Tender for Construction Of Certain Technical Buildings And Allied Services At Af Stn Purnea Under Age (I) (Af) Purnea
BOQ
| Sl. No. | Item Description |
| 1 | BOQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CHIEF ENGINEER (AF) SHILLONG ZONE, SHILLONG. Name of Work: CONSTRUCTION OF CERTAIN TECHNICAL BUILDINGS AND ALLIED SERVICES AT AF STN PURNEA UNDER AGE (I) (AF) PURNEA Contract No: CE(AF)SZ/PUR/ OF 2026-2027 File No: 88672/CHAB/E8 Bidder Name : PRICE SCHEDULE : BOQ(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # SL No ITEM DESCRIPTION Item Code / Make QTY UNIT ESTIAMTED RATE Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE IN FIGURES TO BE ENTERED BY THE BIDDER RS. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT IN WORDS Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | Sch 'A' Part-I (BUILDING WORK)Design, Drawing & Construction of Double Entry Blast Pen with permanent specifications including RCC M-30 framed structure including motorized door, earth filling, water proofing treatment over roof, PQC flooring, joints, traverse wall and toe wall, etc complete all as specified and directed and shown on drawings.Note:- Rate for bringing approved earth, forming embankement from NGL to MGL are included in quoted Lump Sum |
| 3 | Design, Drawing & Construction of Parking shed with permanent specifications complete all as specified and directed and as shown in drawings. |
| 4 | Design, Drawing & Construction of water staging with permanent specifications complete all as specified and directed and as shown in drawings. |
| 5 | Total amount of Such 'A' Part-II (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK)Details of prepriced Schedule is given in tender documents |
| 6 | Total amount of Such 'A' Part-III (INTERNAL ELECTRIC SUPPLY)Details of prepriced Schedule is given in tender documents |
| 7 | Total amount of Such 'A' Part-IV (INTERNAL WATER SUPPLY)Details of prepriced Schedule is given in tender documents |
| 8 | Total amount of Such 'A' Part-V (TARMAC/ LINK TT)Details of prepriced Schedule is given in tender documents |
| 9 | Total amount of Such 'A' Part-VI (ROAD/PATH/CULVERT) Details of prepriced Schedule is given in tender documents |
| 10 | Total amount of Such 'A' Part-VII (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents |
| 11 | Total amount of Such 'A' Part-VIII (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents |
| 12 | Total amount of Such 'A' Part-IX (LIGHTENING PROTECTION) Details of prepriced Schedule is given in tender documents |
| 13 | Total amount of Such 'A' Part-X (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents |
| 14 | Total amount of Such 'A' Part-XI (EXTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents |
| 15 | Total amount of Such 'A' Part-XII (CCTV & LAN) Details of prepriced Schedule is given in tender documents |
| 16 | Total amount of Such 'A' Part-XIII (WATER COOLER) Details of prepriced Schedule is given in tender documents |
| 17 | SCHEDULE \\"A\\" PART -XIV (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col.' F ' signifies this fact only. |
| 18 | SITE CLEARANCE, SITE DEVELOPMENT AND EARTHWORKSupply only approved earth soil for construction of soil sub grade and shoulders approved material obtained from borrow areas outside MOD land by the contractor at his own cost, with all lifts and leads transporting to site and soil tested as per IS 2720, shall have maximum laboratory dry unit weight not less than 17.5 KN/Cum and depositing where directed complete all as specified and directed. Note:-The soil recovered/excavated shall be tested in the presence of AGE(I)/Engr-in-charge in any Govt approved lab and will be incorporated for preparation of subgrade etc, if found the soil suitable after testing) |
| 19 | INTERNAL ELECTRIFICATIONSupply and fixing Flame proof well glass type flood light 200 watt 230 V AC dimmer type in cast aluminium alloy LM6 construction with integral reflector and mounting arrangment on wall/piuller with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 20 | S&F flame proof weather proof DB TPN 415 volt 8 way with 200A bus bar and cast aluminium LM6 enclosure, operated externally spring type knob complete with M-25 cable entry to suit incoming cable and 2 Nos M-20 cable entries for outgoing cables from bottom with cable gland suitable for hazaraduous area certified by CMRS dhanbad for group II A & II B consisting of the following complete all as specified and directed :-Incoming : (a) MCB TPN 63 Amps -01 NoOutgoing : (a) MCB TP 16 Amps -01 No (For 3 Phase metal plug socket) (b) MCB SP 6-32 Amps - 24 Nos |
| 21 | S&F flame proof weather proof DB SPN 230 volt 8 way with cast aluminium LM6 enclosure, operated externally spring type knob complete with M-25 cable entry to suit incoming cable and 2 Nos M-20 cable entries for outgoing cables from bottom with cable gland suitable for hazaraduous area certified by CMRS dhanbad for group II A & II B consiting of the following complete all as specified and directed :-Incoming : (a) MCB SPN 32 Amps -01 NoOutgoing :(a) MCB SP 6-32 Amps -6 Nos |
| 22 | M&L of chemical earthing(Compound Based earthing) having advance encapsulated compound based CPRI tested maintainance free , pipe in -pipe technology upgraded( Zinc and alloy coated), Zinc coated (80-100) microns with pure zinc (99.9%) & alloy coating (200-250 microns). Earthing system confirming to IS 3034. The outer and inner pipe should be 76.2mm & 41.9 mm dia, 3 metre length, Zinc coated with additional special alloy coating 300 mm on the top side for additional protection of the terminal. The annular space between the pipes being filled up with compact fill (CF) (Crystalline conductive compound) . The compact fill (CF) mixture which is machine pressed in the pipes should not disintegrate or collapse when outer pipes corrodes. The inner pipe should be extended with terminals for connectivity. The job includes digging the pit not less than 3 metre and refilling the same by electrodite Back fill compound(Ground Enhancer), The BFC should be eco friendly , It should not contain environmentally hazardous material/metal having ROHS certification from NABL acrredited lab . The Earth pit should be provided with FRP earth pit cover for protection and safe guard of terminals with Back Fill Compound(BFC) Electrodite , 25 KG to a Bag complete all as specified and directed. |
| 23 | S&F flame proof wall fan AC single phase 230V of size 600mm with all compelte accessories. the following complete all as specified and directed |
| 24 | S&F flame proof metal plug socket 32 Amp 5 pin TPN 415 V including with cable gland with all accessories complete all as specified and directed. |
| 25 | Supply and fixing flame proof exhaust fan, steel body AC single Phase. 230V of size 300mm sweep with, blades, and frame and louvers with all accessories complete all as specified and directed. |
| 26 | Supply and fixing flame proof ceiling fans complete with blades, down rods,electronic with Flame proof regulator and complete accessories, 230 V, 1200 mm sweep and Min. air delivery 210 CFM complete all as specified and directed. |
| 27 | ROAD/PATH/CULVERT Material & Labour for dual direction road studs cat eye of impact ABS plastic/polycarbonate studs 100/100mm having ultra violet resistance colour (white, yellow & red) with plastic strips connecting to 31 mini retro reflectic glass beads of colour (white, yellow & red) to a side prov ded with steel zinc plated nail of dia 12mm and length 120mm for fixing to road surface by hammering including taking down old unserviceable studs complete all as specified and directed |
| 28 | SEWAGE DISPOSAL M&L for RCC septic tank conventional type designed to carry sewage and sullage water excavation in any type of soil, PCC 1:4:8 below foundation RCC M-30 Design mix in walls, Base slabs, Baffle walls and Roof slab incl beams etc with vent shaft, manholes opening with cover connection etc complete with effective depth of 1.50m and over all depth of 3m for 50 users complete all as specified and directed. |
| 29 | M&L for soakage wells excavation in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M-25 concrete incl intercepting chamber and screen chamber made of brick masonry in CM, RCC cover slab in M-25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 2.4m dia x 3m effictive depth complete all as specified and directed. |
| 30 | LIGHTENING PROTECTION S & F MS Junction box size 200 x 100 x 100 mm made out of 2 mm thic for mounting Test terminal block including provision of passing earth strips from top and bottom of the box complete all as specified and directed. |
| 31 | EXTERNAL WATER SUPPLY Cutting PPR/ cast iron pipes of dia 110 mm and reducing to required length before laying for insertion of Tee complete all as specified and directed. |
| 32 | Construction of Valve pit brick/stone/PCC block masonry constructed complete of size 600mm x 600mm x 600mm with mild stell sheet cover 3mm thick and angle iron frame of size 40x40x5mm duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and incl locking arrangement and lifting handle all as specified and shown on drawing. Brick/stone/PCC block work all inner surfaces of pit shall be plastered in cement mortar 1.4 complete all as specified and shown on drawing of sizes complete all as specified and directed.(Note - valve pits considered for 40 mm valves only , 25 mm valves are above ground) |
| 33 | EXTERNAL ELECTRIFICATIONSupply, installation, testing and commissioning of 11 KV Compact Substation (CSS) out door type plinth mounted, enclaving construction of Powder Coated/ Galvanised sheet steel of 2.0 mm thickness for non load bearing and 2.0 mm for load bearing partition sheets, and door with HRCA 4.00 mm base frame. The enclosure shall have IP54 degree of protection for HT< switchgear components and IP34 degree of protection for Transformer component. Each components will be provide with corrosion resistance and all side openable hinged door and lock and key arrangements. Heavy lifting lugs with all equipment's load. Necessary danger plates outside of the CSS. The compartment illumination lamp with door operated switch shall be provided for all the compartment including necessary foundation and earth work as per manufacturer's recommendation and as the site conditions complete all as specified and directed. (drawing and specifications of the foundation recommended by the manufacturer to be approved by AGE (I) before commencement of the work and the quoted rates are deemed to be inclusive of the same). The CSS is comprising of the following:- |
| 34 | HT SWITCHGEAR:-11 KV. Non-extensible 2 WAY Non- Extensable RMU compact switchgear consisting of 1 no's direct Module (LBS) and 1 No Fixed operated Manual charging & closing) 11 KV/630 Amps VCB in SF6 insulated stainless steel enclosure with series trip, self. powered microprocessors numerical over current and earth fault relay protection, HT cable/Bus Bar, and one metering module with necessary CTs and PT and digital panel mounted multifunction meter with class 1.0 accuracy, comprising the folowing.-(Complete unit is to be installed inside CSS, protection accessories, Enclosure: Metal Clad, IP-54 Protection. Protection Relay.Self Powered Alfa numeric LCD display type. Internal arc tested for 1 sec, Fully compartmentalized sheet steel enclosure withautomatic safety shutters, GI foundation bolts with provision of cable terminating facilities with powder coated smooth glossyfinish and as per follows: - |
| 35 | Rated Voltage - 12 KV, Rated Frequency - 50 Hz., Rated continuous current rating - 630 Amps., Rupturing capacity of VCB -250 MVA, Rated Interrupting Current - 21 KA., Rated making current for VCBs- 52 KA., Rated making current for Isolators - 62KA, Rated short time current for 3 sec - 21 KA, Operating duty - 0-3min-CO -3min-CO, Power frequency withstand voltage -28 KV, Impulse withstand voltage - 75 KV Busbar rating - 120% of continuous current., Operation: Spring closing mechanism -DC motor operated with 24-volt supply, Breaker Closing - Manual & Electrical through TNG switch., Shunt Trip coil - 24 V DC,Safety Interlock Locking faciality - Required. Breaker panel indication - ON (Red) OFF (Green)Accessories: 1 No. Self Powered Relay P3U20-6AAA2AHAA, Mechanical counter, Space Heater with Thermostat, Fuse and ON/OFF Switch, Aux relays for remote trip/indication for PC interface etc, cubicle illumination lamp LED 10 watt retrofit type 230 VAC, T-N Switch, Anti pumping contractor etc. In addition to the above all standard fittings to be provided as per IS Norms Mimic Diagram: An operating mimic diagram shall be provided on the front side of each cubicle.Note: - Circuit breaker complete wil be obtained directly from the OEM and not from the authorised system assemblers of OEM.The installations, calibration and testing of SF-6 circuit breakers will be conducted in the presence of authorised representative ofOEM by the OEM Contractor. Battery bank of minimum 30 min backup with charger for RMU is included in the item rate and rating of battery as described by OEM. |
| 36 | 11KV/0.433KV OIL TYPE TRANSFORMER OF 100KVAOil filed Type 3 phase, 50 Hz, Dynt1/ONAN type Sealed Copper wound Transformer with OFF Load Tap Changing Arangement on HV side in steps of 2.5%, 45% 10 -10% having cable end boxes on HV side suitable for 3 Crore X 95 Sq mm XLPE cable of 11 KV grade of HT side and Busduct in LV side complete with all accessories like buchhloz relay,oil temp indication,winding temp indication and alarm etc preferbly DMCR protection relay i/c first filling of filtered dehydrated class natural Ester oil bio transol (as per IS 16659) and confirming to IS 1180 andlosses shall be as energy efficiency Level -3 only and 100% load with an impedence of 6.25% Ic as per specification below complete in all respect as required at site.Design ambient to be considered a s 5 0 Deg C.All the balance parameter like temp rise,basic insulation level,flux denesity etc shall be strictly in accorgance with IS 1180 Part -1 only. Heat run test is the mandotary test for Transformer Standard the equipment shall be conform to the latest edition of applicable standards as folows. In case of conflict between aplicable standards and this specification, this • I S 1180 Standard for Oil filled Transformeraccordance with IS conflict between aplicable standards and this specification shall govern. * I S 1180 Standard for Oil filled Transformer* IS: 3639 for Fitings and Acesories* IS 209 for Bushings > 1000 V* IS 7421 for Bushings < 10 V* IS:1271 for Electrical Insulation classified by Thermal stability- IEC 6270 Natural Ester Oil* CBIP Guidelines, ol Insulation clas: K class. It should also exhibit safety against fire hazards |
| 37 | CORE: Transformer shall be double wound, core type with low loss, non-ageing, high permeability PRIMEGRADE, CRGO with M4 Grade or Better, perfectly insulated and clamped to minimize noise and vibrations. Folowings should be Mandatory for any manufacturer. -a. Transformer shall be of BOLTLESS core designb. Core shal b e purchased Directly from Manufacturer or from their accredited MaCORE: Transformer shall be double wound. core type with low loss, non-ageing, high permeabilityPRIMEGRADE, CRGO with M4. Grade or Better, perfectly insulated and clamped to minimize noise and vibrations. FolowingsManufacturer's name during bidding having sufficient credential Transformer manufacturer should have in-house core cutting facilities for proper control & monitoring of quality & to avoid mixong of Prime core with Second grade /defective core materiats. Transformer Manufacturer should have in-house siting Machine so that core is cut to width & stacked with minimum air gap thus ensuring Burr level less than 10Microns. Core shall be procured from one of these reputed Manufacturers - Posco / Nippon/ Novex! Ak Steels. The insulation structure for the core to bolts and core to clamp plates shal be such as to withstand a voltage of 2000V for one minute, Transformer must necessarily have BIS certification,BEE starlabeling and valid type test report duly isued by NABL accredited BIS approved lab. |
| 38 | LT Panel LT panel- Separate compartment for LT network inside the CSS made with 2.0mm CRCA sheet with necessary angle iron frame. dust and vermin proof, with separate openable door for LT side with necessary locking arrangement, opening for LT AL Busbar 400 Amp /cable entry, opening for natural air ventilation/cooling, necessary suitable range of panel mounting Multifunction Meter (6400NG), CTs etc as required with ACB 4 pole Icu=Ics=Icw(1sec) = 50KA @ 440V AC 50 Hz of breaking capacity 50KA, with EDO type, Microprocessor based overcurrent, short-circuit and earth fault release of capacity 250 Amps -01 Nos (Main incomer of LT) and including the followings LT distribution (i.e. LT out going).LT Outgoing: - (i) MCCB 4 pole 415-volt 50 Hz of breaking capacity 25 KA, 100 Amps, Ics=100% Icu TMD overload and short circuit protection with Encapsulated double break roto technique ensures outstanding current limiting capability - 3 Nos. (ii) MCCB 4 pole 415-volt 50 z of breaking capacity 16KA, 63 Amps, Ics=100% Icu TMD overload and short circuit protectior with Encapsulated double break roto technique ensures outstanding current limiting capability - 3, Nos. (iii) MCCB 4 pole 415-volt 50 Hz of breaking capacity 16KA, 32 Amps, Ics=100% Icu TMD overload and short circuit protection with Encapsulated double break roto technique ensures outstanding current limiting capability - 3 Nos. (iv) MCB SPN 230V fixed with 32 A 10KA -01 (v) Fix time switvhes astro type three phase 430 V 32 Amp rating-01 |
| 39 | M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 40 | M & L for cable junction box with IP 66 protection (halogen free and weather proof) for outdoor installations of size 155 x 210 x 92 mm with terminals including SP MCB of 6 A, gland for cable, FI clamp of size 20x3 mm, nuts, bolts, washers, provision of connectors for connection of cables etc complete all as specified and directed. |
| 41 | Supply & fix LED aviation obstruction light, Die-cast aluminum housing with Red polycarbonate dome for better illumination with integral driver and IP 66 Protection complete all as specified and directed. |
| 42 | Design, Fabrication, Testing & Commissioning of Varmin dust proof LT Feerder Pillar board outdoor type of Al Bus bar 400 Amp rating made out of MS sheet 3.15 mm thick, Type tested conforming to IEC 61439, powder coated , rear and front operated door with locking arrangement , suitable aluminium busbar and fixed on angle iron base suitable for pedastal mounting of size 50x50x5 mm at least 2 feet above GL to accomodating the following complete all as specified and directed. :- INCOMING :- (a) MCCB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 250 Amps - 01(in coming) (b) Digital VAF metre and Indication lamp R,Y and B OUTGOING :-(b) MCCB 4 Pole, 415 V, Adjustable type, 32 Amps with breaking capacity 16 KA - 02 No. (VTPN DB of Annex RS and Spare)(c) MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity 16 KA - 02 No. (VTPN DB of Annex LS and Spare)(d) MCCB 4 Pole, 415 V, fixed type, 63 Amps with breaking capacity 16 KA No-1 (motorized door Panel) (e) MCCB 4 Pole, 415 V, fixed type, 32 Amps with breaking capacity 16 KA No-1(Flood light And Street light) (f) MCB SPN Pole, 415 V, fixed type, 32 Amps with breaking capacity 10 KA No-1(Veh Parking Shed) (g) Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class (h) Fix time switches astro type (Having longitude and latitude of Indian cities in memory) 440 V three phase of 32 Amp rating with contactor fitted inside steel enclosure. Note : The rate quoted by the contractor is deemed to be inclusive of all material mentioned from sl no (a) to (h) and P.C.C foundation as per manufacturer's instructions etc complete all as specified and directed. |
| 43 | M/L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level connected to galvanised iron strip 32×6mm upto 7.5 m by means of bolts nuts, check nut and washers , earthing strip shall be protected by 32 mm bore light grade galvanised iron pipe and other end conneted to earthing test point including funnel with watering pipe of 20 mm bore light grade galvanised iron pipe, wire mesh, charcoal or coke and common salt in alternate layer of 15 cm(compacted thickness) all around the earthe electrode with concrete earth pit in PCC (1:3:6) typeC 1, cast iron frame, pre cast RCC (1:2:4) type B1 cover slab 400 x 400 x 50 mm set in CM 1:4 reinforced with 8 mm dia TMT bar 10 cm C/C with one handle for lifting made out of 10 mm dia MS round bar, includingnecessary excavation earth work and disposal of soil to a distance n exc 50 m and necessary testing complete all as specified and directed Electrical plate no 3 of SSR Part-I.complete all as specified and as directed.NOTE:- Earth lead and 20mm dia GI protetion pipe upto 7.50 m length shall be measured in this item. |
| 44 | M&L for Earthing complete with GI earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI wire 4 mm dia earth lead by means of nuts, bolts, check nuts, washers of galvanized iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 45 x 45 x 5cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed (GI strip upto 7.5m including testing is deemed included in the item ). |
| 45 | DG SETSupply and installation of silent Diesel Engine driven generating set of capacity 100 KVA 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB- IV (CENTRAL POLLUTION CONTROL BOARD) norms and foundation etc, in addition to the details as listed below complete all as specified and as directed :-a) Fly wheel to suit flexible coupling.b) Flexile coupling with guards.c) Dry type air cleaners with filters.d) Lubricating oil filter, fuel filter, fuel pre filter.e) Anti-vibration pads-quantity and type as OEM recommended by manufacturer.f) Fuel injection system with injector pump, nozzles, governor(electronic) of suitable capacity.g) Electric start equipment.h) Lead acid storage maintenance free battery 2x12V DC of suitable rating with charging alternator, ammeter, as recommended by manufacturers make: As per OEM standard along with copper battery lead and connector.i) Battery rack made out of MS angle iron 40mmX40mmX5mm and 150mm height.j) Standard safety device. |
| 46 | k) Daily service fuel tank of suitable capacity for running 24 hrs non-stop on Full Load with mechanical oil level indicator, detachable strainer, drain cock, fuel outlet, air vent and locking arrangement etc, including fuel pipe connections.l) Exhaust silencer(Residential silencer) with exhaust piping of suitable size brought out side on top of size 76.5 mm dia and complete length of silencer and exhaust piping continuously wrapped with 12 mm dia asbestos rope and suitable anti vibration arrangement around pipe passing through wall. m) LCD display type control panel as per manufacturer's instructions indicating KWH, KVA, PF, Volts, Amps, Hz, RPM, Hour, Oil pressure, Oil temprature, coolent temprature, fuel level, battery charging ammeter, battery charging lamp and incator lamp (RYB), panel duly prewired and displaying protection and safetys as under:- aa) Protection:- short circuit, overload, over speed, earth fault as standard and reverse power as optional.ab) Safeties:- Auto shut down, visual & audio alarm for low lub oil pressure, high coolant temperature, low fuel level, canopy temperature & radiator water level. |
| 47 | (B) Alternator :100 KVA brushless type at 0.8 power factor, self regulated, self excited, screen protected 3 phase with neutral 415 volts 50 HZ, 1500 RPM, as per IS:13364/IS-4722 complete with automatic voltage regulator, having voltage regulation +/-1%, SPDP enclosure including making cable connections, insulation class-H and alternator control panel as supplied by manufacturer.C) Base frame sturdy, MS fabricated, channel iron base frame for mounting the engine & alternator with anti vibration pads.(D) Acoustics enclosure of suitable size to accommodate DG set 100 KVA, modular construction, fabricated out of 3 mm thick, cold annealed CRCA sheet duly epoxy painted doors to be provided with high quality EDPN gasket, duly epoxy painted. The canopy to be equipped with heavy duty fans of reputed manufacturer for air circulation and cooling the canopy. Rock wool of requisite density per Kg/m3 to be used for insulation. Enclosure to be provided with one light point controlled with one switch for internal lighting. Noise level at one meter to be 75 decibels @ one meter in line as per latest CPCB norms. |
| 48 | NOTE:- (i) The engine of DG set suitably conditioned to suit the all climatic condition, so as to give desire outputs including and testing up to 110% over load.(ii) The DG sets shall be placed as per OEM recommendation platform. (iii) The items required for testing (initial and IEM) of DG set e.g. fuel, tripod, tools, water tank etc and panel as below shall be deemed quated rate by the contractor and the rate of which to be included in the rate of item. (iv) DG set to be carried out by rep of accepting officer factory testing. |
| 49 | M&L for Earthing complete with copper earth plate electrode of size 600x600x3.15 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to 20×3mm copper strip as earth lead by means of nuts, bolts, check nuts, washers of galvanized iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed. (copper strip upto 7.5m including testing consider in this item). |
| 50 | AIR CONDITIONING Supply and fix explosion Proof Split Type Air Conditioner Unit. Suitable for 1.5 TR Operating voltage supply 230V/AC, 50Hz Certified by CIMFR Dhanbad or PESO (Nagpur) and cosisting following complete all as specified and directed :- (A) Condensing Unit :To be kept in hazardous area along with Emerson make hermetically sealed Explosion proof compressor R407 C, Eco-Friendly.Condensing Moto, Condensing Coil made up of Aluminium blue fins duly coated with Specialist chemical to prevent Refrigerant leakage.GI/SS304 Enclosure will be used to integrate the components of Conditioner Unit. |
| 51 | (B) Cooling Unit :Indoor Wall mounted Unit to be kept in hazardous area of split type cooling unit. Cooling Motor, Condensing coil with Copper tubes and Aluminium blue fins duly coated with specialist chemical to prevent refrigerant leakage.SS304 Cabinet will be used to integrate the components of cooling unit.(C) Flameproof Control Panel :RYB 230 VAC – 3 nos. (Power ON, Compressor ON, Cooling motor ON, With temperature indicator, 2 relay output, FLP RTD PT100 3wire.Switch/MCB, Contactor & Overload relay for protection compressor and condensing motor cooling motor as suitable Incomer MCB will be provided. Classification Area -- Zone I & II, Gas Groups IIA IIB,IIC with Dustprotection Zone 21 & 22.(D) Drain pipe,copper pipe with insulation,wall hole and surface finishing is deemed to be included in the quoted rate by contractor. |
| 52 | FIRE FIGHTING Supply and fix Fire Extinguisher CO2 type (light weight squeeze grip type) stored pressure MS RED Portable capacity 4.5 Kg as per IS: 2190/15683 complete all as specified and directed. |
| 53 | S&F Cable Junction Box 200X160X98mm in size, made out of thermoplastic sheet having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos polymide gland with check nut (M-32 - 2 nos) fixed on poles with flat aluminium clamps of size 25x3mm, nuts, bolts, washers etc. complete all as specified and as directed. |
| 54 | Supply and fixing of Automatic Street light Switch using NATURE SWITCH for automatic switching of street lights based on LUX level of Natural light. The sensor (nature switch) along with suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable Enclosure made of rust proof , electric shock proof termite proof and FR grade special moulding compound (Sintex make SMC junction box ) conforming to IP54. The contactor MCB and circuit wiring should suitable enough to take load of 12KW equally distributed over 3-phase (4KW/Phase). Contactor rating 40 Amps(SP 3 Nos ). Wiring main load with 6sqmm copper conductor FR grade cable complete all as specified and directed. |
| 55 | Supply & fixing post top luminaire LED type of 25 W of with IP 65 protection with die cast aluminium graphite grey powder coated finished body , polycarbonate opal diffuser, low power warm white (WW) LEDs with better heat dissipation, high efficient constant current electronic driver having operating voltage range from 140 to 280 Volt AC, provided with high voltage, open and short circuit protection, Voltage surge protection 10 KV etc complete including suitable size loop in loop out boxes & flexible 3 core 1.5 Sqmm copper connecting cable from loop in loop out box to fitting etc complete all as specified and directed. |
| 56 | Supply and fixing single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of capacity 20A complete all as specified and as directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 19, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysAug 21, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender