Tender For Repair/ Maint/ Renewal Of Perimeter Lights, Street Light, Security Lights, Post Top Lanterns, Garden Lights, Gate Lights Including Control Panels, Illumination Sys, Dg Set, Cranes And Misc Installations, External Fire Fightning Sys, Incl A
Tender Overview
Project Description
Tender for Repair/ Maint/ Renewal Of Perimeter Lights, Street Light, Security Lights, Post Top Lanterns, Garden Lights, Gate Lights Including Control Panels, Illumination Sys, Dg Set, Cranes And Misc Installations, External Fire Fightning Sys, Incl Attending Breakdown And Day To Day Complaints At Unchibassi Under Ge South Pathankot
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-Aug-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 13-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Material, labour , testing & commissioning of straight through jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 6 to 50 Sqmm 3.5/4 core with working voltage 1100 volts complete all as specified and directed. |
| 2 | M&L for GI pipe light grade 40 mm dia for cable protection on road crossings /plinth protection with fixed to the pole wall etc. suitable fittings for cable protection complete all as specified and directed. |
| 3 | Taking down defective LED street light fitting of any size/capacity from height of pole/walls/high mast of any location exceeding 7.0 m height for repair work and re-fixing back after repair work including checking, inspecting, testing and commissioning complete all as directed by Engr-in-Charge.Note: a) The M/L for Items like electronic drivers, surge protection devices etc. shall be measured and paid separately under relevant items here in under this Schedule. b) Necessary tools like ladders & other T&P required etc. shall be arranged by the Contractor. c) The rate quoted deemed to be inclusive for minor parts nut bolts, circle clips, clamps etc. if any required at site. d) The M/L for repairs to LED panel is not included in the scope and shall be measured and paid separately. |
| 4 | S&F in repair new automatic street light timer switch for LED street light using infrared sensor based nature switch for automatic switching of street light 230 volt, single phase of cap 5-8 KW outdoor type factory made IP-65 protection having nature switch operating should be based on natural light flux level and selector switch to change the mode of operation supply indicator with including SMC box and locking arrangement. the sensor alongwith power contactor of Cap 40 Amp and incoming and outgoing MCB TPN Cap upto 40 Amp with auto manual operation and overvoltage and overcurrent protection and auto trip & auto reset making arrangement incl internal wiring of copper cable FRLS 10 Sqmm single core multistranded and mounted arrangement with clamp and nut bolt on wall/pole, dust proof and temper proof complete all accessories as required and provided by manufacturer complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply and fixing in repair Electronic driver potted type IP-65, suitable for 90 to 120 W LED light fitting complete all as specified and directed. |
| 6 | Supply and fixing in repair Electronic driver potted type IP-65, suitable for 70 to 80 W LED light fitting complete all as specified and directed. |
| 7 | Supply and fixing in repair Electronic driver potted type IP-65, suitable for 30 to 60 W LED light fitting complete all as specified and directed. |
| 8 | Supply and fixing in repair Surge protection device of capacity 10 KV suitable for LED light fitting complete all as specified and directed. |
| 9 | Disconnecting from electric supply and remove from bracket/pole and dismantling LED light fitting of capacity 25 to 120 W, by strip opening the electronic driver, LED panel complete, identifying defective LEDs, make it functional by complete soldering, replacement of pitted control wiring from LED panel to driver etc. complete, including testing and commissioning all as specified and directed. |
| 10 | Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with PC cover in frame,(with total lumen output not less than 2500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 30 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items. |
| 11 | Taking down old unserviceable security light fittings roadway luminaire type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with PC cover in frame,(with total lumen output not less than 4500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) Min 45 watt roadway luminaire type with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 12 | Taking down old unserviceable security light fittings roadway luminaire type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with PC cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 13 | Taking down old unserviceable security light fittings roadway luminaire type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 72/70 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 14 | Taking down old unserviceable street light fittings from any height and Supply & fixing LED street light fittings comprising of epoxy powder coated housing, enclosed with cover in frame, with lumen output not less than 9000 lumens suitable wattage for efficiency not less than 100 lumens/Watt, min wattage 90 watt, with ingress protection IP 65 and SPD of capacity 10 KV etc. complete and testing on completion all as specified and directed. Note: The GI pipe if required bracket will be measured and paid separately under relevant schedule items |
| 15 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 15000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 150 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. |
| 16 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 20000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 200 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. |
| 17 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc. incl necessary clamps etc. complete and testing on completion all as specified and directed. |
| 18 | Dismantling old un-serviceable flood light fittings from any position exceeding 7.5 m height, Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame LED type (with total lumen output not less than 10000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 100/120 watt, with ingress protection IP 65 and surge protection device of 10 KV capacity etc. incl necessary, angle iron supports , clamps etc. complete and testing on completion all as specified and directed |
| 19 | Supply & fix replacement decorative path way light lighting LED decorative post top lantern for 360 degree 40 watts 230 volts, 50 HZ, maple shaped in soothing opal/ prismatic finish made up of polycarbonate, including all accessories prewired complete all as specified and directed. Note for serial item No. 10 to 19 :- (i) Minimum 2 years guarantee period of LED fittings (ii) Driver shall be IP 66 degree of protection potted seal type. (iii) Power factor more than 0.9 |
| 20 | S&F in repair PVC insulated 3 core 1.0- 2.5 Sq mm stranded Copper conductor cable for connecting OH line/junction box to street light fitting testing and commissioning complete all as specified and directed. |
| 21 | Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings complete all as specified and directed. |
| 22 | M&L for earthing complete with galvanized steel earth plate electrode 60cmX60cm X6mm thick buried directly in ground (earth plate not less than 2.25 mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized earth lead wire of 4.0mm dia by means of nuts bolts, washers, check nuts of iron or steel including PCC pits and RCC cover in PCC 1:2:4 (type B-1) and necessary earth work in any type of soil medium grade GI watering pipe 20 mm dia with funnel and wire mesh and 15mm bore GI pipe light grade protection pipe upto test point etc including excavation and charcoal, common salt surrounded with 15cm all around the plate all as specified and shown in EP-3 of SSR Part-I. all specified. |
| 23 | M&L for bracket for street light fitting made out of 40 mm bore pipe light grade GI tube bent to shape required, not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc. complete including dismantling old defective. |
| 24 | M&L for bracket for street light fitting made out of 25 mm bore pipe light grade GI tube bent to shape required, not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc. complete including dismantling old defective. |
| 25 | M&L for preparation of old painted steel surfaces of 9 m long steel poles incl removing oily/greasy spots and applying one coat of aluminium paint complete including applying a coat of white wash on pole coping and lettering the pole details with white letters/ background etc. complete all as directed |
| 26 | Repairs to High Mast/mid mast pole motor of Capacity 1.0 HP/0.75 KW 415 Volts 50 Hz 3 Phase 930 RPM and necessary rewinding with super enamelled copper wire all as per existing and servicing/greasing of reduction gear box complete all as specified and directed by Engr-in-Charge. |
| 27 | Decarbonizing of the control panel of High mast/Mid mast and including servicing of parts such as contactors/timers including replacement of pitted lugs, thimbles, control wiring etc. complete including painting with a coat of synthetic enamel paint. |
| 28 | S & F in repair 3 pole power contactor with coil voltage 230 volt AC of current carrying capacity 32 to 40 Amps complete including control wiring thimbles etc. complete all as specified and directed. |
| 29 | M&L for preparation of old painted surfaces of 9 m long PCC poles incl removing oily/greasy spots and applying one coat of synthetic enamel paint of black and yellow in alternate strips of 30 cm width upto 1.5 mtr height including applying a coat of white wash on pole coping and lettering the pole details with white letters/ background etc. complete all as directed |
| 30 | S&F in repair powder coated Mild steel junction box with MCB SP 03-10 Amps-01 No outdoor type , CRCA sheet with front openable hinged door , locking arrangements with 4 Nos Aluminum bus bars , 200 Amps, mounted on porcelain insulator, glands and lugs etc. and fixed to pole/ PTL post etc. with suitable size flat iron clamps, nuts , bolts complete including taking down all as specified and directed. |
| 31 | S&F in repair powder coated Mild steel junction box with MCB SP 03-10 Amps-01 No outdoor type , CRCA sheet with front openable hinged door , locking arrangements with 2 Nos Aluminum bus bars , 200 Amps, mounted on porcelain insulator, glands and lugs etc. and fixed to pole/ PTL post etc. with suitable size flat iron clamps, nuts , bolts complete including taking down all as specified and directed. |
| 32 | Supply and fixing galvanized steel tube light grade of 15 mm dia, over the electric pole with the help of suitable size MS clamp, passing the service cable from the busbar to the light fitting through it, and making connection, of the cable to both the ends from bus bar to the light complete all as directed and specified. |
| 33 | Supply and erecting in true vertical or to be planed as strut, steel tubular swaged welded pole complete with MS base plate final taper plug, bolt, nuts & screw, 6mm thick of size 300mmx300mm welded at the centre of the pole, type 410 SP-31 (09 Mtr long) including drilling of holes of required size and nuts for fixing of cross arms, painting with coat of red oxide zinc chrome primer and two coats of aluminum paint on exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting three black and three white bands at lower portion of pole each of 300mm height at 300mm spacing complete all as specified incl dismantling old one complete all as directed and specified. NOTE :- Earth work, Cement concrete in foundation, coping etc. will be measured and paid separately under relevant item. |
| 34 | M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete all as specified and directed. |
| 35 | M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work complete all as specified and directed. |
| 36 | Repair, maint and making the fully functioning of flameproof electric operated crane of cap 2 Ton to 5 ton after checking long travell motion , cross travel motion , hoisting motion (electrically and mechanically) in presence of user rep and MES rep & rectify any type of defects immediately when found including servicing, greasing, top up gear box oil & carrying out routine maintenance as directed by Engineer in Charge. Note :- (i) any accessories found unserviceable that shall be replaced under respective items of this Sch. (ii) : Labour for lowering, mounting arrangement such as ladder , pulley block, rope system, T&P , any type nut, bolt, washers and other connected mechanism shall be contractor arrangement and rates are deemed to be included in this Job. No extra payment will be made to the contract or against lowering/lifting the spare etc. at a height of 20' to 30' (iii) Repair/maint of each flame proof EOT crane of capacity 2 to 5 Ton (total 17 Nos) for two times or as per complaint of EOT cranes in a month. |
| 37 | Dismantling the main driving shaft of forward/reverse drive of flameproof EOT crane after unscrewing nuts, bolts, washers including other connected accessories with shaft such as breaking assembly, coupling, bearings rings, gear box lowering down the smaller portion of shaft from up to 30' approximate height for removing and threading, repairing manufacturing cutting teeth keys one Nos bearing housing cabinet and replacement of one Nos tapper bearing welding of foundation rest pad making drills holes in rest pads matching with main foundation of trolly, cleaning, greasing and oiling of all the bearing, bearing housing, gear box etc. complete for smooth functioning including providing nut, bolts with locking arrangement & washers of any type/size as site requirement complete including re-assembly with connected accessories after repair including carrying out necessary alignment of all the parts connected with shaft all as specified and directed by Engineer-in-charge (Capacity of crane - 2 to 5 Ton ) |
| 38 | Dismantling of micro -up and down drive arrangement of flameproof EOT crane after un-screwing L- key bolts/screws nuts, washers etc. which includes gear box of micro drive main box of up -down drive, braking arrangements including dismantling of 3 set (3 pair) of micro coupling, micro-drive arrangement for under taking repair including getting down all as dismantled parts from existing platform at a minimum height about 20' to 30' approximately reassembling and re alignment all the parts complete including testing on load on both micro and main drive complete all as specified and directed by Engineer -in-charge. (capacity of Crane 2 to 5 Ton) |
| 39 | Dismantling/strip opening gear of micro main shaft drive for replacement of 2 Nos gun metal bushes having internal lining for oiling arrangement, replacement of all the nuts/bolts of bush side plate with L-key, bolts of size as per sample oiling/greasing of gear box including necessary cast iron repair to broken foundation which includes welding lathing and grinding complete all as specified and directed by Engineer -in-charge. (Crane capacity 2 to 5 Ton ) |
| 40 | Dismantling and refixing after repair brake shoe leather suitable any motion of flameproof EOT crane 2 to 10 ton cap complete all as specified and directed Engineer in charge. |
| 41 | Dismantling/strip opening flameproof micro drive box complete with rectifier transformer arrangement, magnetic disc both side coupling for remotting both the side ends of driving shaft (Gear box coupling side and braking arrangement coupling side) making multi key arrangement on both the shaft and couplings (teeth system ) to avoid any kind of play in coupling and shaft including replacement of 4 Nos carbon bushes, replacement of 02 Nos gun metal bushes including making oiling arrangement in bushes and side covers of bushes/housing of micro drive re-assembling/testing complete (crane capacity up to 5 Ton) all as specified and directed by Engineer -in-charge. |
| 42 | Dismantling/strip opening of up/down micro electric braking arrangement after un-screwing nuts, bolts washers, re-adjustment of braking springs, replacement of brake leathers, replacement of two Nos 440 volts any make brake coils, replacement of both gun metal bushes of shaft housing in brake box making oiling/greasing arrangement complete re-assembling and testing complete all as specified and directed by Engineer -in-charge.(Crane capacity 2 to 5 Ton if any part required will be paid and measured under respective item of schedule) |
| 43 | M&L for replacement of coupling as per sample or approved by GE suitable for perfect alignment between flameproof motor and driven machine all as directed by Engineer in charge. |
| 44 | M&L for replacement of L Key bolts 1\\" x 10mm as per sample or approved by GE including applying moose threads found worn out and taking out broken bolts from body/housing of machine for 2 to 5 ton capacity flameproof EOT Crane complete all as specified and directed by Engineer-in-charge. |
| 45 | Dismantling/ lowering of burnt flame proof/weather proof three phase 440 volts , 50 Hz , 960 RPM , class F, 5 HP induction motor from platform complete including strip opening the same and rewinding with super enameled copper winding wire of same size /gauge as existing earlier complete including all backing material , insulation material and re- installation the same at original site complete all as specified and directed Engineer in charge. |
| 46 | All as per serial item No. 45 here-in-before but capacity of motor 3 HP. |
| 47 | M & L for of Power contactor 3 pole 16 Amp , 110 Volt as per sample or approved by GE complete all as specified and directed by Engineer in charge. |
| 48 | M & L for of Power contactor 3 pole 40 Amp , 110 Volt as per sample or approved by GE complete all as specified and directed by Engineer in charge. |
| 49 | M & L for of Over load relay 1.7 to 2.4 Amp as per sample or approved by GE complete all as specified and directed by Engineer in charge. |
| 50 | M & L for of main bearing as per site requirement suitable for 2 to 10 Ton cap crane all as specified and directed by Engineer in charge |
| 51 | M&L for brake oil suitable for flameproof EOT crane up to 5 Ton cap as per manufacture recommendation or directed by Engr In Charge. Make : Servo/HP/Castrol |
| 52 | M&L for grease suitable for flameproof EOT crane up to 5 Ton cap as per manufacture recommendation or directed by Engr In Charge. Make : Servo/HP/Castrol |
| 53 | S & F Thruster for flame proof EOT crane cap upto 5 Ton complete with all accessories all as specified and directed by Engr-in-charge. |
| 54 | M&L for Earthing complete with galvanized cast iron earth plate electrode of size 600x600x6 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using galvanized iron strip 32x6mm earthing lead as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade 40mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil remain surplus excavated material all as required at site and specified in EP No 3 of SSR complete all as specified and directed by Engineer-in-charge incl testing on completion. |
| 55 | Excavation in trenches not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide in any type of soil for laying of cables, foundation filling of or stays complete all as specified and directed by Engr-in-Charge |
| 56 | Returning filling in including spreading, leveling watering and well ramming in layers not exceeding 25cm thick complete all as directed. |
| 57 | Removing excavated soils to a distance not exceeding 50 m and depositing where directed complete all as specified and directed. |
| 58 | M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specified and punned thickness shall be measured and paid. |
| 59 | Supply and laying sub class 'B' bricks of old size (230x115x75 mm) or of size locally available , laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge |
| 60 | Supply and lay cable XLPE insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade of cross sectional area 16 Sq mm 2 core. Note: Earth work (Excavation, Returning & refilling and removal), sand cushioning , cable protection cover, GI protection pipe shall be measured and paid for separately under respective item of Schedule |
| 61 | All as per serial item No. 60 above but of size 16 Sqmm 4 core |
| 62 | All as per serial item No. 60 above but of size 25 Sqmm 4 core |
| 63 | All as per serial item No. 60 above but of size 35 Sqmm 3.5 core |
| 64 | All as per serial item No. 60 above but of size 50 Sqmm 3.5 core |
| 65 | All as per serial item No. 60 above but of size 70 Sqmm 3.5 core |
| 66 | Dismentaling,repair & refixing, servicing of the SMPS power plant up to 150 Amp including replacement of burn out components and testing after refixing the components complete all as specified and directed by Enr-in-Charge.(Note: components if reqd will be measured and paid under respective item of schedule.) |
| 67 | Supply only SMPS Controller card |
| 68 | Supply only SMPS Module |
| 69 | Supply only Control Supply |
| 70 | Supply only Surge protection Cartridge |
| 71 | S&F in replacement of 12 Volt 60 Amp lead acid battery for solar street light complete all as specified and directed by Engr-in-Charge. |
| 72 | Supply and fix in replacement 12 volt 20 watt solar street light complete all as specified and directed by Engr-in-Charge. |
| 73 | Supply and fix in replacement solar PV module/Solar panel for 12 volt 20 watt solar street light complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 74 | Supply and fix in replacement solar PV module/Solar panel for 12 volt 20 watt solar street light complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender