Tender For special Repair / Replacement Of Ht Feeder Including Replacement Of Isolater, Light Protection Earthing And Connected Works From Ramnagar Substation To Samnabanj, Rc Peak, Battal Node Under Ge (Army) Dhar Road Udh Ur
Tender Overview
Project Description
Tender for special Repair / Replacement Of Ht Feeder Including Replacement Of Isolater, Light Protection Earthing And Connected Works From Ramnagar Substation To Samnabanj, Rc Peak, Battal Node Under Ge (Army) Dhar Road Udh Ur
BOQ
| Sl. No. | Item Description |
| 1 | BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER, UDHAMPUR Name of Work: SPL REPAIR / REPLACEMENT OF HT FEEDER INCLUDING REPLACEMENT OF ISOLATER, LIGHT PROTECTION EARTHING AND CONNECTED WORKS FROM RAMNAGAR SUBSTATION TO SAMNABANJ, RC PEAK, BATTAL NODE UNDER GE (ARMY) DHAR ROAD UDHAMPUR Contract No: CWE/U(DR)-57 /2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint indoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm, including taking the old unserviceable joint kit, complete all as specified and directed |
| 3 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm, including taking the old unserviceable joint kit, complete all as specified and directed |
| 4 | Cable jointing kit for 11 KV (Earthed) grade cable for heat shrinkable straight through joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm including taking the old unserviceable joint kit, complete, all as specified and directed. |
| 5 | Supply & fixing switch air break gang operated, vertical type triple pole, mechanically operated, mounted on insulator and steel frame with operating machanism worked from ground level using heavy duty GI pipe, for current rating 200 Amp, outdoor type (conforming to IS specifications) HT 11 KV, triple pole with fixed contacts of phosphorous and bronze and a set of drop out HT fuse assembly, fuse carrier fitting, 12 insulator type mounted on MS channel operating rod with pad lock arrangement complete all as specified. |
| 6 | Routine and periodical work required for trimming / cutting of tree branches of any girth, touching /obstructing the over head lines of HT poles of three phase distribution system at places not more than 40 mtr span distance so as to keep minimum 2.0 mtr clearance all around the lines and poles with due care after taking proper electric shoutdown from concern MES competent staff complete disposal thereof ( trimmed branches) to a distance not exceeding 100 metre , complete all as specified and directed. |
| 7 | M&L for preparing scraping the old painted surfaces and applying two coat of aluminium paint on steel tubular swaged poles 11 mtrs long steel and swan neck /bracked, chanels/angles including making/pasting three nos cricular strips of 300 mm wide yellow & black colour with synthetic reflected enamel paint and marking /stencil writing of pole numbers with black paint complete and all as specified and directed |
| 8 | Excavation in trenches, n exc 1.5 m wide and n.exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, and for laying of cable or pipes etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil, complete all as specified and as directed. |
| 9 | All as per item No. 07 above but depth exceeding 1.5m and not exceeding 3m complete all as specified and as directed. |
| 10 | Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil,complete all as specified and as directed. |
| 11 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and as directed. |
| 12 | Material and labour for laying Precast reinforced concrete cable cover class HV, TYPE 2 with peak, size 450mmx180mmx40mm complete all as specified and as directed |
| 13 | Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed by Engr-in-Charge. NOTE :- For payment purpose punned thickness shall be measured . |
| 14 | Supply and laying double wall corrugated pipe (DWC) confirming to IS 14930 Part-I of size 120 mm outer dia and 103.5 mm inner dia icnluding taking down unsv old one all as directed. |
| 15 | 80 mm bore galvanised steel water tubing medium grade (ISI Marked) with and including all fittings and fixed complete Roads/Poles and or laid in trenches complete all as specified and as directed. |
| 16 | Earth continuity conductor or main earthing lead fixed wall on batten or recess or chases or brried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing as required 32mm x6mm dia galvanised iron steel strip complete all as specified and as directed. |
| 17 | Supply , laying and testing and commissiong of HT Cable XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable ( heavy duty) with aluminium conductor , 11000 volts earthed grade cross sectional area 120 Sqmm 3 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles, complete all as specified and directed. |
| 18 | Taking down old unserviceable lightening arrestor 11 KV , complete all as specified and directed. |
| 19 | Supply and fixing lightning arrestors gapless metal oxide type complete with all fittings, suitable for 11000 volts grade transmission class, discharge capacity 65 KA including brackets, clamps, nuts, washers and connecting to 4 mm dia GI earth wire complete all as specefied and directed. |
| 20 | Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and as directed. |
| 21 | Material and labour for making test point for lightning arrestor by providing of four numbers procelain insulator fixed on wall through rowal plug, rectangular block of size 75mmx75mmx25mm made of phosphorus bronze or gun metal mounted over the insulator in horizontal shape, connecting the earth strip and down lightning conductor with the help of copper or brass nuts, washers over the phosphorus bronze blockincluding material and labour for making enclosure for test point made of mild steel steet of 1.6mm thick of size 250mmx250mmx250mm in box shape, openable from front side with locking arrangement,handle etc mounted/grouted into wall covering to the test point all as specified and directed at site incl taking down old one . |
| 22 | Disc type insulator porcelain vitreous white brown or green as per IS 731-1963 of size 145 mm high and 255mm dia ball & socketed type single disc with tension clamp for working pressure 11000 volts complete all as specified and directed. |
| 23 | Pin Type, Porcelain vitreous, White, brown insulator of size 150 mm height, 150 mm dia for 11000 volts grade including one galvanised mild steel spindle , two galvanised iron washers and one galvanised iron nut in replacement, complete all as specified and directed. |
| 24 | Stay Assembly using stay rod of 16mm dia complete with galvanized stay strand of size 7/4mm & accessories as shown in Electrical Plate No 1 of SSR 1991 Part-I, complete all as specified (loop type insulator, stay clamp, earth work and PCC shall be measured and paid for separately) |
| 25 | S&F in replacement of stay wire using galvanised steel strand of 7/3.15mm complete with necessary binding incl dismentling taking down unserviceable one complete all as specified and directed. |
| 26 | Dismantaling anti clambing device barbed wire complete all as specified and directed |
| 27 | M&L in replacement for Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered complete all as specified and directed by the Engineer-in-Charge. (clamps measured separately) |
| 28 | Removing/dismantling Old UNSV pole and Supplying, transporting, erecting and fixing up steel tubular swaged pole overall height 11 mtrs type 410 SP 55 complete with cast iron base plate pole cap finial taper plag bolt nut washer etc including painting with two coats of Aluminum paint over one coat of red oxide primer including 3 No bent /strips with post office red/yellow colour ( 300 mm wide each) synthetic enamel paint at a distance 300 mm from plinth block and marking pole No with black synthetic enameled paint including tarring one coat on steel surface emmbedded in concrete complete all as specified and directed by the Engineer-in-Charge. |
| 29 | Plain cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregates as in coping, benching and similar work etc including necessary form work complete all as specified and as directed. |
| 30 | Plain cement concrete 1:4:8 type D-2 using 40mm graded crushed stone aggregates as in foundation for pole or any other work, complete all as specified and as directed. |
| 31 | Material & labour danger notice plate of 1.6 mm thick mild steel sheet vitres enameled , white with letter ( in English & Hindi ) Figured & conversional “Skull & Bone” in signal red colour & fixed with MS clamps bolt & nuts of approved size 25 X 20 cm for 11000 Volts, complete all as specified and directed. |
| 32 | Dismentling and taking down old/unsv cross arms, bracing, supports etc complete all as specified and directed |
| 33 | M & L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections ( flat, angle, channel) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide primer, one under coat and one finishing coat of aluminium paint, complete all as specified and directed. |
| 34 | Supplying and laying synthetic rubber insulated mats 2.5mm thick for voltage upto 11kv for electrical purpose as per IS 15652-2006 suitable for electrical shock safety of size 2mtr x 1mtr complete all as specified and directed. |
| 35 | Dismetling and taking down old/unsv ACSR conductor any size complete all as specified and directed. |
| 36 | S&F ACSR conductor incl jointing with existing conductor and strengthning on LT pole and proper fastening to pin/shackle insulators with aluminium binding wires and required jumpering connection complete all as specified and directed.Note :- Size of aluminium conductor as per site requirement will be directed by Engineer-in-Charge. |
| 37 | Material and labour cutting road/path way (concrete) any type including execavation returning in spreading, leveling, well ramming in layers, soiling with stones, WBM 7.5 CM thick and laying permix carpet 25mm thick using ready mix patch mate material, including rolling and compection of path work complete all as directed. |
| 38 | Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6.00mm thick burried directly in ground (earth pit not less than 2.25 meter deep below normal ground level with top edge of earth plate not less than 1.5 m below the normal ground level) connected to galvanised iron strip 25 x 4mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in elelctrical plalte No 3 including charcoal dust, commen salt, 20mm bore GI medium grade watering pipe, 40mm dia GI light grade protection pipe with funel and wire mesh, PCC Pit in 1:2:4 type B 1 using 20mm graded stone aggregate with angle iron 40x40x5mm frame, RCC pit cover of suitable size complete all as specified and directed by engineer encharge and testing for required value complete. Note :- (i) Item include the cost of earth lead and GI protection pipe upto 7.5 mtr length. (ii) On completion of Earthing Contractor should check Earthing Results and submit the Test Report to Engr-in-charge. If desired results are not obtained then Earthing shall be redone by the contractor at his own cost. |
| 39 | Earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized iron(GI) wire of size 4mm dia as earth continity conductor or main earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40 x 40 x 5 mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by the Engineer-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. Total in Figures 0.0 0.0 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 15 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender