Tender For Operation Of electrical installation And Fans Including Compound Light, Dg Set, Water Supply And Dewatering System, Fire Fighting And Sprinkler System, Lifts, Fire Alarm And Pa System At Old Age Home, Kanti Nagar, Delhi Under Pwd Sub Divis
Tender Overview
Project Description
Tender for Operation Of electrical installation And Fans Including Compound Light, Dg Set, Water Supply And Dewatering System, Fire Fighting And Sprinkler System, Lifts, Fire Alarm And Pa System At Old Age Home, Kanti Nagar, Delhi Under Pwd Sub Division-3/M2533 Shahdara Delhi.
BOQ
| Sl. No. | Item Description |
| 1 | Providing services of the qualified and experienced staff for operation of DG Set, fresh water pump sets and attending day to day electrical complaints i/c maintenance & repair/cleaning of electrical installation such as ceiling fan, exhaust fan, tube light fitting, lamp holder, electrical main board, sub-distribution board, earthing, compound lights etc. on all working days including Sunday and Gazetted / National Holidays in three shifts from (6AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM ) round the clock by employing following minimum staff as per terms & conditions and scope of work attached. (a) Wireman cum pump operator - 3 nos. |
| 2 | Providing Services of the experienced staff for day-to-day maintenance & upkeep of electrical installations for assisting the wireman cum pump operator for up keeping all the electrical installation i/c cleaning the pump house & electrical panel room/enquiry on all working days including Sunday and Gazetted / National Holidays in general shifts from (9AM to 5 PM) by employing following minimum staff as per terms & conditions and scope of work attached.(a) Khallasi - 1 no. |
| 3 | Providing services of the qualified and experienced staff for operation of Fire Alarm/fire fighting system installed at Old age home Kanti Nagar, Delhi round the clock in three shifts (6AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM) on all the days of the week (including Sunday and Holidays) etc. i/c cleaning of all system and operating the system in case of any emergency and attending false alarm (if any) complete as required and as per terms & conditions attached. (a) Fire Attendant – 3 Nos. |
| 4 | Providing services of the qualified and experienced staff for operation of CCTV surveillance system installed at Old age home Kanti Nagar, Delhi in general shift (9AM to 5 PM) on all the days of the week (including Sunday and Holidays) etc. i/c cleaning of all CCTV equipment’s etc. complete as required and as per terms & conditions attached. (a) CCTV Operator – 1 No. |
| 5 | Operation of 2 Nos., 10 Passengers capacity Johnson make lifts in two shifts (6AM to 2 PM & 2 PM to 10 PM) on all the days of the week (including Sunday and Holidays) etc. including cleaning the lift car and up keeping the system healthy and acting as a resue person in case any person gets stuck in the lift car and as per terms and conditions & inventory and duty staff details attach. (a) Lift Operator – 2 Nos. |
| 6 | Annual Comprehensive maintenance of conventional type Fire Alarm system with complete cabling work installed in the building with following inventory:- a) Main Panel - 1 no.b) MCB (ABS body) - 12 nos.c) Wall/ Ceiling mounted speakers - 58 nos. |
| 7 | Annual Comprehensive maintenance of IP based CCTV system with complete cabling work installed in the building with following inventory:-a) 3 MP IP Bullet camera - 14 nos. b) 3 MP IP Dome camera - 14 nos. c) IP PTZ camera - 1 no. d) 64 Channel NVR - 1 no.e) NVMMS- 1 no.f) 8 port POE switch - 2 nos.g) 24 port POE switch - 1 no. h) 42 inch Fully HD display - 1 no. i) Rack mounted work station - 1 no.j) 9U wall mounted Rack - 3 nos. |
| 8 | Comprehensive running maintenance and servicing of WTAC/STAC (1.0/1.5/2.0) TR)/ Water Coolers & RO of different makes and models installed at various places including labour change and replacement of all defective minor parts i/c supplying and charging of R-410A/R-22 refrigerant gas in the compressor in case of leakage (Except replacement of compressor) i/c checking the units oiling, greasing, chemical cleaning of condenser coil, cooling coil i/c replacement of defective parts, Air Filter, running capacitor, starting capacitor, starting relay, thermostat switch, wiring kit, 15/20 Amp Plug tip/Industrial socket, flexible wire and tightening the loose connection, complete as required. |
| 9 | For Summer Season 18 Nos. for 8 Months |
| 10 | Comprehensive maintenance of 02 nos. 10 Passenger (680 kg) in Old age home at kanti nagar, Shanti Mohalla, Gandhi Nagar, Delhi i/c servicing routine checkup of all installations, safety device, alarm system and other accessories applicable i/c rectifying of day to day complaints etc. as required. |
| 11 | Supply and replacing following material of 10 Passenger (680 kg) (Make - Johnson) (Labour cost shall not be paid as it is covered in AMC.) |
| 12 | Lift no. 1 Ref no. QTN20260500018 |
| 13 | Lift no. 2 Ref no. QTN20260500019 |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 15 | 5/6 amps switch |
| 16 | 15/16 amp switch |
| 17 | 3 pin 5/6 amp socket outlet |
| 18 | 6 pin 15/16 amp socket outlet |
| 19 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 20 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 21 | 18- 22 watt |
| 22 | LED Street light fixture, powder coated pressure die cast aluminum body (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/ 6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 23 | 150 watt |
| 24 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy ≥120 and <135 lm/Watt)Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 25 | 200 Watt |
| 26 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 27 | Supplying, installation, testing and commissioning of heavy duty exhaust fan of 300 mm sweep, 900 RPM confirming to IS 2312/67 complete with louvers and frames in the existing opening including making the hole to suit the size of the above fan, making good the damage, connections, earthing etc. as required. |
| 28 | Online UPS - Input supply: Single Phase, Output Supply: Single Phase.Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion(ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. .........................Cont.............................. |
| 29 | Operating temperature 0 to 40 0C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge, 10 KV surge. Display for watt/VA, Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3). The UPS should be with IGBT Based Inverter Technology, Communication RS232/ RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc.2KVA |
| 30 | Supplying, Installation, Testing and Commissioning following capacity Surveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications.8TB (Terabytes) |
| 31 | S.I.T.C of 5 HP, Submersible pump set minimum 8 Stage outlet size 50mm suitable for 420 volt, Three phase, 50 HZ Ac supply, with help of chain pully block and tripot stand etc. complete as reqd. (Make- Kirloskar/Crompton/KSB/Wilo Equivalent |
| 32 | Supplying and replacement of compressors of following capacities in the split type AC units/WTAC units/ Water Coolers i/c charging the gas, piping (upto 2 mtr) etc. complete as required i/c buy back of credit on dismantled material, testing and commissioning etc. complete as required. |
| 33 | 2.0 T.R. capacity |
| 34 | Repairing of defective inverter type PCB 1.5/2.0 TR capacity STAC testing & commissioning etc. complete as reqd. |
| 35 | Supplying and replacement of Cooling Coil of 1.0/1.5/2.0 TR capacity WTAC/STAC i/c dismantling of defective coil testing & commissioning etc. complete as required. i/c buy back of credit on dismantled material, testing and commissioning etc. complete as required. |
| 36 | Split AC |
| 37 | SITC of Copper wound Automatic Voltage Stabilizer suitable for 2 TR capacity Air Conditioner with High/ Low Voltage trip and time delay relay, input voltage 170-270 Volts etc. as required. |
| 38 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 39 | Servicing/overhauling the desert/room coolers, checking the unit, changing the wood wool pads, distributor of water, elbow, PVC pipe of required length, Balde, oiling of Blower motor, fixing missing nuts, bolts, screws etc. providing necessary insulation tape etc. on wire joints, reinstallation of Desert Coolers to its original position, testing, commissioning etc. complete as required. |
| 40 | Supply & Replacement of Cooler Pump in the existing Desert Cooler etc. complete as required. |
| 41 | Supply & Replacement of burnt out Cooler Motor single phase motor in existing desert coolers i/c testing commissioning etc. as required. |
| 42 | Less of Account of buy back of following dismantled material |
| 43 | Automatic Voltage Stabilizer suitable for 2 TR capacity |
| 44 | Cooler Motor single phase |
| 45 | Cooler Pump Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender