167Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates.
168PCC Poles 9 Mtr. Long(200 Kg.)
169Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire
1706\\"x5/8\\" with 7/10 SWG stay wire
171Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1 Nos. disc & 1 set of H/W ) on terminal point including fixing of hardware and strips.
172Fixing of 11 KV pin insulator with pins.
173Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.
174ACSR RABBIT
175Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.
176(B) IN RURAL AREA
177G.I.Earth wire 8 SWG
178Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil:
179Where drilling is required Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56520610
AUTHORITY Government Departments
TENDER VALUE 12.54 Lakhs
LAST DATE 30-07-2026
Authority
Authority Name Jaipur Vidyut Vitran Nigam Limited
Work Description Tender for Construction Of New 33/11 Kv Sub- Station Fauladpur & 33 Kv Line And 11 Kv Inter Connection Under Aen(Htm), Jpd, Behror In The Jurisdiction Of Kotputli Circle Of Jaipur Discom.
Basic Detail
Tender No JPD/ZCE(JZ)/TN-200
Bidding Type Tender
Location
City Jaipur
State Rajasthan
Key Dates
Publish Date 17 Jul 2026
Submission Date 30 Jul 2026
Open Date 31 Jul 2026
Finance
Tender Value 12.54 Lakhs
Tender Fee 2950
EMD 25088
Exemption Not Available
Document List
41010957-4b37-4914-bb4c-b920d5c96c1b.html
BOQ_1023376.xls
Tendernotice_1 (29).pdf
TENDERSPECSTN200.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 30, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 7 days
Jul 31, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
html

41010957-4b37-4914-bb4c-b920d5c96c1b.html

xls

BOQ_1023376.xls

pdf

Tendernotice_1 (29).pdf

pdf

TENDERSPECSTN200.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender