Tender For Providing Internal And External Electrification Arrangements To The Construction Of Additional Building In Government Hospital At Alangudi In Pudukkottai District
Tender Value
23.13 Lakhs
Estimated cost
Bid Submission
30 Jul 2026
1 days left
EMD
22000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pudukkottai → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing Internal And External Electrification Arrangements To The Construction Of Additional Building In Government Hospital At Alangudi In Pudukkottai District
BOQ
| Sl. No. | Item Description |
| 1 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End. |
| 2 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End. |
| 3 | Wiring with 3 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A two way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End. |
| 4 | Supply and fixing of 24 W LED 2x2 square type surface fitting (Higher end) on ceiling with PVC unsheathed copper leads from terminals to the fitting. |
| 5 | Supply and fixing of 4 Feet LED 20 W Fitting with LED 20 W tube (HigherEnd)complete with conduit pipe suspension from the ceiling with PVC unsheathed FRLS copper leads from terminals to the fitting with tube |
| 6 | Supply and fixing of 4 Feet LED 20 W Fitting with LED 20 W tube (HigherEnd)complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting. |
| 7 | Supply and fixing of fancy glass shade and 7W / 9W LED bulb . |
| 8 | Supply and fixing of WT bulk head fitting with guard suitable with 7W / 9W LED bulb. |
| 9 | Supply and fixing of 48W LED street light fitting with LED (Higher end) with 32 mm dia. GI pipe (class B) with 1 no. 32 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting . |
| 10 | Supply and fixing of 1200mm (48\\") sweep AC ceiling fan complete High Speed ( Higher end) with 2 module 100W fan step regulator (Higher end) with 300mm down rod with 12 mm U fan clamp in the concrete . |
| 11 | supply and fixing of 400 mm Sweep Wall Mounting Fan with MS Clamp set with connections complete . |
| 12 | Supply and fixing of 300 mm (12\\") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall. |
| 13 | Supply and fixing of louvers shutters arrangements for 300 mm (12\\") sweep (light duty) AC exhaust fan. |
| 14 | Supply and run of 2 of 1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion |
| 15 | Supply and fixing of 3 nos. 6A two module 3 pin socket , 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End. |
| 16 | Supply and run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire and making good of the concealed portion. |
| 17 | Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End. |
| 18 | Supply and fixing of 4 nos.6/16 A two module 5 pin socket , 4 nos. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End. |
| 19 | Supply and fixing of 25A Flush type Wall Socket 25A DP MCB complete set for AC Plug in flush with wall with earth connection (For AC Plug). |
| 20 | Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 10 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End. |
| 21 | Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour. |
| 22 | Supply and fixing of 4 way metal box enclosure with 6A to 32A FP MCB in flush with wall and making good of the concealed portion with earth connection only. (For X-Ray) |
| 23 | Supply and run of 4 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour |
| 24 | Supply and fixing of 6 way Horizontal Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A 4P MCB as incoming and 18 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End. (Essential plug points) |
| 25 | Supply and run of 4 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sq.mm copper wire and making good of the concealed portion with suitable colour |
| 26 | Supply and fixing of 4 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 63A 4P MCB switch as incoming and 12 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End. |
| 27 | Supply and fixing of 6 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 63A 4P MCB switch as incoming and 4 nos. 32A TP MCB , 6 nos 6A to 32 A SP MCB as outgoing in flush with wall with earth connection only. Higher End. (Generator DB ) |
| 28 | Supply and Run of 4 of 10 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 10 sq.mm copper wire and making good of the concealed portion |
| 29 | Supply andand fixing of 100 A Three phase 500V 4 Pole Change over Switch on suitable angle iron frame work with MS cable entry boxes with earth connection only |
| 30 | Supply and fixing of 8 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 100 A 4P MCB Isolator as incoming and 5 Nos. 63 A 3P MCB , 3 nos. 32A 3P MCB as outgoing in flush with wall with earth connection only. Higher End |
| 31 | Supply and Laying of 3 1/2 x 70 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. |
| 32 | Supply and clamping of 3 ½ x 70 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps |
| 33 | Supply and fixing of Brass Cable Gland for 3 ½ x 70 sqmm PVC LTUG cable with Earth Connection. |
| 34 | Supply and providing cable end termination of 3 ½ x 70 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete |
| 35 | Supply and fixing of 100 A TPN sheet steel double break switch with HRC fuses and neutral on suitable angle iron frame work with MS cable entry boxes and with earth connection only |
| 36 | Supply and fixing of cable entry box for 4 way Vertical Triple pole and neutral MCCB DB |
| 37 | Supply, erection, testing and commissioning of 2.0 TR (6000 K. cal/ hr) ABS plastic split type Air conditioner conforming to IS: 1391 (Part-2) 1992 with Amdt No.1 to 2 fitted with Rotary compressor operating on non CFC refrigerant suitable for wall mounting for operation on 230V, 50 HZ single phase AC supply with 5 star rating as per BEE specification and capable of performing the functions of 1) Cooling 2) Dehumidifying 3) Air circulating 4) FilteringThe installation works for the above split type A.C units includes the following.1. Mounting / Fitting indoor and outdoor units at their respective locations.2. Laying refrigerant pipe line of 6 meters length, both units after drilling hole / holes in the wall if required. Thickness of the copper tubing shall not be less than 0.7mm.3. Insulating the suction pipe with expanded polyurethelene foam 5mm thick tubing.4) Laying 25mm dia flexible PVC drain pipe of 6 mts. Length to drain out the condensate water being formed in the indoor unit.5) Leak testing the entire gas unit.6) Charging refrigerant gas in the unit.7) Suitable electric wiring to be provided with 3 core 2.5sq.mm PVC insulated copper wire between indoor and outdoor units up to 4 meters length and up to switch within 3 meters of location of indoor unit. |
| 38 | Supply and fixing of 5 KVA electronic automatic voltage stabilizer with input range of 170-270V and output range 200-240 V with high and low voltage cut off and 3 minutes time delay relay with demonstration suitable for operation on 230V/50Hz single phase AC supply |
| 39 | Supply and fixing of MS stand wall clamp support for mounting outdoor unit of split type AC unit complete. |
| 40 | Supply and fixing of 5/8” and 3/8” copper pipes with insulation foam of 6mm thickness suitable for split type AC unit |
| 41 | Supply and fixing water drain pipe line (1\\" PVC pipe) |
| 42 | Earthing as per the ISI specification with an earth electrode of 2.10 metre Class 'B' GI pipe of dia not less than 40mm with copper earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry |
| 43 | Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection |
| 44 | ADD GST 18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayJul 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer