Tender For repair maintenance electrical installation & Fans, Compound Lights, Pump Sets, Ro System & Air Conditioning Units Installed At Dseu-1 (Polytechnic & Printing Technology) Pusa, New Delhi During 2026-27. (Sh : electrical installation Work, M
Tender Overview
Project Description
Tender for repair maintenance electrical installation & Fans, Compound Lights, Pump Sets, Ro System & Air Conditioning Units Installed At Dseu-1 (Polytechnic & Printing Technology) Pusa, New Delhi During 2026-27. (Sh : electrical installation Work, Maintenance Of Air Conditioner & Pump Etc.).
BOQ
| Sl. No. | Item Description |
| 1 | SH-I (EI Work)Operation of 11 KV electric sub-station equipments (excluding 250 KVA transformer installed at Polytechnic), DG sets installed as per inventory at DSEU -I (Polytechnic & Printing Technologry), & Operation and preventive maintenance of pump set installed at above Site to fill up over head tank i/c timely operation of valves of O.H. tank and underground tank to delivery water supply in various building on all days of the month i/c attending day to day complaints of EI and fans, rectification of fault, upkeeping and preventive maintenance complete etc. as reqd. by providing following minimum staff as per terms & conditions enclosed. |
| 2 | a) Wireman cum DG Set Operator cum Pump Operator - 3 No.(Round the clock) (One in each shift) (Including Sunday & Holiday) |
| 3 | Wireman 1 No (In General Shift) (Excluding Sunday & Holiday) |
| 4 | Khallasi – 1 No. (In General Shift) (Excluding Sunday & Holiday) |
| 5 | SH- II- (Supply of material)Following material /electrical accessories shall be supply by agency and fixing will be done by the existing man power existing for replacement on day to day maitenance works etc as required. (Labour already included in Item No. 1 & 2 Sub Head - I.) |
| 6 | 5 Amp Modular Switch |
| 7 | 5 Amp Modular Socket |
| 8 | 15/16 Amp Modular Switch |
| 9 | 15/16 Amp Modular Socket |
| 10 | S.P. 5/6 A, one way switch, piano type ISI marked |
| 11 | S.P. 15/16 A, one way switch, piano type ISI marked |
| 12 | 3 pin 5/6 A socket outlet, piano type ISI marked |
| 13 | 6 pin 15/16 & 5/6 A socket outlet, piano type ISI marked |
| 14 | 3 mm thick phelonic laminated sheet |
| 15 | 6 to 32 Amp c Curve SP MCB, \\"C\\" curve, 10 kA breaking capacity |
| 16 | 6 amps. to 32 amps. ratings , DP MCB, “C” curve, 10 KA breaking capacity |
| 17 | 6 amps. to 32 amps. ratings , SPN MCB, “C” curve, 10 KA breaking capacity |
| 18 | 6 amps. to 32 amps. ratings , TP MCB, “C” curve, 10 KA breaking capacity |
| 19 | 6 amps. to 32 amps. ratings , TPN MCB, “C” curve, 10 KA breaking capacity |
| 20 | 40 amps., 2 pole isolator |
| 21 | 63 amps., 2 pole isolator |
| 22 | 40 amps., 4 pole isolator |
| 23 | 63 amps., 4 pole isolator |
| 24 | 100 amps., 4 pole isolator |
| 25 | 1.5 Sq.mm FRLS Copper wire |
| 26 | 4 Sq.mm ISI marked FRLS copper wire |
| 27 | 6 Sq.mm FRLS Copper wire |
| 28 | 2.50 mfd fan capacitor |
| 29 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM / Min (Minimum) BLDC Fan |
| 30 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/ Min (Minimum) BLDC Fan |
| 31 | 300 mm sweep heavy duty exhaust fans |
| 32 | 380 mm sweep heavy duty exhaust fans |
| 33 | Call bell/ buzzer, single phase |
| 34 | Stepped type Modular Fan regulator (2 module) |
| 35 | Modular base & cover plate for 3 module |
| 36 | Modular base & cover plate for 6 module |
| 37 | Modular base & cover plate for 8 module |
| 38 | Modular base & cover plate for 12 module |
| 39 | 3 pole MCCB, 100A, 16kA |
| 40 | 3 pole MCCB, 125A, 16kA |
| 41 | 3 pole MCCB, 400A, 35kA |
| 42 | Supplying of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 43 | 36 watt |
| 44 | Supplying of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 45 | 36 watt |
| 46 | Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 47 | 150 watt |
| 48 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 49 | 120 watt |
| 50 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 51 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 52 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 53 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 54 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 55 | Group C |
| 56 | Supplying & laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade aluminium armoured cable of following size for existing RCC/HUME/METAL pipe/Air/Surface etc complete as required. |
| 57 | 4 x 25 Sq.mm |
| 58 | SH- III- (Pump)Supplying, Installation, Testing & Commissioning of Borewell submersible Pump set of following capacity suitable for working on 3 phase,415 volts A.C. supply 50 Hz i/c lowering in the sump well with the help of chain pulley block and tripod stand, connecting with existing delivering pipe lines, connections etc complete as reqd. |
| 59 | Head 320-40 mtrs., discharg 0-105 LPM, 7.5 HP |
| 60 | Lowering of 3/5/7.5/10 H.P. Submersible/ Mono-submersible pump/Sewage Submersible pump /sets in the underground tank or Borewell along with existing GI Pipe submersible cable etc. With the help of tri-port and chain pully block including P/F nub bolts, rubber packing, including testing, commissioning etc as required. |
| 61 | Mono-Submersible Pump Set/Dewatering Pump Set. |
| 62 | Lifting of 3/5/7.5/10 H.P. Submersible/ Mono-submersible pump/Sewage Submersible pump /sets from the underground tank or Borewell with the help of tri-port and chain pully block along with existing GI pipe and submersible cable etc complete as required. |
| 63 | Mono-Submersible Pump Set/Dewatering Pump Set. |
| 64 | Rewinding Mono Submersible pump sets of following rating including cutting the burnt winding wire including rewinding the same with high quality motor resistance PVC Insulated copper winding the wire and credit of dismantled material i/c testing commissioning complete etc. as reqd. |
| 65 | 5 HP Mono Sbmersible Pump |
| 66 | Providing and fixing of following 5 HP Mono Submersible spare parts in the above motor i/c credit of old dismantled material etc as reqd. |
| 67 | Rematling of shaft and Turning & Polishing of Rotor sleeve- 1 job |
| 68 | G.M. Bush - 4 Nos. |
| 69 | Rematling of Impeller& Neck ring- 1job. |
| 70 | Oil/Water Seal- 2 Nos. |
| 71 | Flat Cable 3X2.5 Sq.mm- 5 Mtr. |
| 72 | Thrust plate and Thrust Bearing- 1Set |
| 73 | Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. complete as required. |
| 74 | 3 Core 4.0 Sq mm Flat Cable |
| 75 | SH- IV(Comprehensive maintenance of AC)Comprehensive & Routine maintenance of 7 Nos. WTAC / STAC unit i/c attending day to day complaints and rectify the defects, supplying and replacement of wornout parts such as starting / running capacitors, starting relays, overload relay, tharmostat, selector switches, sleeves, knobes, connector and associated control wiring, filter, drain pipe etc which reqd to be replace during routine maintenance and monthly cleaning of filters etc. (Replacement of compressor, condensor unit, cooling coil unit, blower, fan blower motor, front grill, man leads, gas charging etc not covered under routine maintenance) complete as per terms & conditons. |
| 76 | Servicing of existing installed WTAC / STAC of 1.5 TR & 2.0 TR capacity AC and water coolers of 80/150/250 LPH, checking for unit, inspection, greasing, oiling etc i/c chemical cleaning of the condensing coil with high pressure pump changing the air filter, checking & tightening all electic connection, testing the machine etc as reqd. |
| 77 | Providing and fixing WTAC /STAC fan motor capcity 1/4 to 1/8 HP etc complete as required. |
| 78 | Supplying & charging of M-22 / R-22 gas in the exising WTAC / STAC of 1.5TR unit i/c pressure testing, flushing the system & gas charging complete etc |
| 79 | Supplying & charging of M-22 / R-22 gas in the exising WTAC / STAC of 2 TR unit i/c pressure testing, flushing the system & gas charging complete etc as |
| 80 | Supplying & fixing of 25 mm dia PVC heavy duty pipe drainage in the existing split type AC unit with supporting clamps etc complete as reqd |
| 81 | Repair of damaged PCB of indoor and outdoor unit i/c tightening the loose connection, testing the machine etc as required |
| 82 | Supplying & fixing of copper refrigerant pipe of size 1/4\\", 5/8\\" with insulation and copper wire 3 core 4 sq.mm i/c making all connections in the AC units etc as per reqd at site. |
| 83 | Supplying & fixing of Fan blower suitable for 1.5/2.0 ton indow/Split AC i/c connections, testing, commissioning etc complete as reqd. |
| 84 | Supplying & fixing of 1.5 TR capacity rotary compressor in the existing WTAC / Split AC making copper pipe connection, brazong pressure testing and supplying and charging M-22 refrigerant gas charging i/c cutting the copper piping dismantling etc. complete as required. |
| 85 | Providing and fixing of follwing WTAC /STAC accessories i/c dismantling & credit of the burnt materials from the existing unit & fixing & making connection, testing complete etc as reqd:- |
| 86 | 1.5 / 2 TR Condensor Coil |
| 87 | SH-V (Credit Material)Credit for old dismantle material as and where basis etc as reqd. |
| 88 | Old fan blower motor 1.5 / 2 TR |
| 89 | Fan blower |
| 90 | Old assorted copper wire |
| 91 | Old assorted aluminium wire |
| 92 | Old assorted size Switch & sockets |
| 93 | Old assorted 1200 mm Ceiling Fan |
| 94 | Old assorted 1400 mm Ceiling Fan |
| 95 | Old assorted Exhaust Fan |
| 96 | Old assorted MCB (6-32 Amp) |
| 97 | Old assorted DP/Isolator/TP (32/40/63/100Amp) |
| 98 | Old assorted size submerible pump |
| 99 | DG set accessories i/c fillter, mobil oil, battery, starter, charger etc Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender