Tender For Name Of Work:-A/R & maintenance of Lift Water Supply Scheme To Dr. Rajinder Prasad Medical College Tanda In In Teshil Nagrota Bagwan Distt. Kangra (H.P). (Sub Head:- Providing, Laying, Jointing And Testing Of Mserw Pipe 300Mm Dia From Main
Tender Overview
Project Description
Tender for Name Of Work:-A/R & maintenance of Lift Water Supply Scheme To Dr. Rajinder Prasad Medical College Tanda In In Teshil Nagrota Bagwan Distt. Kangra (H.P). (Sub Head:- Providing, Laying, Jointing And Testing Of Mserw Pipe 300Mm Dia From Main Overhead Tank At Rd 0 To 250 = 250 Rmt Due To Construction Of Lecture Theater Building.)
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in foundation and trenches (for pipes and pits) up to all depths and in all clasification of earth work such as pick Work, jumper work, chiselling or Wedging out of soft and hard rock where the blasting work is prohibited saturated soil including pumping or bailing out water in all lifts including trimming and dressng of sides, levelling of beds to correct grade including shoring strutting planking timbering and dewatering where ever required. Stacking usable and unusable matrial/soil separetaly and after laying, jointing and testing of pipes (for pipes, pipe duct, chambers, x-signs etc.) returning the usable soil in 15 cm layers by ramming and wetering and then desposing of all surlus excavated soil/un usable material as directed wirhin all leads/lifts includng restoration of unmetalled surfaces to its original conditionn and includng cost of divresion for traffic, night signal boards, fixing custion boards, crossing over tranches for access to houses, fencing etc. complete in all respect as per the direction and to be entire of Engineer-in-Charge within all leads and lifts. (Pick work & jumper work) |
| 2 | Providing, laying, jointing & testing of bevelled ended MSERW pipe (Zinc Coated) 4.80mm thick with MS Flange (6%) Table-5 and other pipe (94%) with circumfrential butt welded joints by electrical arc welding ( welding thickness shall be equal to pipe wall thickness) and testing of pipe of Jindal/Surya Roshni/Tata/AST make of following dia meters conforming to IS/ISO 3183:2007 with steel grade L-210 or A, having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers , all short pieces, bends etc. as per site requirement made from parent tubes . The laying of pipe shall include all operations such as cutting, welding, jointing, fabrication of bends, tees, making bevelled pipe ends suitable for butt welding , lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (Earth work in trenches and the cost of providing and welding flanges i/c nut & bolts, gasket will be measured and paid for separately) . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes ( If damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing of pipes, D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts. |
| 3 | 300mm dia |
| 4 | Providing and Fixing of double flanged Cast iron Sluice Valve of following dia Leader/Kirlosker Make (with hand wheel) PN-1.6 as per BIS Code-14846-2000 with standing nominal seat pressure latest upto date ammendments and it shall also include carriage of materials complete in all respect as per the direction and to the entire satisfication of Engineer-in-Charge within all leads and lifts. |
| 5 | 300mm dia |
| 6 | Providing and replacement of double flanged Cast iron Non Return Valve of following dia Leader/Kirloskar make PN-1.6 as per IS Code-5312-2000 with standing nominal seat pressure latest upto date ammendments and it shall also include carriage of materials complete in all respect as per the direction and to the entire satisfication of Engineer-in-Charge within all leads and lifts. |
| 7 | 300mm dia Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
TodayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender