Tender For Repairs / Maintenance To Dg Sets, Fire Fighting Network And Other Misc E/M Works At Nad, Technical Building At installation Dega And Adjacent Areas Along With Certain E/M Amd B/R Services Of Ncn Kakinada Other Certain Installation And Conn
Tender Overview
Project Description
Tender for Repairs / Maintenance To Dg Sets, Fire Fighting Network And Other Misc E/M Works At Nad, Technical Building At installation Dega And Adjacent Areas Along With Certain E/M Amd B/R Services Of Ncn Kakinada Other Certain Installation And Connected Works With Certain Water Supply Works Under Ge (Utility-Ii) Visakhapatnam
BOQ
| Sl. No. | Item Description |
| 1 | Material and Labour for servicing of DG set of capacity 500 KVA of existing Make and modelby carrying out the following maintenance as per manufacturers instructions including cleaning the engine, alternator, inferiors and exteriors of acoustic enclosure completely by blowering and with cotton waste and testing on completion at connected load, complete all as specified and directed:-(a) Draining out engine oil from the sump by removing drain plug, cleaning the sump thoroughly and refilling the sump with new engine oil to required level (Note: Engine Oil will be measured and paid separately as 'Supply Only').(b) Draining out of diesel from tank and storing in cleaned containers, cleaning the tank thoroughly by removing sediments settled at the bottom and refilling the drained out diesel duly filtered.(c) Supply and replace complete set of engine oil filters, fuel filters, Bypass filter, air cleaner element and water separator.(d) Draining out complete coolant water mixture from the radiator and re-filling the radiator with new coolant and water mixture with proportionate ratio (Note: Coolant will be measured and paid separately as 'Supply Only').(e) Check and top up the electrolyte/distilled water in starting batteries to maintain the required specific gravity. Cleaning of battery terminals & applying petroleum jelly to battery poles & brass connectors.(f) Checking and Tightening all the fasteners of complete DG set to the required torque, if required. |
| 2 | All as per item No.1.00 here-in-before but for DG set of capacity 400 KVA of existing Make and model |
| 3 | All as per item No.1.00 here-in-before but for DG set of capacity 320 KVA of existing Make and model |
| 4 | All as per item No.1.00 here-in-before but for DG set of capacity 250 KVA of existing Make and model |
| 5 | All as per item No.1.00 here-in-before but for DG set of capacity 200 KVA of existing Make and model |
| 6 | All as per item No.1.00 here-in-before but for DG set of capacity 160 KVA of existing Make and model |
| 7 | All as per item No.1.00 here-in-before but for DG set of capacity 125 KVA of existing Make and model |
| 8 | All as per item No.1.00 here-in-before but for DG set of capacity 100 KVA of existing Make and model |
| 9 | All as per item No.1.00 here-in-before but for DG set of capacity 82.5 KVA of existing Make and model |
| 10 | All as per item No.1.00 here-in-before but for DG set of capacity 75 KVA of existing Make and model |
| 11 | All as per item No.1.00 here-in-before but for DG set of capacity 62.5 KVA of existing Make and model |
| 12 | All as per item No.1.00 here-in-before but for DG set of capacity 30 KVA of existing Make and model |
| 13 | All as per item No.1.00 here-in-before but for DG set of capacity 20 KVA of existing Make and model |
| 14 | All as per item No.1.00 here-in-before but for DG set of capacity 15 KVA of existing Make and model |
| 15 | Supply only engine oil of grade 15W-40 for various DG Sets, complete all as specified and directed. |
| 16 | Supply only of premix coolant water mixture (50:50) suitable for DG sets, complete all as specified and directed. |
| 17 | Supply only Def oil of high grade of approved make suitable for CPCB IV+ DG Set, complete all as specified and directed. |
| 18 | Supply and replace complete set of fuel pipes & leak off pipe with clamps suitable for existing make & model of DG set up to 400 KVA to 500 KVA capacity, complete all as specified and directed. |
| 19 | All as per Item No 18.00 here-in-before but for DG set up to 125 KVA to 320 KVA capacity |
| 20 | All as per Item No 18.00 here-in-before but for DG set up to 82.5 kva to 100 KVA capacity |
| 21 | Supply and replace 'V' belt suitable for existing make & model of DG set 400 KVA to 500 KVA capacity, complete all as specified and directed. |
| 22 | All as per Item No 21.00 here-in-before but for DG set 100 KVA to 320 KVA capacity |
| 23 | All as per Item No 21.00 here-in-before but for DG set up to 100 KVA capacity |
| 24 | Supply and replace complete set of hoses with clamps suitable for existing make & model of DG set 400 KVA to 500 KVA capacity, complete all as specified and directed. |
| 25 | All as per Item No 24.00 here-in-before but for DG set 125 KVA to 320 KVA capacity |
| 26 | All as per Item No 24.00 here-in-before but for DG set up to 100 KVA capacity |
| 27 | De-scaling of radiator assembly by carefully removing from the engine, transporting to civil workshop and removing the sediments, scales and rust etc by means of acid cleaning, high pressure water washing and air cleaning, arresting the leakages by gas welding / soldering with suitable material, re-assembling the same with new gaskets including replacement of radiator cap (wherever required) and transporting to the site, fixing to the engine for DG Set of capacity 400 KVA to 500 KVA and testing for satisfactory performance, complete all as specified and directed by Engineer-in-Charge. |
| 28 | All as per item No.27.00 here-in-before but for DG Set of capacity from 200 KVA to 320 KVA. |
| 29 | All as per item No.27.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA. |
| 30 | All as per item No.27.00 here-in-before but for DG Set of capacity from 62.5 KVA /75 KVA/ 82.5 KVA. |
| 31 | All as per item No.27.00 here-in-before but for DG Set of capacity from 20 KVA / 30 KVA. |
| 32 | Dismantling the defective water pump (coolant pump) assembly and Supply and fix new water pump assembly suitable for existing DG set of capacity 400 KVA to 500 KVA complete all as specified and directed by Engr-in-Charge. |
| 33 | All as per item No.32.00 here-in-before but for DG Set of capacity 200 KVA to 320 KVA. |
| 34 | All as per item No.32.00 here-in-before but for DG Set of capacity 100 KVA / 125 KVA. |
| 35 | All as per item No.32.00 here-in-before but for DG Set of capacity 62.5 KVA /75 KVA/ 82.5 KVA. |
| 36 | All as per item No.32.00 here-in-before but for DG Set of capacity 20 KVA / 30 KVA. |
| 37 | Dismantling the defective fuel injectors & FIP from the engine and Material & Labour for repair/calibration of fuel injectors & FIP including replacement of barrel, plunger, spring & ‘O’ rings etc. for DG Set of capacity 400 KVA to 500 KVA, complete all as specified and directed by Engineer-in-Charge. |
| 38 | All as per item No.37.00 here-in-before but for DG Set of capacity 200 KVA to 320 KVA. |
| 39 | All as per item No.37.00 here-in-before but for DG Set of capacity 100 KVA / 125 KVA. |
| 40 | All as per item No.37.00 here-in-before but for DG Set of capacity 62.5 KVA / 82.5 KVA/75 KVA |
| 41 | All as per item No.37.00 here-in-before but for DG Set of capacity 40 KVA / 50 KVA. |
| 42 | All as per item No.37.00 here-in-before but for DG Set of capacity 20 KVA to 30 KVA. |
| 43 | Supply only lube oil super bypass filter for 200 to 250 KVA DG Set, complete all as specified and directed. |
| 44 | Supply only lube oil super bypass filter for 400 KVA to 500 KVA DG Set, complete all as specified and directed. |
| 45 | Taking down unserviceable lube oil pressure sender and Supply and fix Lube Oil Pressure Sender (Sensor + Switch) suitable for DG set of capacity 400 KVA to 500 KVA complete all as specified and directed by Engineer-in-Charge. |
| 46 | All as per item No.45.00 here-in-before but for DG Set of capacity 100 KVA to 320 KVA. |
| 47 | All as per item No.45.00 here-in-before but for DG Set of capacity up to 82.5 KVA. |
| 48 | Dismantling the fly wheel coupling between engine and alternator and Supply and replace complete set of bullet rubber bushes, coupling nuts & bolts including proper alignment of engine & alternator for smooth running for DG set of capacity 200 KVA to 320 KVA complete all as specified and directed by Engineer-in-Charge. |
| 49 | All as per item No. 48.00 here-in-before but for DG set of capacity 100 KVA / 125 KVA. |
| 50 | All as per item No.48.00 here-in-before but for DG Set of capacity up to 82.5 KVA. |
| 51 | Dismantling the defective 24 V battery charging alternator carefully from any capacity of DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace carbon brush, brush holders, bushes/bearings, varnishing etc, re-assembling and re-fixing the same and testing on completion complete all as specified and directed by Engineer-in-Charge. |
| 52 | All as per item No.51.00 here-in-before but 12 V battery charging alternator for any capacity of DG set. |
| 53 | Supply and fix RPM Meter with cable suitable for DG Set including taking down of existing unserviceable meter complete all as specified and directed by Engineer-in-Charge. |
| 54 | Supply and fix Oil Pressure Gauge suitable for DG Sets including taking down existing unserviceable gauge, complete all as specified and directed by Engineer-in-Charge. |
| 55 | Supply and fix Water Temperature Gauge suitable for DG Sets including taking down existing unserviceable gauge complete all as specified and directed by Engineer-in-Charge. |
| 56 | Supply and connect battery connecting cable (1.50m long each) made out of PVC Insulated Plain/Striped Automobile Cables with high conductivity bright annealed copper conductor bunched together, insulated with dielectric grade PVC compound (impervious to oils, greases, acids, petrol and water) conforming to IS 2465 of size 25 sqmm soldered one end with brass connector with nuts and bolts for battery pole and the other with copper lug for self starter terminal including taking down of existing u/s battery connecting cable with connector and lug of any description complete all as specified and directed by Engineer-in-Charge. |
| 57 | Supply and replace brass connector with bolt and nut suitable for positive/negative pole of battery of any size, complete all as specified and directed by Engineer-in-Charge. |
| 58 | Taking down unserviceable engine wiring and Material & Labour for rewiring of engine safety control system from control panel to engine control gadgets like HWT, LLOP, shut down valve, dynamo & self-starter etc with suitable gauge and grade of wires for DG set of capacity from 400KVA to 500 KVA complete all as specified and directed by Engineer-in-Charge. |
| 59 | All as per item No.58..00 here-in-before but for DG Set of capacity from 100 KVA to 320 KVA. |
| 60 | All as per item No.58.00 here-in-before but for DG Set of capacity up to 75 KVA. |
| 61 | Dismantling the defective self starter assembly 12V/24V carefully from the DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace commutator, carbon brush set, carbon brush holder, king pin holder, armature choke nut, body screens, clutch plate assembly and solenoid etc, re-assembling and re-fixing the same and testing on completion for DG set of capacity from 400 KVA to 500 KVA complete all as specified and directed by Engineer-in-Charge. |
| 62 | All as per item No.61.00 here-in-before but for DG Set of capacity from 100 KVA to 320 KVA. |
| 63 | All as per item No.61.00 here-in-before but for DG Set of capacity up to 82.5 KVA. |
| 64 | Supply and replace battery 12V, 180 AH with 24 months full replacement warrantee for DG set including initial filling & charging complete all as specified and directed by Engineer-in-Charge. |
| 65 | All as per item No. 64.00 here-in-before but of rating 12V, 130 AH |
| 66 | All as per item No. 64.00 here-in-before but of rating 12V, 100 AH |
| 67 | All as per item No. 64.00 here-in-before but of rating 12V, 80 AH |
| 68 | Dismantling the defective alternator from DG set, transporting to civil work shop, separating the stator and rotor from alternator housing, cutting and removing burnt winding of stator completely, cleaning the slots and rewinding the stator with existing gauge of super enamelled copper wire with suitable grade of insulation, applying varnish and heating in heating chamber till completely dried and reassembling the alternator, transporting back to site and re-fixing to the DG set including proper alignment for smooth running and testing on completion for DG set of capacity 400 KVA to 500 KVA complete all as specified and directed by Engineer-in-Charge. |
| 69 | All as per item No. 68.00 here-in-before but for DG set of capacity 200 KVA to 320 KVA. |
| 70 | All as per item No. 68.00 here-in-before but for DG set of capacity 100 KVA / 125 KVA. |
| 71 | All as per item No. 68.00 here-in-before but for DG set of capacity 75 KVA /82.5 KVA. |
| 72 | All as per item No. 68.00 here-in-before but for DG set of capacity 30 / 62.5 KVA. |
| 73 | All as per item No. 68.00 here-in-before but for DG set of capacity 15 to 20 KVA. |
| 74 | Supply and fix in replacement of left hand/ right hand hinge suitable for acoustic enclosure doors for DG set of any make and capacity 400 KVA to 625 KVA including removing of existing broken hinge complete all as specified and directed by Engineer-in-Charge. |
| 75 | All as per item No. 74.00 here-in-before but for DG set of capacity 100 KVA to 320 KVA. |
| 76 | All as per item No. 74.00 here-in-before but for DG set of capacity up to 82.5 KVA. |
| 77 | Supply and fix in replacement of MCCB, 630 A, 3 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. |
| 78 | Supply and fix in replacement of MCCB, 400 A, 3 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. |
| 79 | Supply and fix in replacement of MCCB, 250 A, 3 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. |
| 80 | Supply and fix in replacement of MCCB, 160 A, 3 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. |
| 81 | Supply and fix in replacement of MCCB, 25 to 100 A, 3 Pole, 16 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description, complete all as specified and directed by Engineer-in-Charge. |
| 82 | Supply only Voltage Regulator (AVR) suitable for DG set of capacity 100 KVA to 125 KVA, complete all as specified and directed by Engineer-in-Charge. |
| 83 | Supply only Voltage Regulator (AVR) suitable for DG set of capacity 82.5/62.5/30/20 KVA, complete all as specified and directed by Engineer-in-Charge. |
| 84 | Supply only battery lead, complete all as specified and directed by Engineer-in-Charge. |
| 85 | Supply only battery terminal made of brass, complete all as specified and directed by Engineer-in-Charge. |
| 86 | Supply only Benjo bolts of suitable sizes, complete all as specified and directed by Engineer-in-Charge. |
| 87 | Supply only Radiator hose flexible suitable for the following DG sets, complete all as specified and directed by Engineer-in-Charge:- |
| 88 | 15 KVA to 30 KVA |
| 89 | 62.5 KVA to 82.5 KVA |
| 90 | 100 KVA to 125 KVA |
| 91 | 200 KVA to 250 KVA |
| 92 | 400 to 500 KVA |
| 93 | Supply only Hose plain for water pump suitable for the following DG sets, complete all as specified and directed by Engineer-in-Charge:- |
| 94 | 15 KVA to 30 KVA |
| 95 | 62.5 KVA to 82.5 KVA |
| 96 | 100 KVA to 125 KVA |
| 97 | 200 KVA to 250 KVA |
| 98 | 400 KVA to 500 KVA |
| 99 | Supply only Lube oil pressure gauge of suitable range, complete all as specified and directed by Engineer-in-Charge. |
| 100 | Supply only starter motor assembly for 100 KVA to 400 KVA, 12 / 24 volt DC, complete all as specified and directed by Engineer-in-Charge |
| 101 | Supply only A series electronic timers on delay function with time range 0.3S to 30 Min, complete all as specified and directed by Engineer-in-Charge |
| 102 | Supply only B series electronic timers adjustable cyclic function 240 Volts AC suitable for AMF panel, complete all as specified and directed by Engineer-in-Charge |
| 103 | Supply only '' ON DELAY TIMERS (for STOP/START/LOP/LOT/FAULT etc) Time range 3 sec to 30 hours contact 5 Amps 240V/12-24 volts DC, complete all as specified and directed by Engineer-in-Charge |
| 104 | Supply only HRC fuses of capacity 4-20 Amps, complete all as specified and directed by Engineer-in-Charge |
| 105 | Supply only HRC fuse cartridge assembly both base and top 20A rating, complete all as specified and directed by Engineer-in-Charge |
| 106 | Supply only indicator lamps DC filament type, complete all as specified and directed by Engineer-in-Charge |
| 107 | Supply only indicator lamps AC 230 Volt LED Type for the panel boards, complete all as specified and directed by Engineer-in-Charge |
| 108 | Supply only push button with contact element 5 A with NO-NC, complete all as specified and directed by Engineer-in-Charge |
| 109 | Supply only Selector switch for Voltmeter and Ammeter, complete all as specified and directed by Engineer-in-Charge |
| 110 | Supply only Ammeter as per sample of range 0-30/50/100 Amps AC for control/AMF panel, complete all as specified and directed by Engineer-in-Charge |
| 111 | Supply only Volt Meter as per sample of Range 0-600 Volts AC, complete all as specified and directed by Engineer-in-Charge |
| 112 | Supply only main 3P/4P contactor for AMF panel as required for 75 KVA to 100KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 113 | Supply only main 3P/4P contactor for AMF panel as required for 125 to 200KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 114 | Supply only main 3P/4P contactor for AMF panel as required for 250 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 115 | Supply only contactor(neutral control) for AMF panel, model MNX 32 of 125 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 116 | Supply only main contactor for AMF panel model TCA3-M40 of 30/45/62.5 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 117 | Supply only main contactor 4P for AMF panel model MCX 11, 50 Amps for 20/30/62.5 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 118 | Supply only contactor 4P for AMF panel model MCX 47 , 800 Amps for 400/500 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 119 | Supply only contactor 4P for AMF panel model MCX 43 , 400 Amps for 200/320 KVA DG set, complete all as specified and directed by Engineer-in-Charge |
| 120 | Supply only auxiliary /control contactors of suitable contactor(2NO, 02NC) of suitable ratings for AMF Panel, complete all as specified and directed by Engineer-in-Charge |
| 121 | S& F Battery Charging Unit (external type) 12 / 24 Volts suitable to charge batteries ranges from 80 AH to 150 AH, complete all as specified and directed by Engineer-in-Charge |
| 122 | S&F Battery charger 12 v /24 v SMPS(System main power supply) type control unit assembly fitted with AMF Panel, complete all as specified and directed by Engineer-in-Charge |
| 123 | Supply only ignition key suitable for DG set panel/control panel, complete all as specified and directed by Engineer-in-Charge |
| 124 | Supply only Energy meter 3 phase, 4 wire, 20-40 Amps range microprocessor based, complete all as specified and directed by Engineer-in-Charge |
| 125 | Supply only voltage monitoring regulator (UV, OV, SP) of suitable ratings for AMF panels, complete all as specified and directed by Engineer-in-Charge Please Enable Macros to View BoQ information |
| 126 | Supply only voltage monitoring regulator (UV, OV, SP) of suitable ratings for AMF panels, complete all as specified and directed by Engineer-in-Charge Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender